| Plan Review Stops For Permit 01021176 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2002-02-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-02-06 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-02-06 00:00:00 | GARAGE DOOR: PRESSURE TO LOW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-11-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-27 |
Time |
15:50 |
Rev Time |
2.50 |
| Received By |
jwitmer |
Date |
2001-11-27 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2001-11-27 00:00:00 | BUILDING REVISION TYPE III BUILDING | | | REVISION DATED 9/28/01 | | | MASTER# 01021176 | | | | | | 1)- THE REVISIONS SUBMITTED NOV.1/01 | | | TO THE BUILDING DEPARTMENT AS REVISION | | | DATE 9/28/01 ARE IDENTICAL TO THE PLANS | | | ON RECORD. THE DELTA OR TRIANGLE | | | IDENTIFICATION ISN'T GIVING ENOUGH | | | INFORMATION TO DETERMINE WHAT THE REVISI | | | ON IS FOR. IT MAY HELP TO HAVE A SUMMARY | | | FOR EACH PAGE, WHAT THE REVISION IS | | | ABOUT? | | | 2) THE MECHANICAL SHEETS INDICATE A VENT | | | THROUGH VARIOUS FLOORS, SBC TABLE | | | 705.1.2 INDICATES A 1 HR SHAFT . | | | 3)- A REVISION FROM SLIDING GLASS DOORS | | | TO SWING STYLE FRENCH DOOR, PRODUCT | | | APPROVAL REQUIRED, LARGE MISSLE IMPACT | | | TESTING, 3 COPIES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-09-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-09-27 |
Time |
12:05 |
Rev Time |
5.00 |
| Received By |
jwitmer |
Date |
2001-09-27 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2001-09-27 00:00:00 | MASTER MODEL TYPE III | | | BUILDINGS 2,6,9,11,16&17 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-06-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-06-12 |
Time |
09:49 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-12 00:00:00 | TYPE III BUILDING | | | BUILDINGS 2,6,9,11,14,16 & 17 | | | PLAN REVIEW 01021176 | | | ARCH MOURIZ SALAZAR | | | PHONE (305) 273-9911 | | | FAX(305) | | | BUILDING 2TYPE III | | | | | | SAME COMMENTS AS ON PLAN REVIEW01021175 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-04-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-04-04 |
Time |
17:34 |
Rev Time |
3.75 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-04-04 00:00:00 | | | | TYPE III BUILDING | | | BUILDINGS: 2,6,9,11,14,16 & 17 | | | PROJECT: 01021176 | | | ARCH. MOURIZ SALAZAR | | | PHONE (305) 273-9911 | | | FAX(305) | | | BUILDING 2 TYPE III | | | | | | | | | NOTE: AREA INCREASE REQUIRED WILL BE | | | REQUIRED TO BE USED, AS INDICATED ON | | | PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-01-30 |
Time |
21:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2001-11-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-07 |
Time |
22:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-07 |
Time |
22:46 |
Sent To |
|
|
| Notes |
| 2001-11-07 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT ALL CHANGES/ | | | REVISIONS NEED TO BE IDENTIFIED BY | | | CLOUDS OR TRIANGLES. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE NAY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELELCTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-09-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2001-09-27 |
Time |
13:55 |
Rev Time |
4.00 |
| Received By |
jleahy |
Date |
2001-09-27 |
Time |
13:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-05-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2001-05-24 |
Time |
12:27 |
Rev Time |
1.00 |
| Received By |
jleahy |
Date |
2001-05-24 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2001-05-24 00:00:00 | PAGE E-302 HAS A 1200 AMP MAIN WITH ONLY | | | 1125 AMPS OF WIRE240-3C,100-16C2 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2001-07-17 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-07-17 |
Time |
16:36 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2001-07-17 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2001-07-17 00:00:00 | PASSED : | | | 1. SEE PERMIT # 01060486 | | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | | EXT. 8496 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2002-02-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-12 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-12 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2002-01-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-01-16 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-01-16 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2002-01-16 00:00:00 | 1) PLEASE CLEARLY IDENTIFY THE NEW | | | REVISIONS WITH CLOUDS OR TRIANGLES. | | | THE PLANS SHOW THE LAST REVISION AS | | | 9.28.01. IT APPEARS ON THE RESUBMITTAL | | | FORM THAT THIS IS THE FIFTH REVISION. | | | PLEASE CORRELATE INFORMATION. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-09-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-25 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-25 |
Time |
08:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2002-02-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-12 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
F |
Date |
2002-01-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-30 |
Time |
15:16 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-01-30 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2002-01-30 00:00:00 | *******************DENIED*************** | | | | | | | | | PLAN SHEET M-302 THROUGH M-305 NOTES: | | | #4- 1,"VENTILATION SHAFT (NOT A FIRE | | | RATED CHASE)". | | | | | | DUCTS PENETRATING MORE THAN 1 FLOOR | | | SHALL BE PROTECTED BY A SHAFT ENCLOSURE | | | AS PER 1997 SMC 610.4 & NFPA 90A | | | 3-3.4.1.1 HOUR RATING IS REQUIRED FOR | | | BUILDINGS LESS THAN 4 STORIES AND 2 | | | HOUR RATING FOR BUILDINGS 4 STORIES AND | | | MORE IN HEIGHT. | | | | | | | | | THE ABOVE ISSUED WAS DISCUSSED IN A | | | MEETING ON JANUARY 18,2002.PLEASE SEE | | | ATTACHED LETTER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2001-11-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-19 |
Time |
15:39 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-11-19 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2001-11-19 00:00:00 | *******************DENIED*************** | | | | | | | | | REVISION FOR PLAN SHEET M-303,304 & | | | 305,INDICATE A REVISION (TRIANGLE) | | | DATED 5/7/01.THIS WAS NOT A REVISION | | | AND WAS NOT WITH THE PLANS APPROVED FOR | | | PERMIT.DUCTS PENETRATING MORE THAN 1 | | | FLOOR SHALL BE PROTECTED BY A SHAFT | | | ENCLOSURE AS PER 1997 SMC 610.4. | | | | | | PLEASE INDICATE ALL CHANGES BY CLOUDS | | | AND TRIANGLES ALONG WITH THE DATE OF | | | THE REVISION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2001-09-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-12 |
Time |
08:13 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-09-12 |
Time |
08:06 |
Sent To |
|
|
| Notes |
| 2001-09-12 00:00:00 | *******************PROVISO************** | | | | | | | | | DRYER EXHAUST SHALL HAVE A BACKDRAFT | | | DAMPER AS PRE 509.3. | | | | | | PLEASE REMOVE / CORRECT NOTES THAT REFER | | | TO DETAILS ON PLANS THAT ARE NOT IN THE | | | PLAN SET OR HAVE BEEN ADDRESSED ON A | | | DIFFERENT PLAN (EXAMPLE:PLAN SHEET | | | M-204 NOTES, SHAFT ENCLOSURE DETAL SEE | | | ARCHITECTURAL PLAN SHEET A-13 #25 - | | | SHAFT DETAIL IS ON PLAN SHEET M-206). | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-07-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-23 |
Time |
12:35 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-07-23 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2001-07-23 00:00:00 | ******************PROVISO*************** | | | | | | THE FOLLOWING ISSUES WHERE NOT ADDRESSED | | | FROM THE PREVIOUS REVIEW.PLEASE SUBMI | | | T REVISED DRAWINGS PRIOR TO FIRST INSPEC | | | TION. | | | | | | 1.AHU #2 NEEDS A RETURN AIR IN THE | | | "FUN CENTER". | | | | | | 2.AHU #1 NEEDS A RETURN AIR FROM THE | | | "CLUBROOM" AND THE "RECEPTION AREA". | | | | | | 3.PLAN NUMBER M-2.C, A/C CLOSET DETAIL | | | INDICATES VENT FROM CONDENSATE LINE | | | IS IN THE WALL.CONDENSATE SHALL | | | VENT TO THE ATMOSHPERE, AS PER | | | AMENDED 1994 SPC 804.3, #5.SHOULD | | | VENT TERMINATE IN THE ATTIC, IT | | | SHALL BE A MINIMUM OF 6" ABOVE THE | | | INSULATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-06-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-05 |
Time |
13:42 |
Rev Time |
2.30 |
| Received By |
pkrauss |
Date |
2001-06-05 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2001-06-05 00:00:00 | REVIEW DONE UNDER PERMIT 01021175. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-06-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-05 |
Time |
13:34 |
Rev Time |
2.30 |
| Received By |
pkrauss |
Date |
2001-06-05 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2001-06-05 00:00:00 | NOTES UNDER PERMIT 01021175. | | | | | | THIS IS RESUBMITTAL. ORIGINAL REVIEW | | | DONE 4/5/01. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2001-12-15 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-12-15 |
Time |
11:54 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-12-16 00:00:00 | COMPLETE SET OF REVISIONS,PES | | 2001-12-15 00:00:00 | REVISION, OK PES. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2001-11-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-21 |
Time |
09:50 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2001-11-21 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2001-11-21 00:00:00 | REVISION DENIED | | | REFERENCE: SPC-94 - FHA AMEND 98 DESIGN | | | MANUAL | | | | | | 1) REVISION PAGES DO NOT MATCH PAGE NUM- | | | BERS IN MASTER SET REVIEW FOR PERMIT. | | | 2) ALL REVISIONS SHALL BE DATED AND IN- | | | DICATED WITH EITHER A CLOUD, DART, OR | | | TRIANGLE FOR REVIEW. | | | 3) PAGE SUBMITTED P-3.1 PIPE SIZE FOR | | | BLDG DRAIN NOT APPROVED. ONLY 180 FU | | | ALLOWED ON 4" PIPE AT 1/8" PER FOOT. | | | 4) PLEASE RESUBMIT REVISION WITH MATCH- | | | ING PAGE NUMBERS AND SHOW WHAT IS BEING | | | REVISED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-11-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-16 |
Time |
11:41 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-11-16 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2001-11-16 00:00:00 | DENIED | | | | | | 1) PLEASE DATE REVISIONS SO THEY CAN BE | | | SEPARATED FROM PAST AND/OR FUTURE REVIS- | | | IONS. | | | | | | 2) REVISIONS SHALL BE INDICATED WITH | | | DARTS, TRIANGLES, OR CLOUDS TO INDICATE | | | WHERE REVISIONS ARE LOCATED. | | | | | | REVISION BY KEN STEVENS | | | (561) 569-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-09-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-19 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2001-09-19 |
Time |
16:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-07-16 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-07-16 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2001-07-16 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2001-07-16 00:00:00 | SEE PLAN REVIEW NOTES PERMIT # 01021175 | | | AND 01021194 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-10-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-03 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-03 00:00:00 | ZON: PER MICHAEL SANCHEUZ 10/3/01 |
|
|