Plan Review Details - Permit 01030121
Plan Review Stops For Permit 01030121
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-04-17 Cont ID  
Sent By dpalmer Date 2001-04-17 Time 18:47 Rev Time 0.00
Received By dpalmer Date 2001-04-17 Time 18:47 Sent To  
Notes
2001-04-17 00:00:00************* REVISION NEEDED **********
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE SUBMIT AIC RATINGS FOR ALL BEFORE
 FINAL INSPECTION.
  
 REVISE ANY OTHER CHANGES ON SAME PLANS
 BEFORE FINAL ALSO.(AS-BUILTS)
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-04-12 Cont ID  
Sent By dpalmer Date 2001-04-12 Time 07:33 Rev Time 0.00
Received By dpalmer Date 2001-04-12 Time 07:33 Sent To  
Notes
2001-04-12 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THE FIRST NOTE
 FROM PREVIOUS REVIEW WAS NOT SUBMITTED.
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 THIS IMFORMATION IS VERY IMPORTANT AND
 IS NOT SOMETHING THAT I CAN REDLINE ON
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS ,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-12 Cont ID  
Sent By dpalmer Date 2001-03-12 Time 17:37 Rev Time 0.00
Received By dpalmer Date 2001-03-12 Time 17:37 Sent To  
Notes
2001-03-12 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 4) NOTE: PLEASE SHOW GROUNDING
 ELECTRODEGOING TO BUILDING STEEL AND
 COLD WATER
 PER 250-50.
  
 5) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 6) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 7)NOTE: PLEASE NOTE MISSING OUTLET FOR
 GARAGE PER 210-52 G AND TO BE GFI PER
 210-8.
  
 8)NOTE: PLEASE NOTE PER F.A.C 61G15-23.
 002 AND 471.025 ALL CHANGES ON PLANS
 NEED TO SIGNED AND DATED BY THE
 ENGINEEROF RECORD. PLEASE MAKE ALL
 CHANGES IN
 PRINTED INK OR SIGN AND DATE EACH
 CHANGE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-04-09 Cont ID  
Sent By pkrauss Date 2001-04-09 Time 16:36 Rev Time 0.30
Received By pkrauss Date 2001-04-09 Time 16:31 Sent To  
Notes
2001-04-09 00:00:00******************PROVISO***************
  
 AHU SHALL HAVE FAN SHUT DOWN BY MEANS OF
 A DUCT SMOKE DETECTOR AS PER 1997 SMC
 406.1 IN ADDITION SHALL HAVE
 NOTIFICATION TO ALARM/STROBE NFPA
 4-4.4.3.
  
 AHU SHALL HAVE AUXILIARY DRAIN PAN WITH
 OVER FLOW PROTECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-03-10 Cont ID  
Sent By jleech Date 2001-03-10 Time 07:02 Rev Time 0.50
Received By jleech Date 2001-03-10 Time 07:01 Sent To  
Notes
2001-03-10 00:00:00DENIED;
  
 1.DRYER VENT REQUIRED.
  
 2.BATHROOM WINDOWS SHALL HAVE A CLEAR
 OPEN AREA OF 3 SQ. FT. OR EXHAUST FANS
 ARE REQUIRED.SMC 503.3.1.
  
 3.EQUIPMENT IS TO SMALL. 5 TON IS
 REQUIRED NOT 3 TON.
  
 4.ENERGY CAULKS SHOW A SEER VALUE OF
 13.5 A/C PLAN SHOWS 12. CHANGE ENERGY
 CAULKS OR EQUIPMENT.
  
 5.RETURN AIR IS REQUIRED FROM MASTER
 BEDROOM SUITE.
  
 A/C PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-03-10 Cont ID  
Sent By jleech Date 2001-03-10 Time 07:25 Rev Time 0.25
Received By jleech Date 2001-03-10 Time 07:25 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-04-18 Cont ID  
Sent By jgomez Date 2001-04-18 Time 11:06 Rev Time 3.00
Received By jgomez Date 2001-04-18 Time 11:05 Sent To  
Notes
2001-04-18 00:00:00APPROVED WITH PROVISO (NOTE: THIS ITEMS
 TO BE PROVIDED BEFORE INSTALLATION OR
 CONSTRUCTION):
  
 1-PROVIDE PRODUCT APPROVAL FOR:
 -ENTRY DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY (OR PROFESSIONAL ENGINEER OF
 RECORD TO PROVIDE STRUCTURAL DETAIL
 SHOWING CONSTRUCTION OF LINTEL BETWEEN
 DOORS AND ARCHED TRANSOM WINDOW)
 -SINGLE HUNG WINDOWS PRODUCT APPROVAL
 IS MISSING SOME DRAWINGS. RESUBMIT.
 -ARCHED WINDOW PRODUCT APPROVAL IS
 MISSING DRAWINGS TOO.
 -SLIDING GLASS DOORS.
 -SLIDING GLASS DOORS WITH TRANSOM ABOVE
 SINGLE ASSEMBLY (OR STRUCTURAL DETAIL
 BY ENGINEER OF RECORD).
 -FIXED TRANSOM WINDOW
 -WINDOW MULLIONS.
 -GARAGE DOOR THAT MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER
 OF RECORD (37PSF).
  
 2-ENGINEER OF RECORD TO PROVIDE
 STRUCTURAL BUCK DETAIL USING A 2X
 BUCK AS REQUIRED ON PRODUCT APPROVAL
 FOR DOORS AND WINDOWS.
  
 3-TRUSS ENGINEER TO SIGN, SEAL AND DATE
 THE TRUSS LAYOUT AND PROVIDE COMPLETE
 SET OF ENGINEERED TRUSSES AS WELL.
 -NOTE: ENGINEER OF RECORD TO REVIEW ALL
 TRUSS DRAWINGS PRIOR TO
 SUBMITTAL TO THIS OFFICE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-04-12 Cont ID  
Sent By jgomez Date 2001-04-12 Time 17:51 Rev Time 2.00
Received By jgomez Date 2001-04-12 Time 17:51 Sent To  
Notes
2001-04-12 00:00:00CHECKLIST:
 1-PROVIDE PROFESSIONAL SURVEY SHOWING
 BUILDING LAYOUT AS REQUESTED ON
 CHECKLIST DATED 3-27-01.
 -NOTE: SKETCH THAT WAS SUBMITTED AND
 APPROVED BY ZONING WAS NOT SUBMITTED
 WITH THIS PACKAGE. PLEASE RESUBMIT.
 2-UNABLE TO CHECK TABLE 600 OF SBC 1997
 BECAUSE THERE IS NOT SURVEY OR SITE
 PLAN SHOWING BUILDING LOCATION IN
 REFERENCE TO THE PROPERTY LINES.
 3-PROVIDE PRODUCT APPROVAL FOR:
 -ENTRY DOORS WITH TRANSOM ABOVE AS A
 SINGLE ASSEMBLY AS SHOWN ON PLANS.
 OR ENGINEER OF RECORD TO PROVIDE
 SECTION THRU ENTRY DOORS AREA SHOWING
 LINTEL SPECIFICATIONS. THEN, PROVIDE
 PRODUCT APPROVAL FOR ENTRY DOORS AND
 ARCHED WINDOW SEPARATELY.
 -SINGLE HUNG WINDOWS PRODUCT APPROVAL
 WAS ORIGINALLY SUBMITTED WITH DRAWINGS
 THAT WERE NOT LEGIBLE. NOW, NO PRODUCT
 APPROVAL WAS SUBMITTED.
 -SLIDING GLASS DOORS WITH TRANSOM ABOVE
 SINGLE ASSEMBLY AS SHOWING ON PLANS.
 OR, ENGINEER OF RECORD TO SHOW WALL
 SECTION SPECIFYING STRUCTURAL LINTEL.
 THEN, PROVIDE PRODUCT APPROVAL FOR
 DOORS AND FIXED WINDOW SEPARATELY.
 -HALF ROUND WINDOWS.
 -WINDOW MULLIONS.
 -GARAGE DOORS THAT MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER
 OF RECORD (37PSF).
 4-TYPICAL WALL SECTION SHOWS TIE BEAM
 TO BE AT 10'-0". CLARIFY IF THERE ARE
 NOT LINTELS, THEN WHAT IS IN BETWEEN
 THE WINDOWS AND THE TIE BEAM. REMEMBER
 THAT TIE BEAM IS 8"X12".
 PROVIDE SECTIONS WITH DIMENSIONS
 SHOWING LOCATION OF DOORS AND WINDOWS
 HEADS.
 5-PROVIDE COMPLETE SPECIFICATIONS FOR
 CEILING INSTALLATION AT ENTRY AND REAR
 PORCH. AS REQUIRED BY SECTION 2504.2
 SBC/97. CLEARLY SPECIFY ALL MATERIALS
 AND FASTENERS TO BE USED. SEE ASTM
 C926 AND ASTM C1063.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-03-27 Cont ID  
Sent By jgomez Date 2001-03-27 Time 16:21 Rev Time 3.00
Received By jgomez Date 2001-03-27 Time 16:20 Sent To  
Notes
2001-03-27 00:00:00CHECKLIST:
 1-PROVIDE ORIGINAL SURVEY SIGNED, SEALED
 AND DATED BY THE PROFESSIONAL SURVEYOR
 AS REQUIRED BY FLORIDA STATUTES, 471
 -PROVIDE SURVEY THAT SHOWS REAR PORCH
 AS SHOWN ON ENGINEER'S PLANS.
 2-PROVIDE COMPLETE BEAM AND LINTEL
 SCHEDULE.
 -PROVIDE COMPLETE COLUMN SCHEDULE.
 SECTION 104.2.2 CITY AMENDMENTS.
 3-REAR ELEVATION EXCEEDS THE AMOUNT OF
 OPENINGS ALLOWED BY TABLE 600 SBC/97.
 4-PROVIDE COMPLETE FRAMING DETAILS FOR
 ARCHED OPENINGS.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
  
 5-PROVIDE COMPLETE INFORMATION FOR
 CONSTRUCTION OF PLANTERS AT FRONT OF
 THE HOUSE.SEC 104.2.2 CITY AMENDMENTS
 6-PROVIDE SAFETY GLASS WHERE REQUIRED BY
 SEC. 2405.2 SBC 1997. SEE PLANS.
  
  
 7-SIZE OF ATTIC ACCESS IN HALLWAY TO BE
 22"X36" MIN. SEC. 2309.6 SBC 1997.
 8-SHOW ALL MASONRY OPENINGS AND HOW ARE
 THEY REINFORCED AT THE ENDS.
 -SPECIFY HOW ARE THE WINDOW SILLS
 CONSTRUCTED.
 SEC 104.2.2 CITY AMENDMENTS TO SBC/97.
 9-SPECIFY THE DESIGN PRESSURES
 CALCULATED FOR THE EXTERIOR OPENINGS.
 SECTION 1606 SBC 1997.
 10-SPECIFY COLUMNS TO SUPPORT TRUSS
 GIRDERS AT THE ENDS. SEC 104.2.2 OF
 CITY AMENDMENTS TO SBC/97. SEE PLANS.
 11-SPECIFY VENTILATION AT TOILETS AS
 REQUIRED BY SEC. 1203.4.2 AND 1203.1
 OF SBC 1997.
 12-SPECIFY CEILING INSTALLATION AT REAR
 AND ENTRY PORCH AS REQUIRED BY SEC.
 2504.2 SBC 1997. SEE APPLICATION
 REQUIREMENTS OF ASTM C926 AND ASTM
 C1063.
 13-SPECIFY CEILING FANS AS REQUIRED BY
 TABLE 6-6 FLORIDA ENERGY EFFICIENCY
 CODE FOR BUILDING CONSTRUCTION, 1997.
 14-SPECIFY SIZE OF ROOF VENTS TO COMPLY
 WITH SEC. 2309.7 SBC 1997.
 15-REVISE WALL SECTIONS. FOOTINGS TO BE
 12" MINIMUM BELOW FINISH GRADE AS
 REQUIRED BY SEC. 1804.1.3 SBC 1997.
 16-WALL SECTIONS AND FOUNDATION PLANS
 DON'T MATCH. CHECK SIZES OF FOOTINGS
 AND REINFORCEMENT, ETC.
 17-PROVIDE CONNECTION DETAIL OF WOOD
 BEAM TO CONCRETE BLOCK COLUMN AT
 CORNERS OF ENTRY PORCH. SECTION
 104.2.2 CITY AMENDMENTS TO SBC 1997.
 18-STORM PANELS:
 -PROVIDE COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE ATTACHED.
 -PROVIDE KEY PLAN SHOWING LOCATION OF
 STORM PANELS.
 -CLEARLY INDICATE ON STORM PANEL
 DRAWINGS MOUNTING CONDITIONS AND
 ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE MEAN ROOF HEIGHT,
 DESIGN PRESSURES, PANEL SPAN, EDGE
 DISTANCE, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO (CONCRETE
 BLOCK OR WOOD).
 19-PROVIDE PRODUCT APPROVAL FOR:
 -OUTSWING ENTRY DOORS WITH TRANSOM
 ABOVE SINGLE ASSEMBLY AS SHOWN ON
 FRONT ELEVATION. NOTE: IF DOORS AND
 WINDOW ABOVE ARE SEPARATED BY A LINTEL
 THEN, ENGINEER TO SPECIFY LINTEL ON
 HIS DRAWINGS.
 ALSO, MISSING THE APPROVED DRAWINGS.
 -DRAWINGS FOR SINGLE HUNG PRODUCT
 APPROVAL ARE NOT LEGIBLE.
 -SLIDING GLASS DOORS WITH TRANSOM
 ABOVE SINGLE ASSEMBLY OR ENGINEER TO
 SHOW IN HIS DRAWINGS A LINTEL IN
 BETWEEN DOORS AND WINDOW ABOVE.
 -HALF ROUND WINDOWS.
 -WINDOW MULLIONS.
 20-SEE ADDITIONAL COMMENTS ON PLANS.
 NOTE: PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS, IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-03-08 Cont ID  
Sent By sgraham Date 2001-03-08 Time 07:23 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-03-08 00:00:00NEED SURVEY & SITE PLAN