Plan Review Details - Permit 01021176
Plan Review Stops For Permit 01021176
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2002-02-06 Cont ID  
Sent By jwitmer Date 2002-02-06 Time 09:51 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-02-06 00:00:00GARAGE DOOR: PRESSURE TO LOW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-11-27 Cont ID  
Sent By jwitmer Date 2001-11-27 Time 15:50 Rev Time 2.50
Received By jwitmer Date 2001-11-27 Time 13:25 Sent To  
Notes
2001-11-27 00:00:00BUILDING REVISION TYPE III BUILDING
 REVISION DATED 9/28/01
 MASTER# 01021176
  
 1)- THE REVISIONS SUBMITTED NOV.1/01
 TO THE BUILDING DEPARTMENT AS REVISION
 DATE 9/28/01 ARE IDENTICAL TO THE PLANS
 ON RECORD. THE DELTA OR TRIANGLE
 IDENTIFICATION ISN'T GIVING ENOUGH
 INFORMATION TO DETERMINE WHAT THE REVISI
 ON IS FOR. IT MAY HELP TO HAVE A SUMMARY
 FOR EACH PAGE, WHAT THE REVISION IS
 ABOUT?
 2) THE MECHANICAL SHEETS INDICATE A VENT
 THROUGH VARIOUS FLOORS, SBC TABLE
 705.1.2 INDICATES A 1 HR SHAFT .
 3)- A REVISION FROM SLIDING GLASS DOORS
 TO SWING STYLE FRENCH DOOR, PRODUCT
 APPROVAL REQUIRED, LARGE MISSLE IMPACT
 TESTING, 3 COPIES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-09-27 Cont ID  
Sent By jwitmer Date 2001-09-27 Time 12:05 Rev Time 5.00
Received By jwitmer Date 2001-09-27 Time 12:04 Sent To  
Notes
2001-09-27 00:00:00MASTER MODEL TYPE III
 BUILDINGS 2,6,9,11,16&17

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-06-12 Cont ID  
Sent By jwitmer Date 2001-06-12 Time 09:49 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-12 00:00:00TYPE III BUILDING
 BUILDINGS 2,6,9,11,14,16 & 17
 PLAN REVIEW 01021176
 ARCH MOURIZ SALAZAR
 PHONE (305) 273-9911
 FAX(305)
 BUILDING 2TYPE III
  
 SAME COMMENTS AS ON PLAN REVIEW01021175

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-04 Cont ID  
Sent By jwitmer Date 2001-04-04 Time 17:34 Rev Time 3.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-04 00:00:00 
 TYPE III BUILDING
 BUILDINGS: 2,6,9,11,14,16 & 17
 PROJECT: 01021176
 ARCH. MOURIZ SALAZAR
 PHONE (305) 273-9911
 FAX(305)
 BUILDING 2 TYPE III
  
  
 NOTE: AREA INCREASE REQUIRED WILL BE
 REQUIRED TO BE USED, AS INDICATED ON
 PLANS.

Review Stop E ELECTRICAL
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dpalmer Date 2002-01-30 Time 21:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-11-07 Cont ID  
Sent By dpalmer Date 2001-11-07 Time 22:46 Rev Time 0.00
Received By dpalmer Date 2001-11-07 Time 22:46 Sent To  
Notes
2001-11-07 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT ALL CHANGES/
 REVISIONS NEED TO BE IDENTIFIED BY
 CLOUDS OR TRIANGLES.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE NAY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELELCTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-09-27 Cont ID  
Sent By jleahy Date 2001-09-27 Time 13:55 Rev Time 4.00
Received By jleahy Date 2001-09-27 Time 13:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-24 Cont ID  
Sent By jleahy Date 2001-05-24 Time 12:27 Rev Time 1.00
Received By jleahy Date 2001-05-24 Time 12:26 Sent To  
Notes
2001-05-24 00:00:00PAGE E-302 HAS A 1200 AMP MAIN WITH ONLY
 1125 AMPS OF WIRE240-3C,100-16C2

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-07-17 Cont ID  
Sent By mamini Date 2001-07-17 Time 16:36 Rev Time 1.00
Received By mamini Date 2001-07-17 Time 16:36 Sent To  
Notes
2001-07-17 00:00:00PASSED :
 1. SEE PERMIT # 01060486
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8496 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-02-12 Cont ID  
Sent By mcarsill Date 2002-02-12 Time 15:04 Rev Time 0.00
Received By mcarsill Date 2002-02-12 Time 15:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-01-16 Cont ID  
Sent By mcarsill Date 2002-01-16 Time 15:39 Rev Time 0.00
Received By mcarsill Date 2002-01-16 Time 15:39 Sent To  
Notes
2002-01-16 00:00:001) PLEASE CLEARLY IDENTIFY THE NEW
 REVISIONS WITH CLOUDS OR TRIANGLES.
 THE PLANS SHOW THE LAST REVISION AS
 9.28.01. IT APPEARS ON THE RESUBMITTAL
 FORM THAT THIS IS THE FIFTH REVISION.
 PLEASE CORRELATE INFORMATION.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-09-25 Cont ID  
Sent By mcarsill Date 2001-09-25 Time 08:28 Rev Time 0.00
Received By mcarsill Date 2001-09-25 Time 08:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2002-02-12 Cont ID  
Sent By pkrauss Date 2002-02-12 Time 14:48 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2002-01-30 Cont ID  
Sent By pkrauss Date 2002-01-30 Time 15:16 Rev Time 0.45
Received By pkrauss Date 2002-01-30 Time 15:16 Sent To  
Notes
2002-01-30 00:00:00*******************DENIED***************
  
  
 PLAN SHEET M-302 THROUGH M-305 NOTES:
 #4- 1,"VENTILATION SHAFT (NOT A FIRE
 RATED CHASE)".
  
 DUCTS PENETRATING MORE THAN 1 FLOOR
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 AS PER 1997 SMC 610.4 & NFPA 90A
 3-3.4.1.1 HOUR RATING IS REQUIRED FOR
 BUILDINGS LESS THAN 4 STORIES AND 2
 HOUR RATING FOR BUILDINGS 4 STORIES AND
 MORE IN HEIGHT.
  
  
 THE ABOVE ISSUED WAS DISCUSSED IN A
 MEETING ON JANUARY 18,2002.PLEASE SEE
 ATTACHED LETTER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2001-11-19 Cont ID  
Sent By pkrauss Date 2001-11-19 Time 15:39 Rev Time 0.50
Received By pkrauss Date 2001-11-19 Time 15:39 Sent To  
Notes
2001-11-19 00:00:00*******************DENIED***************
  
  
 REVISION FOR PLAN SHEET M-303,304 &
 305,INDICATE A REVISION (TRIANGLE)
 DATED 5/7/01.THIS WAS NOT A REVISION
 AND WAS NOT WITH THE PLANS APPROVED FOR
 PERMIT.DUCTS PENETRATING MORE THAN 1
 FLOOR SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE AS PER 1997 SMC 610.4.
  
 PLEASE INDICATE ALL CHANGES BY CLOUDS
 AND TRIANGLES ALONG WITH THE DATE OF
 THE REVISION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-09-12 Cont ID  
Sent By pkrauss Date 2001-09-12 Time 08:13 Rev Time 0.45
Received By pkrauss Date 2001-09-12 Time 08:06 Sent To  
Notes
2001-09-12 00:00:00*******************PROVISO**************
  
  
 DRYER EXHAUST SHALL HAVE A BACKDRAFT
 DAMPER AS PRE 509.3.
  
 PLEASE REMOVE / CORRECT NOTES THAT REFER
 TO DETAILS ON PLANS THAT ARE NOT IN THE
 PLAN SET OR HAVE BEEN ADDRESSED ON A
 DIFFERENT PLAN (EXAMPLE:PLAN SHEET
 M-204 NOTES, SHAFT ENCLOSURE DETAL SEE
 ARCHITECTURAL PLAN SHEET A-13 #25 -
 SHAFT DETAIL IS ON PLAN SHEET M-206).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-07-23 Cont ID  
Sent By pkrauss Date 2001-07-23 Time 12:35 Rev Time 0.45
Received By pkrauss Date 2001-07-23 Time 12:35 Sent To  
Notes
2001-07-23 00:00:00******************PROVISO***************
  
 THE FOLLOWING ISSUES WHERE NOT ADDRESSED
 FROM THE PREVIOUS REVIEW.PLEASE SUBMI
 T REVISED DRAWINGS PRIOR TO FIRST INSPEC
 TION.
  
 1.AHU #2 NEEDS A RETURN AIR IN THE
 "FUN CENTER".
  
 2.AHU #1 NEEDS A RETURN AIR FROM THE
 "CLUBROOM" AND THE "RECEPTION AREA".
  
 3.PLAN NUMBER M-2.C, A/C CLOSET DETAIL
 INDICATES VENT FROM CONDENSATE LINE
 IS IN THE WALL.CONDENSATE SHALL
 VENT TO THE ATMOSHPERE, AS PER
 AMENDED 1994 SPC 804.3, #5.SHOULD
 VENT TERMINATE IN THE ATTIC, IT
 SHALL BE A MINIMUM OF 6" ABOVE THE
 INSULATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-05 Cont ID  
Sent By pkrauss Date 2001-06-05 Time 13:42 Rev Time 2.30
Received By pkrauss Date 2001-06-05 Time 13:42 Sent To  
Notes
2001-06-05 00:00:00REVIEW DONE UNDER PERMIT 01021175.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-06-05 Cont ID  
Sent By pkrauss Date 2001-06-05 Time 13:34 Rev Time 2.30
Received By pkrauss Date 2001-06-05 Time 13:33 Sent To  
Notes
2001-06-05 00:00:00NOTES UNDER PERMIT 01021175.
  
 THIS IS RESUBMITTAL. ORIGINAL REVIEW
 DONE 4/5/01.

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-12-15 Cont ID  
Sent By pschmitz Date 2001-12-15 Time 11:54 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-16 00:00:00COMPLETE SET OF REVISIONS,PES
2001-12-15 00:00:00REVISION, OK PES.

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-11-21 Cont ID  
Sent By kstevens Date 2001-11-21 Time 09:50 Rev Time 1.25
Received By kstevens Date 2001-11-21 Time 09:50 Sent To  
Notes
2001-11-21 00:00:00REVISION DENIED
 REFERENCE: SPC-94 - FHA AMEND 98 DESIGN
 MANUAL
  
 1) REVISION PAGES DO NOT MATCH PAGE NUM-
 BERS IN MASTER SET REVIEW FOR PERMIT.
 2) ALL REVISIONS SHALL BE DATED AND IN-
 DICATED WITH EITHER A CLOUD, DART, OR
 TRIANGLE FOR REVIEW.
 3) PAGE SUBMITTED P-3.1 PIPE SIZE FOR
 BLDG DRAIN NOT APPROVED. ONLY 180 FU
 ALLOWED ON 4" PIPE AT 1/8" PER FOOT.
 4) PLEASE RESUBMIT REVISION WITH MATCH-
 ING PAGE NUMBERS AND SHOW WHAT IS BEING
 REVISED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-11-16 Cont ID  
Sent By kstevens Date 2001-11-16 Time 11:41 Rev Time 0.50
Received By kstevens Date 2001-11-16 Time 11:40 Sent To  
Notes
2001-11-16 00:00:00DENIED
  
 1) PLEASE DATE REVISIONS SO THEY CAN BE
 SEPARATED FROM PAST AND/OR FUTURE REVIS-
 IONS.
  
 2) REVISIONS SHALL BE INDICATED WITH
 DARTS, TRIANGLES, OR CLOUDS TO INDICATE
 WHERE REVISIONS ARE LOCATED.
  
 REVISION BY KEN STEVENS
 (561) 569-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-09-19 Cont ID  
Sent By kstevens Date 2001-09-19 Time 16:08 Rev Time 0.00
Received By kstevens Date 2001-09-19 Time 16:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-07-16 Cont ID  
Sent By jleech Date 2001-07-16 Time 10:57 Rev Time 0.00
Received By jleech Date 2001-07-16 Time 10:57 Sent To  
Notes
2001-07-16 00:00:00SEE PLAN REVIEW NOTES PERMIT # 01021175
 AND 01021194

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-03 Cont ID  
Sent By jwitmer Date 2001-10-03 Time 11:41 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-10-03 00:00:00ZON: PER MICHAEL SANCHEUZ 10/3/01