Plan Review Details - Permit 01030082
Plan Review Stops For Permit 01030082
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-05-26 Cont ID  
Sent By jwitmer Date 2001-05-26 Time 10:11 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-13 Cont ID  
Sent By jwitmer Date 2001-03-13 Time 11:27 Rev Time 5.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-13 00:00:00PROJECT# 01030082
 531 SOUTHERN BLVD.
 BURR COMPUTER ENVIROMENTS
 (781) 374-8644
  
 THE CODE COMMENTS LISTED BELOW ARE FROM
 THE 1997 STANDARD BUILDING CODE.
  
 1)- SBC 407.1.3.1: FIRE SPRINKLER PLANS
 ARE TO BE PART OF THE PERMIT APPLICATION
 PACKAGE BEFORE THE BUILDING PERMIT CAN
 BE ISSUED.
  
 2)- SBC 104.2.2: ADDITIONAL INFORMATION
 REQUIRED: IS THERE AREAS OF THE BUILDING
 THAT CONTAIN LARGE QUANITITIES OF
 PRINTED CIRCUIT BOARDS USED FOR SWITCHES
 IN THE TELECOMMUNICATION PROCESS?
  
 3)- SBC 308.2.1: H-4 HEALTH HAZARDS-
 TOXIC SOLIDS, LIQUIDS,CORROSIVES,IRRI-
 TANTS, SENSITIZERS IN EXCESS OF AMOUNTS
 GIVEN IN TABLE 308.2D.
 IN SPRINKLERED BUILDINGS, NOT IN A CABI-
 NET CORROSIVES, IRRITANTS
 SOLIDS : 10,000LBS.
 LIQUIDS:1,000GAL.
 GASSES :1,300 CU FT.
  
 PLAN : S-1 DEPICTS 6,700 LBS./ RACK.
 PLAN : FP.2 DEPICTS 3 RACKS X 6,700 LBS=
 20,100 LBS.IN EXCESS OF 10,000LBS.
 IN TABLE 308.2D = H4 HAZARDOUS OCCUPANCY
 FOR ROOM 114 DC POWER ROOM.
  
 4)- SBC308.2.3: HAZARDOUS OCCUPANCY
 SEPERATION REQUIREMENTS BETWEEN BUSINESS
 FACTORY VS. H-4 OCCUPANCY.
 WALLS: 1 HRS.
 OPENING PROTECTIVES : 3/4 HR OPEN PRO
  
 5)- SBC 407.2.1 STORAGE & DISPENSING
 AREAS: IN EXCESS OFTHE EXEMPT AMOUNTS
 SPECIFIED IN TABLE 308.2D.
 407.2.2EXPLOSION VENTING OR EXPLOSION
 SUPPERSSION 1-7.
 407.2.3.2 SPILL CONTROL.
 407.2.4.2 EXHAUST VENTILATION 1-4.
 407.2.5.1 EMERGENCY ALARM & DETECTION.
 407.2.6.2 LIQUID TIGHT FLOORS.
 407.2.9.1 ELEC WIRING EQUIPMENT INSTALL
 ED IN ACCORDANCE WITH NFPA 70.
 407.2.9.4 STANDBY POWER SHALL BE CONNECT
 ED TO THE FOLLOWING: MECHANICAL VENTIL-
 ATION SYSTEM, ALARM SYSTEM,
 DETECTION SYSTEM AND THE EMER-
 GENCY ILLUMINATION IN ACCORDANCE
 WITH 1016.2.
 407.2.10 IDENIFICATION: VISIBLE HAZARD
 IDENIFICATION SIGNS AS SPECIFIED
 IN NFPA 704.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-08-07 Cont ID  
Sent By dpalmer Date 2001-08-07 Time 22:03 Rev Time 0.00
Received By dpalmer Date 2001-08-07 Time 22:03 Sent To  
Notes
2001-08-07 00:00:00********** NOTE ******* NOTE********
  
 1)NOTE: PLEASE NOTE THAT PERMIT
 APPLICATION VALUE MUST INCLUDE COMPLETE
 SCOPE OF WORK TO INCLUDE ALL LABOR AND
 MATERIALS. PER 104.7.5
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-06-12 Cont ID  
Sent By jleahy Date 2001-06-12 Time 13:56 Rev Time 5.00
Received By jleahy Date 2001-06-12 Time 14:43 Sent To  
Notes
2001-06-12 00:00:001- OUTLET SPACING DOES NOT MEET LOCAL
 CODE,IN OFFICE AREAS IT IS EVERY
 12' AND IN ALL OTHER ARES IT IS EVERY
 20'.ONLY WHAREHOUSE USED FOR
 STORAGE ARE EXEMPT!!!!!!!!!! 210-50
  
 2-VALUE FOR THE ELECTRICAL WORK WILL
 HAVE TO INCLUDE ALL EQUIPMENT AND
 LABOR!!PER 104.7.5
 3-AIC RATINGS FOR MAINS IS SHOWN BUT
 NONE FOR THE PANELS AND CIRCUIT
 BREAKERS!ON THE PANEL SCHEDULE PLEASE
 LIST THE AIAIC RATING FOR ALL THE
 CIRCUIT BREAKERS IN THE PANEL!!!!!IF
 NOT MOST WILL HAVE TO BE 65,000 BASED
 ON WHAT IS SHOWN ON DRAWINGS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-27 Cont ID  
Sent By dpalmer Date 2001-03-27 Time 18:23 Rev Time 0.00
Received By dpalmer Date 2001-03-27 Time 18:23 Sent To  
Notes
2001-03-27 00:00:00**************** UNSAT *****************
  
 1)NOTE:PLEASE NOTE THAT UNDER
 COUNTYWIDE ADMINISTRATIVE AND CITY CODE.
 VALUE OF WORK BEING PERFORMED IS TO
 INCLUDE LABOR AND MATERIALS. THIS VALUE
 IS
 ALSO TO INCLUDE ALL ELECTRICAL
 EQUIPMENTTHAT MAY BE SUPPLIED BY THE
 OWNER.
 PLEASE NOTE THAT THE NOTE ON PLANS
 PERTAINING TO "OWNER FURNISHED"
 /"CONTRACTOR RECEIVED AND
 INSTALLED". ALL ELECTRICAL EQUIPMENT
 NEEDS TO BE SHOWN IN VALUE OF
 APPLICATION. THIS IS TO INCLUDE
 GENERATOR AND ATS ETC. IF THERE ARE ANY
 QUESTIONS ON ANY OF THE ABOVE PLEASE
 CALL.
  
 2)NOTE: PLEASE PROVIDE CLARIFICATION ON
 THE GFI PROTECTION OF MAIN SERVICE PER
 230-95.
  
 3)NOTE: PLEASE NOTE A MEANS OF
 DISCONNECT REQ`D FOR POWER COMING IN
 FROM GENERATOR. 225-31. PLEASE NOTE
 THAT THE DISCONNECT NEEDS TO BE GROUPED
 PER 230-72.
 THE REQ`MENST FOR THIS DISCONNECT NEEDS
 TO MEET 230-76 AND 230-79.
  
 4)NOTE: PLEASE NOTE THAT COLOR CODING
 FOR 277/480 FEEDERS "B","P","Y". GRAY.
  
  
 PLEASE ADDRESS AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-03-09 Cont ID  
Sent By mamini Date 2001-03-09 Time 09:57 Rev Time 2.00
Received By mamini Date 2001-03-09 Time 09:18 Sent To  
Notes
2001-03-09 00:00:00PASSED WITH PROVISOS:
 1. ALL DRIVEWAY MUST BE CONSTRUCTED PER
 CITY OF WPB STANDARD.
 2. ALL BROKEN SIDEWALKS,CURBS (&GUTTERS)
 ALONG THE PROPERTY (ALL SIDES) SHOULD BE
 REPLACED.
 3. CALL OUT THE CONFLICT POINTS WHERE
 WATER CROSSING THE SEWER LINES AND SHOW
 THE CLEARANCES.
 4. CONTRACTOR SHOULD COORDINATE WITH
 PUBLIC UTILITIES ENGINEERING SERVICES
 TO EVALUATE THE CONDITION OF THE
 METR VAULT AND RESTORE TO GOOD CONDITION
 AT NO COST TO THE DEPARTMENT.
 5. ANY IRRIGATION SYSTEM DISTRUPTED
 BY CONSTRUCTION SHALL BE REPAIRED AND
 OR REPLACED AT THE CONTRACTORS EXPENCE.
 6. ANY LANDSCAPE DISTRUPTED BY CONSTRUCT
 ION SHALL BE REPAIRED AND OR REPLACED
 AT THE CONTRACTORS EXPENSE.
 7. LANDSCAPE SHALL BE INSTALLED IN ACCO-
 RDANCE WITH THE CLEAR VISION
 REQUIREMENTS OF ARTICAL X, SECTION
 33-112 (E).

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-07-31 Cont ID  
Sent By mcarsill Date 2001-07-31 Time 10:01 Rev Time 0.00
Received By mcarsill Date 2001-07-31 Time 10:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-05-15 Cont ID  
Sent By mcarsill Date 2001-05-15 Time 15:51 Rev Time 0.00
Received By mcarsill Date 2001-05-15 Time 15:38 Sent To  
Notes
2001-05-15 00:00:001) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED PRIOR TO
 RECEIVING ANY FINAL APPROVALS. PLEASE
 PROVIDE SEPARATE PLANS AND PERMITS FOR
 FIRE SPRINKLER INSTALLATIONS.
 2) PLEASE SUBMIT SEPARATE PLANS AND
 PERMITS FOR THE FIRE ALARM SYSTEM
 INSTALLATION. SMOKE DETECTORS WHEN
 INSTALLED ARE TO BE A MINIMUM OF THREE
 FEET FROM AIR CONDITIONER DIFFUSERS.
 BOTH THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEMS ARE TO BE SUPERVISED BY
 A UL LISTED CENTRAL STATION APPROVED
 BY THE FIRE RESCUE DEPARTMENT.
 3) THE FUTURE EXPANSION AREA IS TO HAVE
 EMERGENCY LIGHTING FIXTURES INSTALLED AS
 A BASE OR SHELL BUILDING WOULD HAVE. THE
 MINIMUM REQUIREMENTS FOR OCCUPANCY SHALL
 BE MET WITH ADDITIONAL WORK OR OCCUPANCY
 BY SEPARATE PERMIT.
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY FUEL INSTALLATION.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-03-08 Cont ID  
Sent By mcarsill Date 2001-03-08 Time 10:59 Rev Time 0.00
Received By mcarsill Date 2001-03-08 Time 10:59 Sent To  
Notes
2001-03-08 00:00:001) PLEASE BE ADVISED THAT THIS SITE
 MAY BE IN THE CITY FIRE LIMITS. CERTAIN
 RESTRICTIONS APPLY IN THE FIRE LIMITS
 TO THE INSTALLATION OF ABOVEGROUND FUEL
 TANKS AND FLAMMABLE LIQUID TANKS.
 SEPARATE PLANS AND PERMITS REQUIRED
 PRIOR TO THE INSTALLATION OF ANY
 FUEL TANKS.
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE SPRINKLER SYSTEM RENOVATION
 AND REMODEL.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE INSTALLATION OF THE FIRE ALARM
 SYSTEM. CUT SHEETS, WIRING DIAGRAM, AND
 BATTERY CALCULATIONS ARE TO BE PROVIDED.
 4) KNOX-BOX RAPID ENTRY SYSTEMS ARE TO
 BE PROVIDED FOR FIRE RESCUE ACCESS.
 5) SEPARATE PLANS AND PERMITS REQUIRED
 FOR GATES AND ELECTRICAL SYSTEMS.
 OPENINGS AT GATE LOCATIONS MUST BE
 TWENTY FEET IN CLEAR WIDTH. HOW IS
 ACCESS ACHIEVED THRU THE SLIDING GATE
 IF LOSS OF POWER SHOULD OCCUR.
 6) DUCT SMOKE DETECTORS REQUIRED IN ALL
 AHU SYSTEMS OVER 2000 CFM. WHEN
 ACTIVATED, THESE SYSTEMS MUST SHUT DOWN
 AIR HANDLING EQUIPMENT AND ACTIVATE THE
 FIRE ALARM SYSTEM.
 7) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION PROVIDED WITH PLANS.
 8) BUILDING ADDRESS REQUIRED PER CITY
 CODE REQUIREMENTS.
 9) NO EMERGENCY LIGHTING SHOWN IN
 EXPANSION AREA. WHAT WILL THIS AREA BE
 USED FOR AND WHEN.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-08-06 Cont ID  
Sent By pkrauss Date 2001-08-06 Time 12:25 Rev Time 0.45
Received By pkrauss Date 2001-08-06 Time 12:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-06-05 Cont ID  
Sent By pkrauss Date 2001-06-05 Time 09:47 Rev Time 1.00
Received By pkrauss Date 2001-06-05 Time 09:46 Sent To  
Notes
2001-06-05 00:00:00********************DENIED**************
  
 PLEASE CLARIFY DESCREPANCY BETWEEN
 DRAWING M2.1, 1 1/2" CONDENSATE DRAIN
 DOWN FROM ROOF TO FLOOR DRAIN AND M2.2
 - DETAIL 01, CONDENSATE FRENCH DRAIN.
  
 ROOF CONDENSATE IS NOT GOING TO FLOOR
 DRAIN...CORRECT?
  
 NOTE:AS PER AMENDED 1994 SPC 804.3,
 CONDENSATE FOR UNITS LARGER THAN
 3 TONS MAY TERMINATE IN A DRYWELL
 NOT A FRENCH DRAIN.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-03-22 Cont ID  
Sent By pkrauss Date 2001-03-22 Time 15:18 Rev Time 1.30
Received By pkrauss Date 2001-03-22 Time 14:37 Sent To  
Notes
2001-03-22 00:00:00*****************DENIED*****************
  
 CONDENSATE FROM ROOFTOP UNITS SHALL NOT
 EMPTY INTO SANITARY DRAIN AS PER
 AMENDED 1994 SPC 804.3.
  
 AS PER 1997 SMC 406.1, UNITS WITH FAN
 CAPACITY GREATER THAN 2,000 CFM SHALL
 HAVE FAN SHUT DOWN BY DUCT SMOKE
 DETECTOR WITH NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS
 (NFPA 90A 4-4.4.3)
  
 NO COMBUSTIBLES ABOVE CEILING IN RETURN
 AIR PLENUM - 1997 SMC 609.1.1.
  
 SEPARATE PERMIT AND PLANS REQUIRED FOR
 UNDERGROUND FUEL OIL TANK.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-08-08 Cont ID  
Sent By pschmitz Date 2001-08-08 Time 13:22 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-08-08 00:00:00PLUMBING PLAN REVIEW PROVISO
 SEE SHT P2.1 ALL INDIRECT WASTE TO F/S.

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-05-22 Cont ID  
Sent By kstevens Date 2001-05-22 Time 09:35 Rev Time 0.75
Received By pschmitz Date 2001-05-22 Time 09:35 Sent To  
Notes
2001-05-22 00:00:00REVIEW NOTES..DENIED..
  
 1) 2 HDCP TOILET ROOMS, 1 MALE AND 1
 FEMALE ARE REQUIRED.
  
 2) MANUFACTURE'S SPEC. SHEET FOR HUMIDI
 FIER REQUIRED. ALSO BACKFLOW IS NOT RE-
 QUIRED FOR HUMIDIFIER, A WATTS N36 VAC-
 UMN BREAKER OR EQUIVALNT WILL WORK.
  
 3) FRENCH DRAINS ARE NOT APPROVED.
 DRYWELL'S ARE ACCEPTABLE.
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-03-20 Cont ID  
Sent By jleech Date 2001-03-20 Time 16:05 Rev Time 2.00
Received By pschmitz Date 2001-03-20 Time 16:05 Sent To  
Notes
2001-03-20 00:00:00DENIED;
  
 1.SUBMIT OCCUPANT LOAD PER TABLE 407 OF
 THE 94 SPC. SEE SEC. 407.1.3 FOR
 ALLOWABLE DEDUCTIBLE AREAS. COMPLY
 WITH TABLE 407 FOR MIN. FIXTURES
 REQUIRED.
  
 2.WATER HEATER TO BE READILY ACCESSIBLE.
 SOULD BE MOUNTED ON FLOOR.
  
 3.REPLACE HUB DRAIN WITH FLOOR SINK.
  
 4.ROOM 118 FD-1 IS UNVENTED.
  
 5.FUTURE 4" WASTE PIPE SHALL COMPLY WITH
 714.3. NO DEAD ENDS.
  
 6.FLOOR DRAIN IN JANITORS ROOM SHALL
 HAVE A TRAP PRIMER.
  
 7.DRINKING FOUNTAIN NOT SHOWN ON FLOOR
 PLAN OR ON RISER DIAGRAM.DRINKING
 FOUNTAIN TO COMPLY WITH FACBC 4.1.3
 (10) AND 4.13.
  
 8.SHEET M-3 (HUMIDIFIER) DISCHARGE OF
 WASTE WATER OVER 140 DEG. IS NOT
 PERMITED.807.3
  
 9.SHEET M-2.2 CONDENSATE FROM A/C UNITS
 TO BE PIPED TO STORM DRAINAGE NOT
 SANITARY.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***