Plan Review Details - Permit 01021181
Plan Review Stops For Permit 01021181
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2002-02-06 Cont ID  
Sent By jwitmer Date 2002-02-06 Time 09:51 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-02-06 00:00:00GARAGE DOOR: PRESSURE TO LOW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-09-27 Cont ID  
Sent By jwitmer Date 2001-09-27 Time 12:14 Rev Time 5.00
Received By jwitmer Date 2001-09-27 Time 12:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-07-24 Cont ID  
Sent By jwitmer Date 2001-07-24 Time 19:10 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-24 00:00:00BUILDING PLAN REVIEW
 PLAN REVIW # 01021181
 1)- ALL BUILDING COMMENTS HAVE BEEN ADD=
 RESSED WITH THE EXCEPTION TO GLAZED OPEN
 INGS, NO INFORMATION ON WINDOWS, DOORS
 OR GARAGE DOORS. SEE CITY POLICY FOR
 LARGE MISSLE IMPACT GLAZING AND STORM
 SHUTTERS
 2)- ROOFING THERE IS ALSO NO PRODUCT
 TESTING FOR THE ROOF ASSEMBLY.
  
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-06-12 Cont ID  
Sent By jwitmer Date 2001-06-12 Time 10:00 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-12 00:00:00TYPE IV BUILDING
 BUILDING # 7
 PLAN REVIEW # 01021181
 ARCH MOURIZ SALAZAR
 BUILDING #7 TYPE 4
  
  
 COMMENTS SAME AS 01021175

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-04 Cont ID  
Sent By jwitmer Date 2001-04-04 Time 18:48 Rev Time 2.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-04 00:00:00TYPE IV BUILDING
 BUILDING # 7
 PROJECT: 01021181
 ARCH.MOURIZ SALAZAR
 PHONE (305) 273-9911
 FAX(305)
 BUILDING # 7
  
 1)- SBC 1007.3.1 STAIR CALCULATION
 REQUIRES 2R + 1T= >24", <25".

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-01-23 Cont ID  
Sent By dpalmer Date 2002-01-23 Time 07:44 Rev Time 0.00
Received By dpalmer Date 2002-01-23 Time 07:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-09-07 Cont ID  
Sent By jleahy Date 2001-09-07 Time 15:10 Rev Time 4.00
Received By jleahy Date 2001-09-07 Time 15:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-24 Cont ID  
Sent By jleahy Date 2001-05-24 Time 12:37 Rev Time 1.00
Received By jleahy Date 2001-05-24 Time 12:36 Sent To  
Notes
2001-05-24 00:00:00PAGE E-302 HAS A 1200 AMP MAIN WITH ONLY
 1125 AMPS OF WIRE240-3C,110-14C2

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-07-17 Cont ID  
Sent By mamini Date 2001-07-17 Time 16:08 Rev Time 1.00
Received By mamini Date 2001-07-17 Time 16:07 Sent To  
Notes
2001-07-17 00:00:00PASSED:
 1. SEE PERMIT # 01060486
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2002-02-12 Cont ID  
Sent By mcarsill Date 2002-02-12 Time 15:02 Rev Time 0.00
Received By mcarsill Date 2002-02-12 Time 15:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2002-01-17 Cont ID  
Sent By mcarsill Date 2002-01-17 Time 14:08 Rev Time 0.00
Received By mcarsill Date 2002-01-17 Time 14:08 Sent To  
Notes
2002-01-17 00:00:001) PLEASE INDICATE THE LATEST REVISIONS
 ON THE PLAN. THE LAST REVISION APPEARS
 TO BE ON 9.28.01. ACCORDING TO THE
 REVISION FORM IT IS THE FOURTH
 REVISION BEING SUBMITTED. PLEASE
 CLARIFY.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-09-25 Cont ID  
Sent By mcarsill Date 2001-09-25 Time 08:27 Rev Time 0.00
Received By mcarsill Date 2001-09-25 Time 08:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-08-28 Cont ID  
Sent By mcarsill Date 2001-08-28 Time 14:48 Rev Time 0.00
Received By mcarsill Date 2001-08-28 Time 14:48 Sent To  
Notes
2001-08-28 00:00:00THE TEMPORARY FIRE PROTECTION PLANNED
 BY USING DRY HYDRANTS AND A PORTABLE
 PUMP WILL NOT BE ACCEPTED BY THIS
 OFFICE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By mcarsill Date 2001-08-02 Time 13:25 Rev Time 0.00
Received By mcarsill Date 2001-08-02 Time 13:25 Sent To  
Notes
2001-08-02 00:00:001) WATER SUPPLY FOR FIRE HYDRANTS WHEN
 THE BUILDINGS ARE UNDER CONSTRUCTION
 HAS NOT BEEN RESOLVED. THE DEVELOPER
 HAS PROPOSED ALTERNATIVES SINCE A
 WATER MAIN EXTENSION MUST OCCUR. THIS
 ISSUE REMAINS UNRESOLVED.
 2) NOTE ON A-1.4. INDICATES THAT NO
 FIRE SPRINKLER SYSTEM WILL BE PRESENT.
 THIS IS NOT CORRECT.
 3) STORAGE NOT PERMITTED UNDERNEATH
 STAIRS. STORAGE AREAS MUST BE RATED
 THE SAME AS THE STAIRS.
 4) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 5) FIRE ALARM RISER SHOWS E.O.L.'S.
 ONLY CLASS A OR FULLY ADDRESSABLE FIRE
 ALARM SYSTEMS WILL PER PERMITTED.
 6) HOW IS COMBUSTIBLE LINT REMOVED FROM
 THE DRYER EXHAUST RISERS.
 7) PROVIDE MORE DETAILS ON EGRESS
 WINDOWS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2002-02-12 Cont ID  
Sent By pkrauss Date 2002-02-12 Time 14:48 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2002-01-30 Cont ID  
Sent By pkrauss Date 2002-01-30 Time 12:34 Rev Time 0.45
Received By pkrauss Date 2002-01-30 Time 12:30 Sent To  
Notes
2002-01-30 00:00:00*******************DENIED***************
  
  
 PLAN SHEETS M-403 THROUGH M-405, UNDER
 THE NOTE: #4- 1. "VENTILATION SHAFT
 (NOT A FIRE RATED CHASE).PLAN SHEET
 M-206, DETAIL FOR THE DRYER & TOILET
 EXHAUST CALLS FOR A 1 HOUR WALL
 ENCLOSURE.REFEREENCE THE ATTACHED
 LETTER FOR CODE REQUIREMENTS FOR
 EXHAUST DUCT.PLANS NEED TO BE
 CORRECTED TO REFLECT CODE REQUIREMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-08-17 Cont ID  
Sent By pkrauss Date 2001-08-17 Time 15:15 Rev Time 0.35
Received By pkrauss Date   Time   Sent To  
Notes
2001-08-17 00:00:00*******************PROVISO**************
  
  
 DRYER EXHAUST SHALL HAVE A BACK DRAFT
 DAMPER AS PER 509.3.
  
 PLEASE REMOVE / CORRECT NOTES THAT REFER
 TO DETAILS ON PLANS THAT ARE NOT IN THE
 PLAN SET OR HAVE BEEN ADDRESSED ON A
 DIFFERENT PLAN (EXAMPLE: PLAN SHEET
 M-204 NOTES, SHAFT ENCLOSURE DETAIL SEE
 ARCHITECTURAL PLAN SHEET A-13 #25 -
 SHAFT DETAIL IS ON PLAN SHEET M-206).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-07-12 Cont ID  
Sent By pkrauss Date 2001-07-12 Time 11:05 Rev Time 1.00
Received By pkrauss Date 2001-07-12 Time 11:05 Sent To  
Notes
2001-07-12 00:00:00REVIEW NOTES FOR TYPE IV ON PERMIT
 01021178.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-05 Cont ID  
Sent By pkrauss Date 2001-06-05 Time 13:12 Rev Time 2.30
Received By pkrauss Date 2001-06-05 Time 13:12 Sent To  
Notes
2001-06-05 00:00:00REVIEW NOTES UNDER PERMIT 01021175.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-05 Cont ID  
Sent By pkrauss Date 2001-06-05 Time 13:11 Rev Time 1.30
Received By pkrauss Date 2001-06-05 Time 13:11 Sent To  
Notes
2001-06-05 00:00:00REVIEW DONE 4/5/01 UNDER PERMIT 01021175

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-12-16 Cont ID  
Sent By pschmitz Date 2001-12-16 Time 10:55 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-16 00:00:00COMPLETE SET OF REVISIONS,PES

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-09-19 Cont ID  
Sent By kstevens Date 2001-09-19 Time 16:04 Rev Time 0.00
Received By kstevens Date 2001-09-19 Time 16:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-08-18 Cont ID  
Sent By kstevens Date 2001-08-18 Time 13:03 Rev Time 0.00
Received By kstevens Date 2001-08-18 Time 13:03 Sent To  
Notes
2001-08-18 00:00:00DENIED
  
 1) PREVIOUS COMMENTS FOR PLUMBING'S #'S
 1 - 2 - 5 & 6 NOT ADDRESSED.
  
 2) COMMENT #3 DETAIL FOR CONDENSATE
 STILL SHOWS VENT IN PLENUM ON PLUMBING
 PAGES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-07-16 Cont ID  
Sent By jleech Date 2001-07-16 Time 11:45 Rev Time 0.00
Received By jleech Date 2001-07-16 Time 11:45 Sent To  
Notes
2001-07-16 00:00:00SEE PLAN REVIEW NOTES PERMIT #01021175
 AND 01021194.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-12-05 Cont ID  
Sent By jwitmer Date 2001-12-05 Time 15:05 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-12-05 00:00:00MASTER TYPE IV BUILDING