Plan Review Details - Permit 01021178
Plan Review Stops For Permit 01021178
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2002-09-20 Cont ID  
Sent By jwitmer Date 2002-09-20 Time 13:39 Rev Time 2.00
Received By jwitmer Date 2002-09-20 Time 11:26 Sent To  
Notes
2002-09-20 00:00:00REV# 4 9/9/02OKJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2002-02-06 Cont ID  
Sent By jwitmer Date 2002-02-06 Time 09:50 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-02-06 00:00:00GARAGE DOOR: PRESSURES LOW

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2001-11-27 Cont ID  
Sent By jwitmer Date 2001-11-27 Time 11:57 Rev Time 3.50
Received By jwitmer Date 2001-11-27 Time 11:57 Sent To  
Notes
2001-11-27 00:00:00SAN MARINO PROJECT
 TYPE II BUILDING
 MASTER# 01021178
  
 1)- THE REVISIONS SUBMITTED NOV.1/01 TO
 THE BUILDING DEPARTMENT AS REVISION DATE
 9/28/01 ARE IDENTICAL TO THE PLANS ON RE
 CORD. THE DELTA OR TRIANGLE IDENTIFICA-
 TION ISN'T GIVING ENOUGH INFORMATION TO
 DETERMINE WHAT THE ACTUAL REVISION IS
 FOR? IT MAY HELP TO HAVE A SUMMARY FOR
 EACH PAGE WHAT THE REVISION IS ABOUT.
 2) THE MECHANICAL SHEETS INDICATE A VENT
 ILATION SHAFT, THE SBC TABLE 705.1.2
 INDICATES THAT A 1 HR RATING WILL BE
 REQUIRED FOR STUCTURES LESS THAN 4 STOR-
 IES.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-09-27 Cont ID  
Sent By jwitmer Date 2001-09-27 Time 12:02 Rev Time 5.00
Received By jwitmer Date 2001-09-27 Time 12:02 Sent To  
Notes
2001-09-27 00:00:00MASTER BUILD MODEL II
 BUILDING # 4,13 & 15

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-07-24 Cont ID  
Sent By jwitmer Date 2001-07-24 Time 18:48 Rev Time 0.00
Received By jwitmer Date 2001-09-27 Time 12:02 Sent To  
Notes
2001-07-24 00:00:00BUILDING TYPE II
 PLAN CHECK : 01021178
  
 1)- ALL BUILDING COMMENTS HAVE BEEN
 IMPLEMENTED WITH EXECTION TO GLAZED OPEN
 INGS, NO INFORMATION ON WINDOWS,
 DOORS, & GARAGE DOORS. SEE CITY POLICY
 FOR LARGE MISSLE IMPACT RESISTANT
 GLAZING & STORM SHUTTERS.
 2)- THERE IS ALSO NO PRODUCT INFORMATION
 FOR THE ROOFING SYSTEM.
  
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-06-12 Cont ID  
Sent By jwitmer Date 2001-06-12 Time 08:48 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-12 00:00:00TYPE II BUILDING
 BUILDINGS # 4,13 &15
 PLAN REVIEW # 01021178
 ARCH: MOURIZ SALAZAR
 PHONE;: (305) 273-9911
 FAX: (305)
  
 BUILDING 4 TYPE II
  
 SAME COMMENTS AS RREVIEW 01021175 &
 GENERAL COMMENTS UNDER CLUBHOUSE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-04 Cont ID  
Sent By jwitmer Date 2001-04-04 Time 15:10 Rev Time 4.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-04 00:00:00TYPE II BUILDING
 BUILDING # 4,13 & 15
 PROJECT: 01021178
 ARCH. MOURIZ SALAZAR
 PHONE (305) 273-9911
 FAX)305)
 BUILDING 4TYPE II
  
 1)- SBC 1007.3.1: STAIR CALCULATION
 REQUIRES BETWEEN >24" &<25".
  
 2)- GENERAL STRUCTURAL NOTES S-4 (11)
 DESIGN LOADS,
 A)- DESIGN IS TO COMPLY WITH THE 1997
 STANDARD BUILDING CODE.
 B)- WIND LOAD CRITERIA, BASIC LOAD
 VELOCITY 110 MPH, ASCE 7-95.
  
 3)- FAIR HOUSING ACT CHAPTER 6.
 A)- LOCATION OF GRAB BARS FOR TUB IS
 32" MIN. & 38" MAXIMUM.
 B)- WATER CLOSET BACKING BEHIND THE
 WATER CLOSET WHEN THER IS NO WING
 WALL.SEE PAGES A-5.1,5.2,5.3, 5.6
 AND 5.10.
 C)_ A 5.6 MASTER BATH LAV DOES NOT MEET
 THE PARALLEL APPROACH AT THE LAV,
 30" X 48" ARE REQUIRED.
 D)- SHEET A-6: MAIL BOXES: FAIR HOUSING
 CHAPTER 2 REFERS TO FL ACCC CODE
 REACH & RANGES, SIDE APPROACH
 SECTION (4.2.6) MAX. HEIGTH 54"
 MIN. HEITH 0"-9".
 E)_ S-1.1, (4) C-1 APARTMENTS DEPICTS
 1/2" VERTICAL DROP + THRESHOLD, SEE
 FL ACC. CODE 4.13.8 THRESSHOLDS AT
 DOORWAYS, 2/1.
  
 4)- SHEET A-9 DETAIL #28: SOFFIT DETAIL
 DOESN'T GIVE THE ANCHORAGE TO THE STRUC-
 TURAL SLAB ABOVE.
  
 5)_ SHEET A 4.1 2ND FL UNIT C-1 DETAILS
 39/43, MISSING1 LAYER OF 1/2"DRYWALL.
  
 6)SH A4-5 NOTE 20, HI BIBBED LATH,
 SBC 2504.2.2 SEC ASTM C 1063.7.10.23
 3/8" RIB LATH ATTACHED TO HORIZONTAL
 WOOD SUPPORTS REQUIRES NAILS OR STAPLES
 TO PROVIDE 1 3/4" PENETRATION INTO
 HORIZONTAL WOOD SUPPORTS, 3/4" INTO
 VERTICAL SUPPORTS.
  
 7)- SHEET A 3.1 NOTE #12, CANVAS AWNINGS
 ON TUBULAR STEEL FRAMES REQUIRES A SEP-
 ERATE PERMIT, (PER BUILDING).
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-01-23 Cont ID  
Sent By dpalmer Date 2002-01-23 Time 10:50 Rev Time 0.00
Received By dpalmer Date 2002-01-23 Time 10:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-11-07 Cont ID  
Sent By dpalmer Date 2001-11-07 Time 22:37 Rev Time 0.00
Received By dpalmer Date 2001-11-07 Time 22:37 Sent To  
Notes
2001-11-07 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT CHANGES ON
 PLANS NEED TO BE IDENTIFIED BY CLOUDS
 OR TRIANGLES.
  
 PLEASE SUBMIT FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-09-07 Cont ID  
Sent By jleahy Date 2001-09-07 Time 15:07 Rev Time 4.00
Received By jleahy Date 2001-09-07 Time 15:06 Sent To  
Notes
2001-09-07 00:00:00NO ROMEX TO BE USED, CHECK CLEARANCE ON
 DISCONNECTS, CHECK WATERHEATERS FOR
 DISCONNECTS WHEN NOT INSIGHT OF PANEL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-24 Cont ID  
Sent By jleahy Date 2001-05-24 Time 12:23 Rev Time 1.00
Received By jleahy Date 2001-05-24 Time 12:22 Sent To  
Notes
2001-05-24 00:00:00PAGE E-202 HAS A 1200 AMP MAIN WITH ONLY
 1125 AMPS OF WIRE240-3C, 110-14C2

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-07-17 Cont ID  
Sent By mamini Date 2001-07-17 Time 16:04 Rev Time 1.00
Received By mamini Date 2001-07-17 Time 16:04 Sent To  
Notes
2001-07-17 00:00:00PASSED:
 1. SEE PERMIT # 01060486
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2002-02-12 Cont ID  
Sent By mcarsill Date 2002-02-12 Time 15:05 Rev Time 0.00
Received By mcarsill Date 2002-02-12 Time 15:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2002-02-07 Cont ID  
Sent By mcarsill Date 2002-02-07 Time 10:10 Rev Time 0.00
Received By mcarsill Date 2002-02-07 Time 10:10 Sent To  
Notes
2002-02-07 00:00:001) MECHANICAL NOTES REGARDING
 VENTILATION SHAFT IS NOT CORRECT.
 REVISED PLANS ARE TO BE MORE DETAIL
 SO THE REVISIONS CAN BE PROPERLY
 RECOGNIZED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-11-21 Cont ID  
Sent By mcarsill Date 2001-11-21 Time 10:19 Rev Time 0.00
Received By mcarsill Date 2001-11-21 Time 10:19 Sent To  
Notes
2001-11-21 00:00:001) PLEASE EXPLAIN VENTILATION SHAFT.
 SHAFTS ARE REQUIRED TO BE FIRE RATED.
 THE SHAFT ON PAGES M-203,204 AND 205
 INDICATE VENTILATION SHAFTS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-09-25 Cont ID  
Sent By mcarsill Date 2001-09-25 Time 08:19 Rev Time 0.00
Received By mcarsill Date 2001-09-25 Time 08:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-28 Cont ID  
Sent By mcarsill Date 2001-08-28 Time 15:05 Rev Time 0.00
Received By mcarsill Date 2001-08-28 Time 15:05 Sent To  
Notes
2001-08-28 00:00:00THE TEMPORARY FIRE PROTECTION BY USING
 DRY HYDRANTS AND A PORTABLE PUMP WILL
 NOT BE ACCEPTED BY THIS OFFICE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2002-02-12 Cont ID  
Sent By pkrauss Date 2002-02-12 Time 14:47 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2002-01-30 Cont ID  
Sent By pkrauss Date 2002-01-30 Time 10:56 Rev Time 0.45
Received By pkrauss Date 2002-01-30 Time 10:55 Sent To  
Notes
2002-01-30 00:00:00*******************DENIED***************
  
  
 PREVIOUS COMMENTS NEVER ADDRESSED.
  
 PLAN SHEET M-204 NOTES:#4 1,
 "VENTILATION SHAFT (NOT A FIRE RATED
 CHASE)".
  
 DUCTS PENETRATING MORE THAN 1 FLOOR
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 AS PER 1997 SMC 610.4 & NFPA 90A 3-3.4.
 1 HOUR RATING FOR BUILDINGS LESS THAN 4
 STORIES AND 2 HOUR RATING FOR 4 STORIES
 AND MORE IN HEIGHT.
  
 THE ABOVE ISSUE WAS DISCUSSED IN A
 MEETING ON JANUARY18, 2002.PLEASE
 SEE ATTACHED LETTER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2001-11-19 Cont ID  
Sent By pkrauss Date 2001-11-19 Time 15:03 Rev Time 0.50
Received By pkrauss Date 2001-11-19 Time 14:54 Sent To  
Notes
2001-11-19 00:00:00******************DENIED****************
  
  
 REVISED PLAN SHEETS M-203,204 & 205
 UNDER NOTES:4. (1) VENTILATION SHAFT
 NOT A FIRE RATED CHASE.AS PER 1997
 SMC 610.4, DUCTS EXTENDING THROUGH MORE
 THAN ONE FLOOR SHALL BE PROTECTED BY A
 SHAFT ENCLOSURE HAVE A FIRE RESISTANCE
 OF NOT LESS THAN 1 HOUR FOR BUIDLINGS
 LESS THAN FOUR STORIES IN HEIGHT (2 HR -
 FOR BUIDLINGS 4 STORIES AND MORE).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-08-17 Cont ID  
Sent By pkrauss Date 2001-08-17 Time 15:16 Rev Time 0.35
Received By pkrauss Date   Time   Sent To  
Notes
2001-08-17 00:00:00******************PROVISO***************
  
  
 DRYER EXHAUST SHALL HAVE A BACK DRAFT
 DAMPER AS PER 509.3.
  
 PLEASE REMOVE / CORRECT NOTES THAT REFER
 TO DETAIL ON PLANS THAT ARE NOT IN THE
 PLAN SEST OF HAVE BEEN ADDRESSED ON A
 DIFFERENT PLAN (EXAMPLE: PLAN SHEET
 M-204 NOTES, SHAFT ENCLOSER DETAIL SEE
 ARCHITECTURAL PLAN SHEET M-206).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-07-12 Cont ID  
Sent By pkrauss Date 2001-07-12 Time 10:48 Rev Time 1.00
Received By pkrauss Date 2001-07-12 Time 09:46 Sent To  
Notes
2001-07-12 00:00:00*******************PROVISO**************
  
 TYPE IV
  
 NOTHING ON PLANS HAVE CHANGED.
  
 PLEASE TAKE NOTE TO THE FOLLOWING ISSUES
  
  
 1.AS STATED IN REVIEW DATED 6/5/01,
 PLAN M-106 DETAIL OF A/C CLOSET,
 PROVIDE OVERFLOW PAN FOR UPPER
 FLOORS ONLY....OVERFLOW PAN SHALL
 GO ON EVERY FLOOR TO PREVENT DAMAGE
 TO CARPET, WALLS AND INTERIOR OF
 APARTMENT.
  
 2.AS DISCUSSED IN MEETING WITH CARLOS
 AT CITY HALL, AS PER AMENDED 1997
 SPC 804.3, #5. CONDENSATE DRAINS
 SHALL VENT TO ATMOSPHERE, IT SHALL
 NOT VENT INTO THE WALL AS SHOWN ON
 THE DETAIL.SHOULD TERMINATION BE
 IN THE ATTIC, IT SHALL BE A MINIMUM
 OF 6" ABOVE THE INSULATION.
  
 PLEASE REMOVE/CORRECT NOTES THAT REFER
 TO DETAILS ON PLANS THAT ARE NOT IN THE
 PLAN SET OR ARE ON A DIFFERENT PLAN ALL
 TOGETHER (EXAMPLE:SHAFT ENCLOSURE IS
 SAID TO BE ON ARCHITECTURAL PLAN SHEET
 A-13 #25).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-05 Cont ID  
Sent By pkrauss Date 2001-06-05 Time 13:13 Rev Time 2.30
Received By pkrauss Date 2001-06-05 Time 13:13 Sent To  
Notes
2001-06-05 00:00:00REVIEW DONE UNDER PERMIT 01021175.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-04-06 Cont ID  
Sent By pkrauss Date 2001-04-06 Time 14:42 Rev Time 1.30
Received By pkrauss Date 2001-04-06 Time 14:51 Sent To  
Notes
2001-04-06 00:00:00******************DENIED****************
  
 APARTMENT BUILDING #4, 13 & 15TYPE II

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-12-15 Cont ID  
Sent By pschmitz Date 2001-12-15 Time 12:03 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-16 00:00:00COMPLETE SET OF REVISIONS,PES
2001-12-15 00:00:00REVISION, OKPES

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-11-21 Cont ID  
Sent By kstevens Date 2001-11-21 Time 10:45 Rev Time 0.50
Received By kstevens Date 2001-11-21 Time 10:45 Sent To  
Notes
2001-11-21 00:00:00REVISION DENIED
 REFERENCE: SPC-94 - FHA AMEND 98 DESIGN
 MANUAL
  
 1) REVISION PAGES DO NOT MATCH PAGE NUM-
 ER IN MASTER SET REVIEWED FOR PERMIT.
  
 2) ALL REVISIONS SHALL BE DATED AND IN-
 DICATED WITH EITHER A CLOUD, DART. OR
 TRIANGLE FOR REVIEW
  
 3) PLEASE RESUBMIT REVISION WITH MATCH-
 PAGE NUMBERS AND SHOW WHAT IS BEING
 REVISED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-11-16 Cont ID  
Sent By kstevens Date 2001-11-16 Time 11:33 Rev Time 0.50
Received By kstevens Date 2001-11-16 Time 11:33 Sent To  
Notes
2001-11-16 00:00:00DENIED
  
 1) PLEASE DATE REVISIONS SO THEY CAN BE
 SEPARATED FROM PAST AND/OR FUTURE REVIS-
 IONS.
  
 2) REVISIONS SHALL BE INDICATED WITH
 DARTS, TRIANGLES, OR CLOUDS TO INDICATE
 WHERE REVISIONS ARE LOCATED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-09-07 Cont ID  
Sent By pschmitz Date 2001-09-07 Time 15:25 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-09-07 00:00:00PLUMBING PLAN REVIEW, PROVISO.
 WATER HAMMER ARRESTORS INSTALLED FOR
 SIZE AND LOCATION, PER MFG INSTRUCTIONS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-07-16 Cont ID  
Sent By jleech Date 2001-07-16 Time 11:43 Rev Time 0.00
Received By jleech Date 2001-07-16 Time 11:43 Sent To  
Notes
2001-07-16 00:00:00SEE PLAN REVIEW NOTES PERMIT #01021194
 AND 01021175.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-03 Cont ID  
Sent By jwitmer Date 2001-10-03 Time 11:39 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-10-03 00:00:00ZON: MICHEAL SANCHEUZ 10/3/01


Account Summary | Usage Policy | Privacy Policy