| Plan Review Stops For Permit 01030051 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2001-08-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2001-08-10 |
Time |
10:41 |
Rev Time |
2.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-07-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2001-07-28 |
Time |
09:47 |
Rev Time |
2.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-28 00:00:00 | REVISION UNSAT | | | | | | 1) PROVIDE DETAILED WALL SECTION OF | | | EXTERIOR STUDIO WALL AT NEW OPENING FOR | | | GLASS BLOCK. INDICATE WALL MATERIAL, | | | FRAMING MATERIAL, HEADER SIZE AND | | | MATERIAL, STRAPPING DETAILS, INTERIOR | | | AND EXTERIOR FINISHES,ETC. | | | | | | 2) INDICATE TYPES OF MATERIALS THAT WILL | | | BE USED TO ENCLOSE STUDIO WINDOW. | | | | | | 3) PLANS SUBMITTED FOR REVISION MUST BE | | | SIGNED, SEALED AND DATED BY THE DESIGNER | | | OF RECORD (ENGINEER). ENGINEER'S BLOCK | | | STAMP IS REQUIRED ON PLANS. | | | | | | PRODUCT APPROVALS | | | | | | 1) PRODUCT APPROVALS SUBMITTED FOR DOORS | | | DO NOT CORRESPOND TO THE DOUBLE FRENCH | | | DOORS SHOWN ON THE PLANS. TWO (2) COPIES | | | ARE REQUIRED. | | | | | | 2) PARTS OF THE PRODUCT APPROVAL | | | SUBMITTED FOR THE GLASS BLOCK ARE | | | ILLEGIBLE. PLEASE SUBMIT TWO (2) CLEAR, | | | READABLE COPIES. | | | | | | 3)PROVIDE (2) CURRENT PRODUCT APPROVALS, | | | KEY PLANS AND INSTALLATION SCHEDULES | | | INDICATING THE SPECIFIC TYPES OF ANCHORS | | | TO BE USED FOR STORM PANELS. | | | PLYWOOD HURRICANE PANELS ARE ACCEPTIBLE | | | IF DESIGNED IN ACCORDANCE WITH AMERICAN | | | PLYWOOD ASSOCIATION GUIDELINES. YOU CAN | | | NOT USE CUSTOM BUILT CEDAR SHUTTERS, | | | UNLESS THEY COMPLY WITH THE CITY OF | | | WEST PALM BEACH REQUIREMENTS FOR MISSLE | | | IMPACT PROTECTION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-05-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2001-05-30 |
Time |
16:19 |
Rev Time |
2.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-30 00:00:00 | ************BUILDING PROVISO************ | | | | | | 1)PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - STORM PANELS (THE ONES SUBMITTED HAD | | | EXPIRED ON 1-8-01) | | | - EXTERIOR DOORS (PREMDOR) THE ONES | | | SUBMITTED WERE NOT METRO-DADE OR SBCCI |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-03-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2001-03-29 |
Time |
10:19 |
Rev Time |
4.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-29 00:00:00 | DENIED | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 3)PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - GLASS BLOCK | | | - GLAZED DOUBLE ENTRY DOORS (INFORMATION | | | THAT WAS SUBMITTED IS NOT ACCEPTABLE) | | | | | | 4) PROVIDE ATTIC VENTILATION PER 97 SBC | | | SEC. 2309.7. | | | | | | 5) PROVIDE CRAWL SPACE VENTILATION PER | | | 97 SBC SEC.1804.6.2.1. | | | | | | 6) SHEET 2 OF PLANS CONTAINS CONFLICTING | | | INFORMATION AND IMPROPER DESIGN CRITERIA | | | THE ACCEPTED DESIGN CRITERIA IS ASCE7-95 | | | OR SEC. 1606 OF THE 1997 SBC. | | | | | | 7) PROVIDE DETAIL OF 2X8 RAFTER ATTACH- | | | MENT TO EXISTING STRUCTURE. | | | | | | 8) PROVIDE ENERGY CALCULATIONS FOR NEW | | | ADDITION AS REQUIRED BY THE 97 FLORIDA | | | ENERGY CODE. | | | | | | 9) INDICATE INSULATION FOR WALLS, FLOORS | | | AND CEILING OF ADDITION THAT COMPLIES | | | WITH THE 97 FLORIDA ENERGY CODE. | | | | | | 10) PROVIDE STRUCTURAL DETAILS AND WALL | | | SECTION OF EXISTING GUEST HOUSE WHERE | | | OPENINGS WILL BE MADE TO ACCOMADATE NEW | | | DOUBLE DOORS. | | | | | | 11)PROVIDE STORM PANEL INFORMATION WITH | | | INSTALLATION SCHEDULE AND KEY PLAN WITH | | | SPECIFIC ANCHORS AND MOUNTING TO BE USED | | | FOR ALL NON-IMPACT GLAZING. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2001-05-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2001-05-30 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-30 00:00:00 | ELECTRIC WILL BE UNDER A SEPARATE PERMIT |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-03-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-29 |
Time |
18:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-29 |
Time |
18:20 |
Sent To |
|
|
| Notes |
| 2001-03-29 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE CLARIFY LOCATION OF | | | SERVICE OR IS SERVICE EXISTING FROM | | | MAIN HOUSE? PLEASECLARFIY LOCATION OF | | | SERVICE. | | | PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2) NOTE: PLEASE SHOW GROUNDING | | | ELECTRODEGOING TO BUILDING STEEL AND | | | COLD WATER | | | PER 250-50. | | | | | | 3)NOTE: PLEASE NOTE BATH OUTLET REQ`D BY | | | 210-52 AND 210-11-C-3. | | | | | | 4) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | ONE WILL BE REQ`D FOR THIS ROOM. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANYQUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-03-16 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-16 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-16 00:00:00 | A/C DRAWING BY A/C CONTRACTOR WITH | | | APPLICATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2001-05-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-05-24 |
Time |
19:17 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-05-24 |
Time |
19:17 |
Sent To |
|
|
| Notes |
| 2001-05-24 00:00:00 | REVIEW NOTES: ...FAILED... | | | | | | NOT ENOUGH INFORMATION. PLEASE SUBMIT | | | A SANITARY RISER DIAGRAM, AND A WATER | | | RISER DIAGRAM, AND DEFINE SCOPE OF | | | PLUMBING WORK TO BE DONE. ALSO SHOW HOW | | | THE NEW WORK WILL BE TIED INTO EXISTING | | | SYSTEMS. SUPPLY INFO WHEN APPLYING FOR | | | SEPARATE PLUMBING PERMIT. | | | | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2001-03-16 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-16 |
Time |
15:37 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-16 00:00:00 | RISER DIAGRAM REQUIRED WHEN PLUMBER | | | PULLS PERMIT. |
|
|