Plan Review Details - Permit 01030051
Plan Review Stops For Permit 01030051
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-08-10 Cont ID  
Sent By rmcdouga Date 2001-08-10 Time 10:41 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-07-28 Cont ID  
Sent By rmcdouga Date 2001-07-28 Time 09:47 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-07-28 00:00:00REVISION UNSAT
  
 1) PROVIDE DETAILED WALL SECTION OF
 EXTERIOR STUDIO WALL AT NEW OPENING FOR
 GLASS BLOCK. INDICATE WALL MATERIAL,
 FRAMING MATERIAL, HEADER SIZE AND
 MATERIAL, STRAPPING DETAILS, INTERIOR
 AND EXTERIOR FINISHES,ETC.
  
 2) INDICATE TYPES OF MATERIALS THAT WILL
 BE USED TO ENCLOSE STUDIO WINDOW.
  
 3) PLANS SUBMITTED FOR REVISION MUST BE
 SIGNED, SEALED AND DATED BY THE DESIGNER
 OF RECORD (ENGINEER). ENGINEER'S BLOCK
 STAMP IS REQUIRED ON PLANS.
  
 PRODUCT APPROVALS
  
 1) PRODUCT APPROVALS SUBMITTED FOR DOORS
 DO NOT CORRESPOND TO THE DOUBLE FRENCH
 DOORS SHOWN ON THE PLANS. TWO (2) COPIES
 ARE REQUIRED.
  
 2) PARTS OF THE PRODUCT APPROVAL
 SUBMITTED FOR THE GLASS BLOCK ARE
 ILLEGIBLE. PLEASE SUBMIT TWO (2) CLEAR,
 READABLE COPIES.
  
 3)PROVIDE (2) CURRENT PRODUCT APPROVALS,
 KEY PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
 PLYWOOD HURRICANE PANELS ARE ACCEPTIBLE
 IF DESIGNED IN ACCORDANCE WITH AMERICAN
 PLYWOOD ASSOCIATION GUIDELINES. YOU CAN
 NOT USE CUSTOM BUILT CEDAR SHUTTERS,
 UNLESS THEY COMPLY WITH THE CITY OF
 WEST PALM BEACH REQUIREMENTS FOR MISSLE
 IMPACT PROTECTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-05-30 Cont ID  
Sent By rmcdouga Date 2001-05-30 Time 16:19 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-05-30 00:00:00************BUILDING PROVISO************
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STORM PANELS (THE ONES SUBMITTED HAD
 EXPIRED ON 1-8-01)
 - EXTERIOR DOORS (PREMDOR) THE ONES
 SUBMITTED WERE NOT METRO-DADE OR SBCCI

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-29 Cont ID  
Sent By rmcdouga Date 2001-03-29 Time 10:19 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-03-29 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - GLASS BLOCK
 - GLAZED DOUBLE ENTRY DOORS (INFORMATION
 THAT WAS SUBMITTED IS NOT ACCEPTABLE)
  
 4) PROVIDE ATTIC VENTILATION PER 97 SBC
 SEC. 2309.7.
  
 5) PROVIDE CRAWL SPACE VENTILATION PER
 97 SBC SEC.1804.6.2.1.
  
 6) SHEET 2 OF PLANS CONTAINS CONFLICTING
 INFORMATION AND IMPROPER DESIGN CRITERIA
 THE ACCEPTED DESIGN CRITERIA IS ASCE7-95
 OR SEC. 1606 OF THE 1997 SBC.
  
 7) PROVIDE DETAIL OF 2X8 RAFTER ATTACH-
 MENT TO EXISTING STRUCTURE.
  
 8) PROVIDE ENERGY CALCULATIONS FOR NEW
 ADDITION AS REQUIRED BY THE 97 FLORIDA
 ENERGY CODE.
  
 9) INDICATE INSULATION FOR WALLS, FLOORS
 AND CEILING OF ADDITION THAT COMPLIES
 WITH THE 97 FLORIDA ENERGY CODE.
  
 10) PROVIDE STRUCTURAL DETAILS AND WALL
 SECTION OF EXISTING GUEST HOUSE WHERE
 OPENINGS WILL BE MADE TO ACCOMADATE NEW
 DOUBLE DOORS.
  
 11)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2001-05-30 Cont ID  
Sent By rmcdouga Date 2001-05-30 Time 16:30 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-05-30 00:00:00ELECTRIC WILL BE UNDER A SEPARATE PERMIT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-29 Cont ID  
Sent By dpalmer Date 2001-03-29 Time 18:20 Rev Time 0.00
Received By dpalmer Date 2001-03-29 Time 18:20 Sent To  
Notes
2001-03-29 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY LOCATION OF
 SERVICE OR IS SERVICE EXISTING FROM
 MAIN HOUSE? PLEASECLARFIY LOCATION OF
 SERVICE.
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE SHOW GROUNDING
 ELECTRODEGOING TO BUILDING STEEL AND
 COLD WATER
 PER 250-50.
  
 3)NOTE: PLEASE NOTE BATH OUTLET REQ`D BY
 210-52 AND 210-11-C-3.
  
 4) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 ONE WILL BE REQ`D FOR THIS ROOM.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANYQUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-03-16 Cont ID  
Sent By jleech Date 2001-03-16 Time 15:35 Rev Time 0.00
Received By jleech Date   Time   Sent To  
Notes
2001-03-16 00:00:00A/C DRAWING BY A/C CONTRACTOR WITH
 APPLICATION.

Review Stop P PLUMBING
Rev No 2 Status N Date 2001-05-31 Cont ID  
Sent By kstevens Date 2001-05-24 Time 19:17 Rev Time 0.33
Received By kstevens Date 2001-05-24 Time 19:17 Sent To  
Notes
2001-05-24 00:00:00REVIEW NOTES: ...FAILED...
  
 NOT ENOUGH INFORMATION. PLEASE SUBMIT
 A SANITARY RISER DIAGRAM, AND A WATER
 RISER DIAGRAM, AND DEFINE SCOPE OF
 PLUMBING WORK TO BE DONE. ALSO SHOW HOW
 THE NEW WORK WILL BE TIED INTO EXISTING
 SYSTEMS. SUPPLY INFO WHEN APPLYING FOR
 SEPARATE PLUMBING PERMIT.
  
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-03-16 Cont ID  
Sent By jleech Date 2001-03-16 Time 15:37 Rev Time 0.25
Received By jleech Date   Time   Sent To  
Notes
2001-03-16 00:00:00RISER DIAGRAM REQUIRED WHEN PLUMBER
 PULLS PERMIT.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-03-08 Cont ID  
Sent By sgraham Date 2001-03-08 Time 07:23 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***