| Plan Review Stops For Permit 01021175 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
F |
Date |
2002-02-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-02-06 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-02-06 00:00:00 | GARAGE DOOR: PRESSURES LOW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2001-11-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-27 |
Time |
18:06 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
2001-11-27 |
Time |
18:06 |
Sent To |
|
|
| Notes |
| 2001-11-27 00:00:00 | SAN MARINO PROJECT | | | TYPE I BUILDING | | | MASTER# 01021175 | | | | | | 1)- THE BUILDING AS WELL AS THE MECHAN- | | | ICAL SHEETS INDICATE VENTS THROUGH MORE | | | THAN 1 FLOOR. SBC 705.1.2 INDICATES | | | A 1 HR RATED SHAFT IS REQUIRED. | | | 2)- REVISION OF SLIDING DOORS TO FRENCH | | | DOORS REQUIRES PRODUCT TESTING, EITHER | | | SBCCI OR DADE COUNTY REPORT ARE ACCEPTED | | | THE REPORT WILL REQUIRE LARGE MISSLE | | | RESISTANCE TESTING, 3 COPIES. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2001-11-19 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-11-19 |
Time |
07:46 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-11-19 00:00:00 | PER JIM WITMER: | | | STRUCTURAL REVISIONS FOR TYPES I, II, & | | | III: SUBMITTED 11/13 PD $280. BZ193677 | | | APPROVED 11/19/01 BY JW ENTERED BY LS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2001-09-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-09-27 |
Time |
11:55 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
2001-09-27 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2001-09-27 00:00:00 | MASTER MODEL TYPE I | | | BUILDINGS ; 1,3,5,8,10&12 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-09-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-09-12 |
Time |
10:07 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
2001-09-12 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2001-09-12 00:00:00 | PLAN REVIEW | | | 01021175 | | | MASTER TYPE I BUILD. | | | | | | 1)- REQUIRE 2 MORE SETS OF ENERGY CALS. | | | 2)- SOILS REPORT WITH THE MINIMUM BEAR- | | | ING VALUE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-07-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-07-24 |
Time |
18:09 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-24 00:00:00 | BUILDING TYPE I | | | PLAN CHECK : 01021175 | | | | | | 1)- ALL BUILDING COMMENTS HAVE BEEN | | | IMPLEMENTED WITH EXCEPTION TO GLAZED | | | OPENINGS NO INFORMATION ON WINDOWS, | | | DOORS, & GARAGE DOORS. SEE CITY POLICY | | | FOR LARGE MISSLE IMPACT RESISTANT | | | GLAZING & STORM SHUTTERS. | | | | | | JIM WITMER | | | (561) 659-8096 X 8412. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-06-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-06-12 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-09-19 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2001-06-12 00:00:00 | TYPE I BUILDING | | | BUILDINGS: 1,3,5,8,10& 12 | | | PLAN CHECK: 01021175 | | | ARCH: MOURIZ SALAZAR | | | PHONE : (305) 273-9911 | | | FAX ;(305) 273- | | | | | | BUILDING 1 TYPE I | | | | | | 1)- SEE A5.6 MASTER BATH LAV DOESN'T | | | MEET THE PARALLEL APPROACH AT LAV 30"X48 | | | | | | 2)- SEE A-6 MAIL BOX, FAIR HOUSING CHAP- | | | TER 2 2.12 #9 REFERS BACK TO FL. ACC. | | | ALLOWABLE REACH RANGES, SIDE MAX 54", | | | MINIMUM 0'-9" | | | | | | 3)- SH. A4-5 NOTE 20 HI RIB LATH SBC | | | 25042504.2.2 SEC ASTM C 1063.7.10.23 | | | 3/8" RIB LATH ATTACHED TO HORIZONTAL | | | WOOD SUPPORTS REQUIRES NAILS/ STAPLES TO | | | PROVIDE 1 3/4" PENETRATION INTO HORIZONT | | | AL WOOD SUPORTS, 3/4" INTO VERTICAL | | | SUPPORTS, NAILED AT EVERY RIB. | | | | | | 4)- SEE SECTION "D" SHEET A4.5 THE BOTTO | | | M OF THE FOUNDATION HAS TO BE A MINIMUM | | | OF 12" BELOW GRADE, SBC 1804.1.3. | | | | | | 5)- ALL GENERAL NOTES LISTED UNDER THE | | | CLUBHOUSEPERTAIN TO COMPONENTS & CLAD- | | | DING DETAILS, ATTACHMENTS OF DOOR & WIN- | | | DOW BUCKS, PRODUCT APPROVALS FOR GLAZED | | | OPENINGS, SEE WEST PALM BEACH POLICY FOR | | | LARGE MISSLE IMPACT RESISTANCE FOR LARGE | | | PROJECTS.PRODUCT APPROVAL FOR OVERHEAD | | | DOORS, AS WELL AS FOR ROOFING MATERIALS. | | | THE CITY ACCEPTS SBCCI & DADE COUNTY PRO | | | DUCT APPROVAL. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-04-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-04-04 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-09-19 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2001-04-04 00:00:00 | TYPE I BUILDING | | | BUILDINGS: 1,3,5,8,10 & 12 | | | PROJECT: 01021175 | | | ARCH. MOURIZ SALAZAR | | | PHONE (305) 273-9911 | | | FAX(305) | | | BUILDING 1TYPE I | | | | | | 1)- SBC 1007.3.1: STAIR CALCULATION | | | REQUIRES 2R+1T= >24",< 25" | | | | | | 2)- GENERAL STRUCTURAL NOTES S-4 (11) | | | DESIGN LOADS, | | | A)- DESIGN IS TO COMPLY WITH THE | | | 1997 STANDARD BUILDING CODE. | | | B)- WIND LOAD CRITERIA, BASIC LOAD | | | VELOCITY 110 MPH ASCE 7-95. | | | | | | 3)- FAIR HOUSING ACT: CHAP 6 | | | A)- LOCATION OF GRAB BAR AT TUB 32" MIN | | | 38" MAXIMUM. | | | B)- WATER CLOSET BACKING BEHIND THE | | | WATER CLOSET. | | | SEE PAGES A-5.1,5.2, 5.3,5.6 & 5.10 | | | C)- A5.6 MASTER BATH LAV DOESN'T MEET | | | THE PARALLEL APPROACH AT LAV, 30" | | | X 48" CLEAR. | | | D)- A-6: MAIL BOX, FAIR HOUSING CHAP.2 | | | REFER TO FL ACC REACH & RANGES, | | | SIDE APPROACH (4.2.6) MAX HEIGTH54" | | | MIN HEIGTH 0'-9". | | | E)- S-1.1: (4) C-1 APTS DEPICTS 1/2 | | | VERTIAL DROP + THRESHOLD, SEE FL | | | ACC CODE 4.13.8 THRESHOLDS AT DOOR- | | | WAYS, 2/1. | | | | | | 4)- SHEET A-9 DETAIL # 28: SOFFIT DETAIL | | | DOESN,T GIVE ANORAGEOF SOFFIT TO THE | | | 5 1/2" STRUCTURAL SLAB. | | | | | | 5)- SHEET A 4.1 2ND FL UNIT C-1 DETAILS | | | 39/43 ONE HR. KNEE WALL, SEE DETAIL ON | | | A-10 DETAIL 43, MISSING 1 LAYER OF 1/2" | | | DRYWALL. | | | | | | 6)- SH. A4-5 NOTE 20, HI RIBBED LATH, | | | SBC 2504..2.2 SEC ASTM C 1063.7.10.23) | | | 3/8" RIB LATH ATTACHED TO HORIZONTAL | | | WOOD SUPPORTS REQUIRES NAILS/ STAPLES | | | TO PROVIDE 1 3/4" PENETRATION INTO | | | HORIZONTAL WOOD SUPPORTS, 3/4" INTO | | | VERTICAL SUPPORTS. | | | | | | 7)- SHEET A3.1 NOTE #12, CANVAS AWNINGS | | | ON TUBULAR STEEL FRAMES REQUIRES A SEP- | | | ERATE PERMIT, (PER BUILDING). | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 (8412) |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-11-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-08 |
Time |
07:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-07 |
Time |
22:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-09-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2001-09-27 |
Time |
13:53 |
Rev Time |
4.00 |
| Received By |
jleahy |
Date |
2001-09-27 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2001-05-24 00:00:00 | PAGE E-102 1200 AMP MAIN HAS ONLY 1125AM | | | PS OF WIRE 240-3C AND 110-14C2 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2001-07-17 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-07-17 |
Time |
08:29 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2001-07-17 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2001-09-12 00:00:00 | PASSED: | | | 1. SEE PERMIT # 01060486 | | | | | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | | EXT. 8496 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2002-02-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-12 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-12 |
Time |
15:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2001-11-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-28 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-28 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2001-11-28 00:00:00 | 1) PLEASE EXPLAIN VENTILATION SHAFTS, | | | NOT FIRE RATED SHAFTS NOTED ON PLANS. | | | THESE NOTES APPEAR TO CONFLICT WITH | | | BUILDING AND MECHANICAL CODES. PLEASE | | | EXPLAIN RATIONALE. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-09-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-25 |
Time |
08:18 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-25 |
Time |
08:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-08-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-28 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-28 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2001-08-28 00:00:00 | THE TEMPORARY FIRE PROTECTION USING | | | A DRY HYDRANT ARRANGEMENT WITH A | | | PUMP WILL NOT BE ACCEPTED BY THIS | | | OFFICE. A WATER TANK WILL BE REQUIRED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-08-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-02 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-02 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2001-08-02 00:00:00 | 1) WATER SUPPLY FOR FIRE HYDRANTS | | | DURING CONSTRUCTION NEEDS TO BE | | | RESOLVED. A WATER MAIN EXTENSION IS | | | NEEDED AND THE DEVELOPER HAS SUGGESTED | | | ALTERNATIVE SOLUTIONS FOR THIS ISSUE. | | | 2) NOTE ON PAGE A-1.2. INDICATES | | | BUILDING WILL NOT BE FIRE SPRINKLER | | | PROTECTED. THIS IS NOT CORRECT. | | | 3) STORAGE NOT PERMITTED UNDERNEATH | | | STAIRS. STORAGE AREAS TO BE RATED AT | | | LEAST THAT OF STAIRS. | | | 4) BUILDING ADDRESS REQUIRED PER CITY | | | CODE 3343-00. | | | 5) HOW IS THE DRYER EXHAUST RISER | | | CLEANED OF COMBUSTIBLE LINT. | | | 6) HOW IS THE OUTER STAIRS BEING | | | ILLUMINATED IN CASE OF POWER OUTAGE. | | | 7) FIRE ALARM RISER DIAGRAM SHOWS E.O.L. | | | ONLY CLASS A OR FULLY ADDRESSABLE WILL | | | PER PERMITTED. | | | 8) PROVIDE MORE DETAILS ON EGRESS | | | WINDOWS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2002-02-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-07 |
Time |
10:56 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2002-02-07 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2002-02-07 00:00:00 | REVISION FOR TYPE I - | | | | | | REVISED PLAN SHEETS M-103 & M-104, | | | NOTE FOR RATING ON SHAFT.NOTE | | | CORRECTED TO REFERENCE ARCH DWG | | | INDICATING 1 HR FIRE RATING. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
F |
Date |
2002-01-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-30 |
Time |
14:34 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2002-01-30 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2002-01-30 00:00:00 | *******************DENIED*************** | | | | | | | | | PLAN SHEET M-102 THROUGH M-105 NOTES: | | | #4- 1, "VENTILATION SHAFT (NOT A FIRE | | | RATED CHASE)". | | | | | | DUCTS PENETRATING MORE THAN 1 FLOOR | | | SHALL BE PROTECTED BY A SHAFT ENCLOSURE | | | AS PER 1997 SMC 610.4 & NFPA 90A | | | 3-3.4.1.1HOUR RATING IS REQUIRED FOR | | | BUILDINGS LESS THAN 4 STORIES AND 2 | | | HOUR RATING FOR BUILDINGS 4 STORIES AND | | | MORE IN HEIGHT. | | | | | | THE ABOVE ISSUE WAS DISCUSSED IN A | | | MEETING ON JANUARY 18, 2002.PLEASE | | | SEE ATTACHED LETTER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2001-11-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-19 |
Time |
16:53 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-11-19 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2001-11-19 00:00:00 | *******************DENIED*************** | | | | | | | | | REVISION FOR PLAN SHEET M-103,104 & | | | 105, INDICATE A REVISION (TRIANGLE) | | | DATED 5/7/01.THIS WAS NOT A REVISION | | | AND WAS NOT WITH THE PLANS APPROVED FOR | | | PERMIT.DUCTS PENETRATING MORE THAN 1 | | | FLOOR SHALL BE PROTECTED BY A SHAFT | | | ENCLOSURE AS PER 1997 SMC 610.4.1 HR | | | FIRE RATING UP TO 3 STORIES, 2 HR RATING | | | 4 STORIES OR MORE. | | | | | | PLEASE INDICATE ALL CHANGES BY CLOUDS | | | AND TRIANGLES ALONG WITH THE DATE OF | | | THE REVISION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2001-08-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-17 |
Time |
12:51 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2001-08-17 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2001-08-17 00:00:00 | ********************PROVISO************* | | | | | | | | | DRYER EXHAUST SHALL HAVE A BACKDRAFT | | | DAMPER AS PER 509.3 | | | | | | | | | PLEASE REMOVE / CORRECT NOTES THAT REFER | | | TO DETAILS ON PLANS THAT ARE NOT IN THE | | | PLAN SET OR HAVE BEEN ADDRESSED ON A | | | DIFFERENT PLAN (EXAMPLE:PLAN SHEET | | | M-204 NOTES, SHAFT ENCLOSURE DETAIL SEE | | | ARCHITECTURAL PLAN SHEET A-13 #25 - | | | SHAFT DETAIL IS ON PLAN SHEET M-206). | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-07-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-11 |
Time |
10:24 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2001-07-11 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2001-07-11 00:00:00 | *******************PROVISO************** | | | ALL TYPE I | | | | | | NOTHING ON PLANS HAVE CHANGED. | | | | | | PLEASE TAKE NOTE TO THE FOLLOWING ISSUES | | | | | | | | | 1.AS STATED IN REVIEW DATED 6/5/01, | | | PLAN M-106 DETAIL OF A/C CLOSET, | | | PROVIDE OVERFLOW PAN FOR UPPER | | | FLOORS ONLY....OVERFLOW PAN SHALL | | | GO ON EVERY FLOOR TO PREVENT DAMAGE | | | TO CARPET, WALLS AND INTERIOR OF | | | APARTMENT. | | | | | | 2.AS DISCUSSED IN MEETING WITH CARLOS | | | AT CITY HALL, AS PER AMENDED 1997 | | | SPC 804.3, #5. CONDENSATE DRAINS | | | SHALL VENT TO ATMOSHPERE, IT SHALL | | | NOT VENT INTO THE WALL AS SHOWN ON | | | THE DETAIL.SHOULD TERMINATION BE | | | IN THE ATTIC, IT SHALL BE A MINIMUM | | | OF 6" ABOVE THE INSULATION. | | | | | | PLEASE REMOVE /CORRECT NOTES THAT REFER | | | TO DETAILS ON PLANS THAT ARE NOT IN THE | | | PLAN SET OR HAVE BEEN SHOWN ON | | | DIFFIERENT PLAN (EXAMPLE:SHAFT | | | ENCLOSURE IS SAID TO BE ON ARCHITECTURAL | | | PLAN SHEET A-13 #25). | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-06-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-05 |
Time |
12:43 |
Rev Time |
2.30 |
| Received By |
pkrauss |
Date |
2001-06-05 |
Time |
12:28 |
Sent To |
|
|
| Notes |
| 2001-06-05 00:00:00 | ******************PROVISO*************** | | | | | | DRAWING M306 INDICATES OVERFLOW | | | PROTECTION WITH FLOAT SWITCH FOR UPPER | | | FLOORS ONLY,PLEASE ALSO PROVIDE FOR | | | GROUND FLOORS SO AS TO PROTECT CONTENTS | | | IN THESE APARTMENTS. (CARPET, WALLS, | | | ETC.). | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-04-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-06 |
Time |
10:43 |
Rev Time |
1.30 |
| Received By |
pkrauss |
Date |
2001-04-06 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2001-04-06 00:00:00 | ******************DENIED**************** | | | | | | | | | 1.DRAWING NUMBER M-104 IN THE NOTES, | | | "1 HOUR FIRE RATED SHAFT ENCLOSURE, | | | SEE ARCHITECTURAL PLAN SHEET A-13 | | | DEATIL #25".NO SUCH DRAWING IN | | | THIS SET OF PLANS. | | | | | | 2.PLEASE INDICATE WHERE RETURN AIR | | | IS LOCATED IN EACH APARTMENT. | | | | | | 3.PLEASE PROVIDE DETAIL OF DRYER VENT | | | TERMINATING IN THE SHAFT AND RISER | | | TO THE ROOF. | | | | | | 4.PLEASE PROVIDE DETAILS ON KITCHEN | | | HOOD. | | | | | | 5.IN "GENERAL HEATING, VENTILATION & | | | AIR CONDITIONING NOTES", #13 F., | | | SHOULD READ "NON-COMBUSTIBLE" | | | MATERIAL IS TO BE PROVIDED IN | | | PLENUM SIDE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2001-12-16 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-12-16 |
Time |
10:47 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-12-16 00:00:00 | COMPLETE SET OF REVISIONS,PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2001-11-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-21 |
Time |
10:27 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-11-21 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2001-11-21 00:00:00 | REVISION DENIED | | | REFERENCE: SPC-94 - FHA AMEND 98 DESIGN | | | MANUAL | | | | | | 1) REVISION PAGES DO NOT MATCH PAGE NUM- | | | BERS IN MASTER SET REVIEWED FOR PERMIT. | | | | | | 2) ALL REVISIONS SHALL BE DATED AND IN- | | | DICATED WITH EITHER A CLOUD, DART, OR | | | TRIANGLE FOR REVIEW. | | | | | | 3) PLEASE RESUBMIT REVISION WITH MATCH- | | | ING PAGE NUMBERS AND SHOW WHAT IS BEING | | | REVISED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-10-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-27 |
Time |
07:32 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-10-27 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2001-10-27 00:00:00 | REVISIONS GOOD FOR BLDGS 3, 5, 8, 10, & | | | 12 ONLY. BLDG # 1 REQD TO HAVE SEPARATE | | | REVISION. BLDG DRAIN EXITING BLDG IS | | | MOVED TO THE RIGHT APPROX. 10' AND A | | | C/O HAS BEEN ADDED TO BLDG DRAIN ON LEFT | | | SIDE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-09-07 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-09-07 |
Time |
15:19 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-07 00:00:00 | PLUMBING PLAN REVIEW APPROVED PREVIOUS | | | COMMENTS ADDRESSED.PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-08-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-18 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2001-08-18 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2001-08-18 00:00:00 | DENIED | | | | | | 1) PREVIOUS COMMENTS FOR PLUMBINGS #'S | | | 1 - 2 - 5 & 6 NOT ADDRESSED. | | | | | | 2) COMMENT # 3 DETAIL FOR CONDENSATE | | | STILL SHOWS VENT IN PLENUM ON PLUMBING | | | PAGES. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-07-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-07-14 |
Time |
10:10 |
Rev Time |
4.00 |
| Received By |
jleech |
Date |
2001-07-14 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2001-07-14 00:00:00 | DENIED; | | | | | | 1.BUILDING TYPE I, II, III, AND IV SHALL | | | COMPLY WITH 94 SPC SEC. 710.2.4, | | | CLEANOUTS; SHOW ALL CLEANOUT LOCATIONS | | | ON PLANS. | | | | | | 2.PAGE 105 PIPE SIZING FOR SANITARY | | | PIPING IS NOT TO CODE. SEE TABLE 714.1 | | | NOTE 3. | | | | | | 3.PAGE P105 AND P106 CONDENSATE PIPING | | | SHALL NOT BE VENTED IN A/H CLOSET IF | | | CLOSET IS A PLENUM. VENTS SHALL BE | | | ABOVE THE CEILING. | | | | | | 4.BACKFLOW PREVENTERS REQUIRED ON EACH | | | BUILDING DOMESTIC WATER SUPPLY. NOT | | | ADDRESSED ON TYPE II BUILDING. NOTE | | | SHOULD BE NEXT TO SYMBOL DENOTING | | | SIZE AND TYPE. | | | | | | 5.PAGE P102 VENTS THRU ROOF ARE NOT | | | PERMITED TO PENETRATE THE FIRE RATED | | | ROOF ASSEMBLY 97 SBC 704.4.2. | | | | | | | | | 6.PAGE P-105 WATER RISER DIAGRAM. AIR | | | CHAMBERS. REFUR TO 94 SPC 607.8.2 AND | | | 607.8.3 HAMMER ARRESTORS SHALL BE | | | INSTALLED PER MANUFACTORS | | | RECOMENDATIONS. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-10-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-03 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-10-03 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2001-10-03 00:00:00 | AS PER M. SANCHEUZ 10/3/01 | | | ZON PER MICHAEL SANCHEUZ MASTER01021195 |
|
|