Plan Review Details - Permit 01030146
Plan Review Stops For Permit 01030146
Review Stop P PLUMBING
Rev No 3 Status P Date 2001-04-16 Cont ID  
Sent By ndenmark Date 2001-04-16 Time 08:36 Rev Time 0.50
Received By ndenmark Date 2001-04-16 Time 08:36 Sent To  
Notes
2001-04-16 00:00:00PROVISO:
 INSPECTIONS WILL BE PERFORMED UNDER THE
 1999 REVISION OF NFPA 99C
 STATE ADOPTED VERSION IN OCTOBER OF 2000

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-03-30 Cont ID  
Sent By pschmitz Date 2001-03-30 Time 08:39 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-03-30 00:00:00MEDICAL GAS PLAN REVIEW 2ND TIME DENIED.
 RESPONSE TO COMMENTS FROM OG&P 03-21-01
 PLEASE ADDRESS COMMENTS DATED 03-20-01
 (1) USE CURRENT EDITION OF NFPA-99-C
 1999 EDITION.
 (2) SHTS P-7/S NOT INCLUDED.
 )3) ALL INFORMATION PERTANING TO MEDICAL
 GAS INSTALLATION,TO BE INCLUDED ON PLANS
 FOR THIS PLAN REVIEW SPC 94 SEC 104.3.1
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-03-20 Cont ID  
Sent By ndenmark Date 2001-03-20 Time 12:30 Rev Time 2.00
Received By ndenmark Date 2001-03-20 Time 12:30 Sent To  
Notes
2001-03-20 00:00:00PROVISO:
 THIS INSTALLATION SHALL COMPLY WITH
 NFPA 99C 1999 EDITION.
  
 PIPE SHALL BE PROMINENTLY LABELED PRIOR
 TO INSTALLATION PER 4-3.2.2.2
  
 PRESSURE TEST PER 4-3.4.1.1 SHALL BE
 PRIOR TO WALLS BEING CLOSED.
  
 ALARM PANELS SHALL BE POWERED BY LIFE
 SAFETY BRANCH OF THE EMERGENCY SYSTEM
 PER 4-3.1.2.7
  
 PIPE MATERIAL TO BE PER 4-3.1.2.7 (C)
  
 PIPING SHOWN AS MEDICAL EVACUATION ON
 THIS PLAN IS TO BE INSTALLED PER 4-3.3
 WASTE ANESTHETIC GAS DISPOSAL SYSTEMS
 OR SUBMIT REVISION DEFINING USE OF THIS
 SYSTEM FOR REVIEW.
  
 CALL FOR INSPECTION PRIOR TO CONCEALING
 WORK. CALL FOR REQUIRED INSPECTIONS AND
 ACCEPTANCE TESTS REQUIRED BY THIS
 OFFICE.
 CALL PAUL SCHMITZ @ (561) 659-8096 EXT
 8233 OR JOHN LEECH EXT 8369 IF YOU HAVE
 ANY QUESTIONS ON REQUIRED TESTS OR
 INSPECTIONS.