Plan Review Details - Permit 01021194
Plan Review Stops For Permit 01021194
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-04-22 Cont ID  
Sent By jwitmer Date 2002-04-22 Time 14:14 Rev Time 0.33
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-22 00:00:00FORM BOARD SURVEY

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-01-10 Cont ID  
Sent By jwitmer Date 2002-01-10 Time 15:22 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-07-24 Cont ID  
Sent By jwitmer Date 2001-07-24 Time 19:01 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-24 00:00:00BUILDING TYPE III
 PLAN REVIEW 01021194
  
 1)- ALL BUILDING COMMENTS HAVE BEEN ADD-
 RESSED WITH EXCEPTION TO GLAXED OPENINGS
 NO INFORMATION ON WINDOWS, DOORS OR
 GARAGE DOORS. SEE CITY POLICY FOR
 LARGE MISSLE IMPACT GLAZING AND STORM
 SHUTTERS
 2)- ROOFING - THER IS ALSO NO PRODUCT
 TESTING FOR THE ROOF ASSEMBLY.
  
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status R Date 2002-01-10 Cont ID  
Sent By jwitmer Date 2002-01-10 Time 15:29 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-09-07 Cont ID  
Sent By jleahy Date 2001-09-07 Time 15:40 Rev Time 4.25
Received By jleahy Date 2001-09-07 Time 15:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-07-12 Cont ID  
Sent By dpalmer Date 2001-07-12 Time 07:13 Rev Time 0.00
Received By dpalmer Date 2001-07-12 Time 07:13 Sent To  
Notes
2001-07-12 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT OUT OF THREE
 SETS ON TYPE III BUILDING. TWO SETS
 HAVE THE HANDWRITTEN CHANGE OF SERVICE
 WIRE SIZE AND THE 3RD SET HAS NO CHANGE
 AT ALL. PLEASE NOTE THAT ALL CHANGES
 MUST BE SIGNED AND DATED BY THE ENGINEER
 OF RECORD. FS, FAC 471.025
  
 2)NOTE: PLEASE ALSO NOTE THAT THE WIRE
 SIZE INCREASE IS NOT LARGE ENOUGH.
 PER 110-14-C AND 240-3-C. .
 PLEASE SEE 310-16 75` COLUMN.
  
 PLEASE MAKE THE ABOVE CHANGES TO MEET
 NEC. PLEASE SUBMIT THE ABOVE FOR REVIEW
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-24 Cont ID  
Sent By jleahy Date 2001-05-24 Time 12:36 Rev Time 1.00
Received By jleahy Date 2001-05-24 Time 12:35 Sent To  
Notes
2001-05-24 00:00:00PAGE E-302 HAS A 1200 AMP MAIN WITH ONLY
 1125 AMPS OF WIRE240-3C ,110-14C2

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2002-01-10 Cont ID  
Sent By jwitmer Date 2002-01-10 Time 15:29 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-01-10 00:00:00MASTER:01021176

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-01-10 Cont ID  
Sent By jwitmer Date 2002-01-10 Time 15:31 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-01-10 00:00:00MASTER: 01021176

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-28 Cont ID  
Sent By mcarsill Date 2001-08-28 Time 14:36 Rev Time 0.00
Received By mcarsill Date 2001-08-28 Time 14:36 Sent To  
Notes
2001-08-28 00:00:00THE TEMPORARY FIRE PROTECTION PLANNED
 BY THE USE OF DRY HYDRANTS AND A
 PUMP WILL NOT BE APPROVED BY THIS
 OFFICE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-07-11 Cont ID  
Sent By pkrauss Date 2001-07-11 Time 13:58 Rev Time 1.00
Received By pkrauss Date 2001-07-11 Time 13:58 Sent To  
Notes
2001-07-11 00:00:00*******************PROVISO**************
  
 TYPE III
  
 NOTHING ON PLANS HAVE CHANGED.
  
  
 PLEASE TAKE NOTE TO THE FOLLOWING ISSUES
  
 1.AS STATED IN REVIEW NOTES DATED
 6/5/01, PLAN M-306 DETAIL OF A/C
 CLOSET, PROVIDE OVERFLOW PAN FOR
 UPPER FLOORS ONLY....OVERFLOW PAN
 SHALL GO ON EVERY FLOOR TO PREVENT
 DAMAGE TO CARPET, WALLS AND INTERIOR
 OF APARTMENT.
  
 2.AS DISCUSSED IN MEETING WITH CARLOS
 AT CITY HALL, AS PER AMENDED 1997
 SPC 804.3, #5. CONDENSATE DRAINS
 SHALL VENT TO ATMOSPHERE, IT SHALL
 NOT VENT INTO THE WALL AS SHOWN ON
 THE DETAIL.SHOULD TERMINATION BE
 IN THE ATTIC, IT SHALL BE A MINIMUM
 OF 6" ABOVE THE INSULATION.
  
 PLEASE REMOVE/CORRECT NOTES THAT REFER
 TO DETAILS ON PLANS THAT ARE NOT IN THE
 PLAN SET OR HAVE BEEN SHOWN ON
 DIFFERENT PLAN (EXAMPLE:SHAFT
 ENCLOSURE IS SAID TO BE ON
 ARCHITECTURAL PLAN SHEET A-13 #25).
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-05 Cont ID  
Sent By pkrauss Date 2001-06-05 Time 13:37 Rev Time 2.30
Received By pkrauss Date 2001-06-05 Time 13:36 Sent To  
Notes
2001-06-05 00:00:00REVIEW DONE UNDER PERMIT 10201175

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-04-06 Cont ID  
Sent By pkrauss Date 2001-04-06 Time 15:07 Rev Time 1.30
Received By pkrauss Date 2001-04-06 Time 15:07 Sent To  
Notes
2001-04-06 00:00:00******************DENIED****************
  
 TYPE III REVIEW UNDER 01021176

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-01-10 Cont ID  
Sent By jwitmer Date 2002-01-10 Time 15:33 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-01-10 00:00:00MASTER: 01021176

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-08-18 Cont ID  
Sent By kstevens Date 2001-08-18 Time 14:46 Rev Time 0.00
Received By kstevens Date 2001-08-18 Time 14:46 Sent To  
Notes
2001-08-18 00:00:00DENIED...
  
 1) PREVIOUS COMMENTS FOR PLUMBING'S #'S
 1 - 2 - 5 & 6 MPT ADDRESSED.
  
 2) COMMENT #3 DETAIL FOR CONDENSATE
 STILL SHOWS VENT IN PLENUM ON PLUMBING
 PAGES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-01-10 Cont ID  
Sent By kstevens Date 2002-01-10 Time 15:32 Rev Time 0.00
Received By jwitmer Date   Time 15:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-07-16 Cont ID  
Sent By jleech Date 2001-07-16 Time 10:41 Rev Time 1.50
Received By jleech Date 2001-07-16 Time 10:41 Sent To  
Notes
2001-07-16 00:00:00DENIED;
  
 1.TYPE III PAGE A-5.6, BATHROOM WIDTH
 SHOULD BE 5' 2". PAGE C-3 BATHROOM
 WIDTH SHOULD 5' 2"
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-15 Cont ID  
Sent By jwitmer Date 2002-01-15 Time 18:31 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***