| Plan Review Stops For Permit 01030082 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-05-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-26 |
Time |
10:11 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-03-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-03-13 |
Time |
11:27 |
Rev Time |
5.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-13 00:00:00 | PROJECT# 01030082 | | | 531 SOUTHERN BLVD. | | | BURR COMPUTER ENVIROMENTS | | | (781) 374-8644 | | | | | | THE CODE COMMENTS LISTED BELOW ARE FROM | | | THE 1997 STANDARD BUILDING CODE. | | | | | | 1)- SBC 407.1.3.1: FIRE SPRINKLER PLANS | | | ARE TO BE PART OF THE PERMIT APPLICATION | | | PACKAGE BEFORE THE BUILDING PERMIT CAN | | | BE ISSUED. | | | | | | 2)- SBC 104.2.2: ADDITIONAL INFORMATION | | | REQUIRED: IS THERE AREAS OF THE BUILDING | | | THAT CONTAIN LARGE QUANITITIES OF | | | PRINTED CIRCUIT BOARDS USED FOR SWITCHES | | | IN THE TELECOMMUNICATION PROCESS? | | | | | | 3)- SBC 308.2.1: H-4 HEALTH HAZARDS- | | | TOXIC SOLIDS, LIQUIDS,CORROSIVES,IRRI- | | | TANTS, SENSITIZERS IN EXCESS OF AMOUNTS | | | GIVEN IN TABLE 308.2D. | | | IN SPRINKLERED BUILDINGS, NOT IN A CABI- | | | NET CORROSIVES, IRRITANTS | | | SOLIDS : 10,000LBS. | | | LIQUIDS:1,000GAL. | | | GASSES :1,300 CU FT. | | | | | | PLAN : S-1 DEPICTS 6,700 LBS./ RACK. | | | PLAN : FP.2 DEPICTS 3 RACKS X 6,700 LBS= | | | 20,100 LBS.IN EXCESS OF 10,000LBS. | | | IN TABLE 308.2D = H4 HAZARDOUS OCCUPANCY | | | FOR ROOM 114 DC POWER ROOM. | | | | | | 4)- SBC308.2.3: HAZARDOUS OCCUPANCY | | | SEPERATION REQUIREMENTS BETWEEN BUSINESS | | | FACTORY VS. H-4 OCCUPANCY. | | | WALLS: 1 HRS. | | | OPENING PROTECTIVES : 3/4 HR OPEN PRO | | | | | | 5)- SBC 407.2.1 STORAGE & DISPENSING | | | AREAS: IN EXCESS OFTHE EXEMPT AMOUNTS | | | SPECIFIED IN TABLE 308.2D. | | | 407.2.2EXPLOSION VENTING OR EXPLOSION | | | SUPPERSSION 1-7. | | | 407.2.3.2 SPILL CONTROL. | | | 407.2.4.2 EXHAUST VENTILATION 1-4. | | | 407.2.5.1 EMERGENCY ALARM & DETECTION. | | | 407.2.6.2 LIQUID TIGHT FLOORS. | | | 407.2.9.1 ELEC WIRING EQUIPMENT INSTALL | | | ED IN ACCORDANCE WITH NFPA 70. | | | 407.2.9.4 STANDBY POWER SHALL BE CONNECT | | | ED TO THE FOLLOWING: MECHANICAL VENTIL- | | | ATION SYSTEM, ALARM SYSTEM, | | | DETECTION SYSTEM AND THE EMER- | | | GENCY ILLUMINATION IN ACCORDANCE | | | WITH 1016.2. | | | 407.2.10 IDENIFICATION: VISIBLE HAZARD | | | IDENIFICATION SIGNS AS SPECIFIED | | | IN NFPA 704. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-08-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-07 |
Time |
22:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-07 |
Time |
22:03 |
Sent To |
|
|
| Notes |
| 2001-08-07 00:00:00 | ********** NOTE ******* NOTE******** | | | | | | 1)NOTE: PLEASE NOTE THAT PERMIT | | | APPLICATION VALUE MUST INCLUDE COMPLETE | | | SCOPE OF WORK TO INCLUDE ALL LABOR AND | | | MATERIALS. PER 104.7.5 | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-06-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2001-06-12 |
Time |
13:56 |
Rev Time |
5.00 |
| Received By |
jleahy |
Date |
2001-06-12 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2001-06-12 00:00:00 | 1- OUTLET SPACING DOES NOT MEET LOCAL | | | CODE,IN OFFICE AREAS IT IS EVERY | | | 12' AND IN ALL OTHER ARES IT IS EVERY | | | 20'.ONLY WHAREHOUSE USED FOR | | | STORAGE ARE EXEMPT!!!!!!!!!! 210-50 | | | | | | 2-VALUE FOR THE ELECTRICAL WORK WILL | | | HAVE TO INCLUDE ALL EQUIPMENT AND | | | LABOR!!PER 104.7.5 | | | 3-AIC RATINGS FOR MAINS IS SHOWN BUT | | | NONE FOR THE PANELS AND CIRCUIT | | | BREAKERS!ON THE PANEL SCHEDULE PLEASE | | | LIST THE AIAIC RATING FOR ALL THE | | | CIRCUIT BREAKERS IN THE PANEL!!!!!IF | | | NOT MOST WILL HAVE TO BE 65,000 BASED | | | ON WHAT IS SHOWN ON DRAWINGS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-03-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-27 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-27 |
Time |
18:23 |
Sent To |
|
|
| Notes |
| 2001-03-27 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE:PLEASE NOTE THAT UNDER | | | COUNTYWIDE ADMINISTRATIVE AND CITY CODE. | | | VALUE OF WORK BEING PERFORMED IS TO | | | INCLUDE LABOR AND MATERIALS. THIS VALUE | | | IS | | | ALSO TO INCLUDE ALL ELECTRICAL | | | EQUIPMENTTHAT MAY BE SUPPLIED BY THE | | | OWNER. | | | PLEASE NOTE THAT THE NOTE ON PLANS | | | PERTAINING TO "OWNER FURNISHED" | | | /"CONTRACTOR RECEIVED AND | | | INSTALLED". ALL ELECTRICAL EQUIPMENT | | | NEEDS TO BE SHOWN IN VALUE OF | | | APPLICATION. THIS IS TO INCLUDE | | | GENERATOR AND ATS ETC. IF THERE ARE ANY | | | QUESTIONS ON ANY OF THE ABOVE PLEASE | | | CALL. | | | | | | 2)NOTE: PLEASE PROVIDE CLARIFICATION ON | | | THE GFI PROTECTION OF MAIN SERVICE PER | | | 230-95. | | | | | | 3)NOTE: PLEASE NOTE A MEANS OF | | | DISCONNECT REQ`D FOR POWER COMING IN | | | FROM GENERATOR. 225-31. PLEASE NOTE | | | THAT THE DISCONNECT NEEDS TO BE GROUPED | | | PER 230-72. | | | THE REQ`MENST FOR THIS DISCONNECT NEEDS | | | TO MEET 230-76 AND 230-79. | | | | | | 4)NOTE: PLEASE NOTE THAT COLOR CODING | | | FOR 277/480 FEEDERS "B","P","Y". GRAY. | | | | | | | | | PLEASE ADDRESS AND SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRCIAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2001-03-09 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-03-09 |
Time |
09:57 |
Rev Time |
2.00 |
| Received By |
mamini |
Date |
2001-03-09 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2001-03-09 00:00:00 | PASSED WITH PROVISOS: | | | 1. ALL DRIVEWAY MUST BE CONSTRUCTED PER | | | CITY OF WPB STANDARD. | | | 2. ALL BROKEN SIDEWALKS,CURBS (&GUTTERS) | | | ALONG THE PROPERTY (ALL SIDES) SHOULD BE | | | REPLACED. | | | 3. CALL OUT THE CONFLICT POINTS WHERE | | | WATER CROSSING THE SEWER LINES AND SHOW | | | THE CLEARANCES. | | | 4. CONTRACTOR SHOULD COORDINATE WITH | | | PUBLIC UTILITIES ENGINEERING SERVICES | | | TO EVALUATE THE CONDITION OF THE | | | METR VAULT AND RESTORE TO GOOD CONDITION | | | AT NO COST TO THE DEPARTMENT. | | | 5. ANY IRRIGATION SYSTEM DISTRUPTED | | | BY CONSTRUCTION SHALL BE REPAIRED AND | | | OR REPLACED AT THE CONTRACTORS EXPENCE. | | | 6. ANY LANDSCAPE DISTRUPTED BY CONSTRUCT | | | ION SHALL BE REPAIRED AND OR REPLACED | | | AT THE CONTRACTORS EXPENSE. | | | 7. LANDSCAPE SHALL BE INSTALLED IN ACCO- | | | RDANCE WITH THE CLEAR VISION | | | REQUIREMENTS OF ARTICAL X, SECTION | | | 33-112 (E). |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-07-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-31 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-31 |
Time |
10:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-05-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-15 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-15 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2001-05-15 00:00:00 | 1) ENTIRE BUILDING IS TO BE COMPLETELY | | | FIRE SPRINKLER PROTECTED PRIOR TO | | | RECEIVING ANY FINAL APPROVALS. PLEASE | | | PROVIDE SEPARATE PLANS AND PERMITS FOR | | | FIRE SPRINKLER INSTALLATIONS. | | | 2) PLEASE SUBMIT SEPARATE PLANS AND | | | PERMITS FOR THE FIRE ALARM SYSTEM | | | INSTALLATION. SMOKE DETECTORS WHEN | | | INSTALLED ARE TO BE A MINIMUM OF THREE | | | FEET FROM AIR CONDITIONER DIFFUSERS. | | | BOTH THE FIRE SPRINKLER SYSTEM AND FIRE | | | ALARM SYSTEMS ARE TO BE SUPERVISED BY | | | A UL LISTED CENTRAL STATION APPROVED | | | BY THE FIRE RESCUE DEPARTMENT. | | | 3) THE FUTURE EXPANSION AREA IS TO HAVE | | | EMERGENCY LIGHTING FIXTURES INSTALLED AS | | | A BASE OR SHELL BUILDING WOULD HAVE. THE | | | MINIMUM REQUIREMENTS FOR OCCUPANCY SHALL | | | BE MET WITH ADDITIONAL WORK OR OCCUPANCY | | | BY SEPARATE PERMIT. | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR ANY FUEL INSTALLATION. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-03-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-08 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-08 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2001-03-08 00:00:00 | 1) PLEASE BE ADVISED THAT THIS SITE | | | MAY BE IN THE CITY FIRE LIMITS. CERTAIN | | | RESTRICTIONS APPLY IN THE FIRE LIMITS | | | TO THE INSTALLATION OF ABOVEGROUND FUEL | | | TANKS AND FLAMMABLE LIQUID TANKS. | | | SEPARATE PLANS AND PERMITS REQUIRED | | | PRIOR TO THE INSTALLATION OF ANY | | | FUEL TANKS. | | | 2) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE FIRE SPRINKLER SYSTEM RENOVATION | | | AND REMODEL. | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE INSTALLATION OF THE FIRE ALARM | | | SYSTEM. CUT SHEETS, WIRING DIAGRAM, AND | | | BATTERY CALCULATIONS ARE TO BE PROVIDED. | | | 4) KNOX-BOX RAPID ENTRY SYSTEMS ARE TO | | | BE PROVIDED FOR FIRE RESCUE ACCESS. | | | 5) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR GATES AND ELECTRICAL SYSTEMS. | | | OPENINGS AT GATE LOCATIONS MUST BE | | | TWENTY FEET IN CLEAR WIDTH. HOW IS | | | ACCESS ACHIEVED THRU THE SLIDING GATE | | | IF LOSS OF POWER SHOULD OCCUR. | | | 6) DUCT SMOKE DETECTORS REQUIRED IN ALL | | | AHU SYSTEMS OVER 2000 CFM. WHEN | | | ACTIVATED, THESE SYSTEMS MUST SHUT DOWN | | | AIR HANDLING EQUIPMENT AND ACTIVATE THE | | | FIRE ALARM SYSTEM. | | | 7) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION PROVIDED WITH PLANS. | | | 8) BUILDING ADDRESS REQUIRED PER CITY | | | CODE REQUIREMENTS. | | | 9) NO EMERGENCY LIGHTING SHOWN IN | | | EXPANSION AREA. WHAT WILL THIS AREA BE | | | USED FOR AND WHEN. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-08-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-06 |
Time |
12:25 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-08-06 |
Time |
12:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-06-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-05 |
Time |
09:47 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2001-06-05 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2001-06-05 00:00:00 | ********************DENIED************** | | | | | | PLEASE CLARIFY DESCREPANCY BETWEEN | | | DRAWING M2.1, 1 1/2" CONDENSATE DRAIN | | | DOWN FROM ROOF TO FLOOR DRAIN AND M2.2 | | | - DETAIL 01, CONDENSATE FRENCH DRAIN. | | | | | | ROOF CONDENSATE IS NOT GOING TO FLOOR | | | DRAIN...CORRECT? | | | | | | NOTE:AS PER AMENDED 1994 SPC 804.3, | | | CONDENSATE FOR UNITS LARGER THAN | | | 3 TONS MAY TERMINATE IN A DRYWELL | | | NOT A FRENCH DRAIN. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-03-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-22 |
Time |
15:18 |
Rev Time |
1.30 |
| Received By |
pkrauss |
Date |
2001-03-22 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2001-03-22 00:00:00 | *****************DENIED***************** | | | | | | CONDENSATE FROM ROOFTOP UNITS SHALL NOT | | | EMPTY INTO SANITARY DRAIN AS PER | | | AMENDED 1994 SPC 804.3. | | | | | | AS PER 1997 SMC 406.1, UNITS WITH FAN | | | CAPACITY GREATER THAN 2,000 CFM SHALL | | | HAVE FAN SHUT DOWN BY DUCT SMOKE | | | DETECTOR WITH NOTIFICATION TO | | | ALARM/STROBE IN NORMALLY OCCUPIED AREAS | | | (NFPA 90A 4-4.4.3) | | | | | | NO COMBUSTIBLES ABOVE CEILING IN RETURN | | | AIR PLENUM - 1997 SMC 609.1.1. | | | | | | SEPARATE PERMIT AND PLANS REQUIRED FOR | | | UNDERGROUND FUEL OIL TANK. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-08-08 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-08-08 |
Time |
13:22 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-08 00:00:00 | PLUMBING PLAN REVIEW PROVISO | | | SEE SHT P2.1 ALL INDIRECT WASTE TO F/S. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-05-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-05-22 |
Time |
09:35 |
Rev Time |
0.75 |
| Received By |
pschmitz |
Date |
2001-05-22 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2001-05-22 00:00:00 | REVIEW NOTES..DENIED.. | | | | | | 1) 2 HDCP TOILET ROOMS, 1 MALE AND 1 | | | FEMALE ARE REQUIRED. | | | | | | 2) MANUFACTURE'S SPEC. SHEET FOR HUMIDI | | | FIER REQUIRED. ALSO BACKFLOW IS NOT RE- | | | QUIRED FOR HUMIDIFIER, A WATTS N36 VAC- | | | UMN BREAKER OR EQUIVALNT WILL WORK. | | | | | | 3) FRENCH DRAINS ARE NOT APPROVED. | | | DRYWELL'S ARE ACCEPTABLE. | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-03-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-20 |
Time |
16:05 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
2001-03-20 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2001-03-20 00:00:00 | DENIED; | | | | | | 1.SUBMIT OCCUPANT LOAD PER TABLE 407 OF | | | THE 94 SPC. SEE SEC. 407.1.3 FOR | | | ALLOWABLE DEDUCTIBLE AREAS. COMPLY | | | WITH TABLE 407 FOR MIN. FIXTURES | | | REQUIRED. | | | | | | 2.WATER HEATER TO BE READILY ACCESSIBLE. | | | SOULD BE MOUNTED ON FLOOR. | | | | | | 3.REPLACE HUB DRAIN WITH FLOOR SINK. | | | | | | 4.ROOM 118 FD-1 IS UNVENTED. | | | | | | 5.FUTURE 4" WASTE PIPE SHALL COMPLY WITH | | | 714.3. NO DEAD ENDS. | | | | | | 6.FLOOR DRAIN IN JANITORS ROOM SHALL | | | HAVE A TRAP PRIMER. | | | | | | 7.DRINKING FOUNTAIN NOT SHOWN ON FLOOR | | | PLAN OR ON RISER DIAGRAM.DRINKING | | | FOUNTAIN TO COMPLY WITH FACBC 4.1.3 | | | (10) AND 4.13. | | | | | | 8.SHEET M-3 (HUMIDIFIER) DISCHARGE OF | | | WASTE WATER OVER 140 DEG. IS NOT | | | PERMITED.807.3 | | | | | | 9.SHEET M-2.2 CONDENSATE FROM A/C UNITS | | | TO BE PIPED TO STORM DRAINAGE NOT | | | SANITARY. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|