Plan Review Details - Permit 01021175
Plan Review Stops For Permit 01021175
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2002-02-06 Cont ID  
Sent By jwitmer Date 2002-02-06 Time 09:48 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-02-06 00:00:00GARAGE DOOR: PRESSURES LOW

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2001-11-27 Cont ID  
Sent By jwitmer Date 2001-11-27 Time 18:06 Rev Time 0.75
Received By jwitmer Date 2001-11-27 Time 18:06 Sent To  
Notes
2001-11-27 00:00:00SAN MARINO PROJECT
 TYPE I BUILDING
 MASTER# 01021175
  
 1)- THE BUILDING AS WELL AS THE MECHAN-
 ICAL SHEETS INDICATE VENTS THROUGH MORE
 THAN 1 FLOOR. SBC 705.1.2 INDICATES
 A 1 HR RATED SHAFT IS REQUIRED.
 2)- REVISION OF SLIDING DOORS TO FRENCH
 DOORS REQUIRES PRODUCT TESTING, EITHER
 SBCCI OR DADE COUNTY REPORT ARE ACCEPTED
 THE REPORT WILL REQUIRE LARGE MISSLE
 RESISTANCE TESTING, 3 COPIES.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2001-11-19 Cont ID  
Sent By lsmith Date 2001-11-19 Time 07:46 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-11-19 00:00:00PER JIM WITMER:
 STRUCTURAL REVISIONS FOR TYPES I, II, &
 III: SUBMITTED 11/13 PD $280. BZ193677
 APPROVED 11/19/01 BY JW ENTERED BY LS

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-09-27 Cont ID  
Sent By jwitmer Date 2001-09-27 Time 11:55 Rev Time 3.00
Received By jwitmer Date 2001-09-27 Time 11:49 Sent To  
Notes
2001-09-27 00:00:00MASTER MODEL TYPE I
 BUILDINGS ; 1,3,5,8,10&12

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-09-12 Cont ID  
Sent By jwitmer Date 2001-09-12 Time 10:07 Rev Time 3.00
Received By jwitmer Date 2001-09-12 Time 10:07 Sent To  
Notes
2001-09-12 00:00:00PLAN REVIEW
 01021175
 MASTER TYPE I BUILD.
  
 1)- REQUIRE 2 MORE SETS OF ENERGY CALS.
 2)- SOILS REPORT WITH THE MINIMUM BEAR-
 ING VALUE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-07-24 Cont ID  
Sent By jwitmer Date 2001-07-24 Time 18:09 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-24 00:00:00BUILDING TYPE I
 PLAN CHECK : 01021175
  
 1)- ALL BUILDING COMMENTS HAVE BEEN
 IMPLEMENTED WITH EXCEPTION TO GLAZED
 OPENINGS NO INFORMATION ON WINDOWS,
 DOORS, & GARAGE DOORS. SEE CITY POLICY
 FOR LARGE MISSLE IMPACT RESISTANT
 GLAZING & STORM SHUTTERS.
  
 JIM WITMER
 (561) 659-8096 X 8412.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-06-12 Cont ID  
Sent By jwitmer Date 2001-06-12 Time 07:28 Rev Time 0.00
Received By jwitmer Date 2001-09-19 Time 15:17 Sent To  
Notes
2001-06-12 00:00:00TYPE I BUILDING
 BUILDINGS: 1,3,5,8,10& 12
 PLAN CHECK: 01021175
 ARCH: MOURIZ SALAZAR
 PHONE : (305) 273-9911
 FAX ;(305) 273-
  
 BUILDING 1 TYPE I
  
 1)- SEE A5.6 MASTER BATH LAV DOESN'T
 MEET THE PARALLEL APPROACH AT LAV 30"X48
  
 2)- SEE A-6 MAIL BOX, FAIR HOUSING CHAP-
 TER 2 2.12 #9 REFERS BACK TO FL. ACC.
 ALLOWABLE REACH RANGES, SIDE MAX 54",
 MINIMUM 0'-9"
  
 3)- SH. A4-5 NOTE 20 HI RIB LATH SBC
 25042504.2.2 SEC ASTM C 1063.7.10.23
 3/8" RIB LATH ATTACHED TO HORIZONTAL
 WOOD SUPPORTS REQUIRES NAILS/ STAPLES TO
 PROVIDE 1 3/4" PENETRATION INTO HORIZONT
 AL WOOD SUPORTS, 3/4" INTO VERTICAL
 SUPPORTS, NAILED AT EVERY RIB.
  
 4)- SEE SECTION "D" SHEET A4.5 THE BOTTO
 M OF THE FOUNDATION HAS TO BE A MINIMUM
 OF 12" BELOW GRADE, SBC 1804.1.3.
  
 5)- ALL GENERAL NOTES LISTED UNDER THE
 CLUBHOUSEPERTAIN TO COMPONENTS & CLAD-
 DING DETAILS, ATTACHMENTS OF DOOR & WIN-
 DOW BUCKS, PRODUCT APPROVALS FOR GLAZED
 OPENINGS, SEE WEST PALM BEACH POLICY FOR
 LARGE MISSLE IMPACT RESISTANCE FOR LARGE
 PROJECTS.PRODUCT APPROVAL FOR OVERHEAD
 DOORS, AS WELL AS FOR ROOFING MATERIALS.
 THE CITY ACCEPTS SBCCI & DADE COUNTY PRO
 DUCT APPROVAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-04 Cont ID  
Sent By jwitmer Date 2001-04-04 Time 12:22 Rev Time 0.00
Received By jwitmer Date 2001-09-19 Time 15:17 Sent To  
Notes
2001-04-04 00:00:00TYPE I BUILDING
 BUILDINGS: 1,3,5,8,10 & 12
 PROJECT: 01021175
 ARCH. MOURIZ SALAZAR
 PHONE (305) 273-9911
 FAX(305)
 BUILDING 1TYPE I
  
 1)- SBC 1007.3.1: STAIR CALCULATION
 REQUIRES 2R+1T= >24",< 25"
  
 2)- GENERAL STRUCTURAL NOTES S-4 (11)
 DESIGN LOADS,
 A)- DESIGN IS TO COMPLY WITH THE
 1997 STANDARD BUILDING CODE.
 B)- WIND LOAD CRITERIA, BASIC LOAD
 VELOCITY 110 MPH ASCE 7-95.
  
 3)- FAIR HOUSING ACT: CHAP 6
 A)- LOCATION OF GRAB BAR AT TUB 32" MIN
 38" MAXIMUM.
 B)- WATER CLOSET BACKING BEHIND THE
 WATER CLOSET.
 SEE PAGES A-5.1,5.2, 5.3,5.6 & 5.10
 C)- A5.6 MASTER BATH LAV DOESN'T MEET
 THE PARALLEL APPROACH AT LAV, 30"
 X 48" CLEAR.
 D)- A-6: MAIL BOX, FAIR HOUSING CHAP.2
 REFER TO FL ACC REACH & RANGES,
 SIDE APPROACH (4.2.6) MAX HEIGTH54"
 MIN HEIGTH 0'-9".
 E)- S-1.1: (4) C-1 APTS DEPICTS 1/2
 VERTIAL DROP + THRESHOLD, SEE FL
 ACC CODE 4.13.8 THRESHOLDS AT DOOR-
 WAYS, 2/1.
  
 4)- SHEET A-9 DETAIL # 28: SOFFIT DETAIL
 DOESN,T GIVE ANORAGEOF SOFFIT TO THE
 5 1/2" STRUCTURAL SLAB.
  
 5)- SHEET A 4.1 2ND FL UNIT C-1 DETAILS
 39/43 ONE HR. KNEE WALL, SEE DETAIL ON
 A-10 DETAIL 43, MISSING 1 LAYER OF 1/2"
 DRYWALL.
  
 6)- SH. A4-5 NOTE 20, HI RIBBED LATH,
 SBC 2504..2.2 SEC ASTM C 1063.7.10.23)
 3/8" RIB LATH ATTACHED TO HORIZONTAL
 WOOD SUPPORTS REQUIRES NAILS/ STAPLES
 TO PROVIDE 1 3/4" PENETRATION INTO
 HORIZONTAL WOOD SUPPORTS, 3/4" INTO
 VERTICAL SUPPORTS.
  
 7)- SHEET A3.1 NOTE #12, CANVAS AWNINGS
 ON TUBULAR STEEL FRAMES REQUIRES A SEP-
 ERATE PERMIT, (PER BUILDING).
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 (8412)

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-11-08 Cont ID  
Sent By dpalmer Date 2001-11-08 Time 07:06 Rev Time 0.00
Received By dpalmer Date 2001-11-07 Time 22:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-09-27 Cont ID  
Sent By jleahy Date 2001-09-27 Time 13:53 Rev Time 4.00
Received By jleahy Date 2001-09-27 Time 13:52 Sent To  
Notes
2001-05-24 00:00:00PAGE E-102 1200 AMP MAIN HAS ONLY 1125AM
 PS OF WIRE 240-3C AND 110-14C2

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-07-17 Cont ID  
Sent By mamini Date 2001-07-17 Time 08:29 Rev Time 1.00
Received By mamini Date 2001-07-17 Time 08:28 Sent To  
Notes
2001-09-12 00:00:00PASSED:
 1. SEE PERMIT # 01060486
  
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8496 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2002-02-12 Cont ID  
Sent By mcarsill Date 2002-02-12 Time 15:10 Rev Time 0.00
Received By mcarsill Date 2002-02-12 Time 15:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2001-11-28 Cont ID  
Sent By mcarsill Date 2001-11-28 Time 13:23 Rev Time 0.00
Received By mcarsill Date 2001-11-28 Time 13:23 Sent To  
Notes
2001-11-28 00:00:001) PLEASE EXPLAIN VENTILATION SHAFTS,
 NOT FIRE RATED SHAFTS NOTED ON PLANS.
 THESE NOTES APPEAR TO CONFLICT WITH
 BUILDING AND MECHANICAL CODES. PLEASE
 EXPLAIN RATIONALE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-09-25 Cont ID  
Sent By mcarsill Date 2001-09-25 Time 08:18 Rev Time 0.00
Received By mcarsill Date 2001-09-25 Time 08:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-08-28 Cont ID  
Sent By mcarsill Date 2001-08-28 Time 13:58 Rev Time 0.00
Received By mcarsill Date 2001-08-28 Time 13:58 Sent To  
Notes
2001-08-28 00:00:00THE TEMPORARY FIRE PROTECTION USING
 A DRY HYDRANT ARRANGEMENT WITH A
 PUMP WILL NOT BE ACCEPTED BY THIS
 OFFICE. A WATER TANK WILL BE REQUIRED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By mcarsill Date 2001-08-02 Time 12:55 Rev Time 0.00
Received By mcarsill Date 2001-08-02 Time 12:54 Sent To  
Notes
2001-08-02 00:00:001) WATER SUPPLY FOR FIRE HYDRANTS
 DURING CONSTRUCTION NEEDS TO BE
 RESOLVED. A WATER MAIN EXTENSION IS
 NEEDED AND THE DEVELOPER HAS SUGGESTED
 ALTERNATIVE SOLUTIONS FOR THIS ISSUE.
 2) NOTE ON PAGE A-1.2. INDICATES
 BUILDING WILL NOT BE FIRE SPRINKLER
 PROTECTED. THIS IS NOT CORRECT.
 3) STORAGE NOT PERMITTED UNDERNEATH
 STAIRS. STORAGE AREAS TO BE RATED AT
 LEAST THAT OF STAIRS.
 4) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 5) HOW IS THE DRYER EXHAUST RISER
 CLEANED OF COMBUSTIBLE LINT.
 6) HOW IS THE OUTER STAIRS BEING
 ILLUMINATED IN CASE OF POWER OUTAGE.
 7) FIRE ALARM RISER DIAGRAM SHOWS E.O.L.
 ONLY CLASS A OR FULLY ADDRESSABLE WILL
 PER PERMITTED.
 8) PROVIDE MORE DETAILS ON EGRESS
 WINDOWS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2002-02-07 Cont ID  
Sent By pkrauss Date 2002-02-07 Time 10:56 Rev Time 0.50
Received By pkrauss Date 2002-02-07 Time 10:56 Sent To  
Notes
2002-02-07 00:00:00REVISION FOR TYPE I -
  
 REVISED PLAN SHEETS M-103 & M-104,
 NOTE FOR RATING ON SHAFT.NOTE
 CORRECTED TO REFERENCE ARCH DWG
 INDICATING 1 HR FIRE RATING.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2002-01-30 Cont ID  
Sent By pkrauss Date 2002-01-30 Time 14:34 Rev Time 0.50
Received By pkrauss Date 2002-01-30 Time 14:34 Sent To  
Notes
2002-01-30 00:00:00*******************DENIED***************
  
  
 PLAN SHEET M-102 THROUGH M-105 NOTES:
 #4- 1, "VENTILATION SHAFT (NOT A FIRE
 RATED CHASE)".
  
 DUCTS PENETRATING MORE THAN 1 FLOOR
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 AS PER 1997 SMC 610.4 & NFPA 90A
 3-3.4.1.1HOUR RATING IS REQUIRED FOR
 BUILDINGS LESS THAN 4 STORIES AND 2
 HOUR RATING FOR BUILDINGS 4 STORIES AND
 MORE IN HEIGHT.
  
 THE ABOVE ISSUE WAS DISCUSSED IN A
 MEETING ON JANUARY 18, 2002.PLEASE
 SEE ATTACHED LETTER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2001-11-19 Cont ID  
Sent By pkrauss Date 2001-11-19 Time 16:53 Rev Time 0.45
Received By pkrauss Date 2001-11-19 Time 16:53 Sent To  
Notes
2001-11-19 00:00:00*******************DENIED***************
  
  
 REVISION FOR PLAN SHEET M-103,104 &
 105, INDICATE A REVISION (TRIANGLE)
 DATED 5/7/01.THIS WAS NOT A REVISION
 AND WAS NOT WITH THE PLANS APPROVED FOR
 PERMIT.DUCTS PENETRATING MORE THAN 1
 FLOOR SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE AS PER 1997 SMC 610.4.1 HR
 FIRE RATING UP TO 3 STORIES, 2 HR RATING
 4 STORIES OR MORE.
  
 PLEASE INDICATE ALL CHANGES BY CLOUDS
 AND TRIANGLES ALONG WITH THE DATE OF
 THE REVISION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-08-17 Cont ID  
Sent By pkrauss Date 2001-08-17 Time 12:51 Rev Time 2.00
Received By pkrauss Date 2001-08-17 Time 12:51 Sent To  
Notes
2001-08-17 00:00:00********************PROVISO*************
  
  
 DRYER EXHAUST SHALL HAVE A BACKDRAFT
 DAMPER AS PER 509.3
  
  
 PLEASE REMOVE / CORRECT NOTES THAT REFER
 TO DETAILS ON PLANS THAT ARE NOT IN THE
 PLAN SET OR HAVE BEEN ADDRESSED ON A
 DIFFERENT PLAN (EXAMPLE:PLAN SHEET
 M-204 NOTES, SHAFT ENCLOSURE DETAIL SEE
 ARCHITECTURAL PLAN SHEET A-13 #25 -
 SHAFT DETAIL IS ON PLAN SHEET M-206).
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-07-11 Cont ID  
Sent By pkrauss Date 2001-07-11 Time 10:24 Rev Time 1.00
Received By pkrauss Date 2001-07-11 Time 10:24 Sent To  
Notes
2001-07-11 00:00:00*******************PROVISO**************
 ALL TYPE I
  
 NOTHING ON PLANS HAVE CHANGED.
  
 PLEASE TAKE NOTE TO THE FOLLOWING ISSUES
  
  
 1.AS STATED IN REVIEW DATED 6/5/01,
 PLAN M-106 DETAIL OF A/C CLOSET,
 PROVIDE OVERFLOW PAN FOR UPPER
 FLOORS ONLY....OVERFLOW PAN SHALL
 GO ON EVERY FLOOR TO PREVENT DAMAGE
 TO CARPET, WALLS AND INTERIOR OF
 APARTMENT.
  
 2.AS DISCUSSED IN MEETING WITH CARLOS
 AT CITY HALL, AS PER AMENDED 1997
 SPC 804.3, #5. CONDENSATE DRAINS
 SHALL VENT TO ATMOSHPERE, IT SHALL
 NOT VENT INTO THE WALL AS SHOWN ON
 THE DETAIL.SHOULD TERMINATION BE
 IN THE ATTIC, IT SHALL BE A MINIMUM
 OF 6" ABOVE THE INSULATION.
  
 PLEASE REMOVE /CORRECT NOTES THAT REFER
 TO DETAILS ON PLANS THAT ARE NOT IN THE
 PLAN SET OR HAVE BEEN SHOWN ON
 DIFFIERENT PLAN (EXAMPLE:SHAFT
 ENCLOSURE IS SAID TO BE ON ARCHITECTURAL
 PLAN SHEET A-13 #25).
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-05 Cont ID  
Sent By pkrauss Date 2001-06-05 Time 12:43 Rev Time 2.30
Received By pkrauss Date 2001-06-05 Time 12:28 Sent To  
Notes
2001-06-05 00:00:00******************PROVISO***************
  
 DRAWING M306 INDICATES OVERFLOW
 PROTECTION WITH FLOAT SWITCH FOR UPPER
 FLOORS ONLY,PLEASE ALSO PROVIDE FOR
 GROUND FLOORS SO AS TO PROTECT CONTENTS
 IN THESE APARTMENTS. (CARPET, WALLS,
 ETC.).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-04-06 Cont ID  
Sent By pkrauss Date 2001-04-06 Time 10:43 Rev Time 1.30
Received By pkrauss Date 2001-04-06 Time 10:43 Sent To  
Notes
2001-04-06 00:00:00******************DENIED****************
  
  
 1.DRAWING NUMBER M-104 IN THE NOTES,
 "1 HOUR FIRE RATED SHAFT ENCLOSURE,
 SEE ARCHITECTURAL PLAN SHEET A-13
 DEATIL #25".NO SUCH DRAWING IN
 THIS SET OF PLANS.
  
 2.PLEASE INDICATE WHERE RETURN AIR
 IS LOCATED IN EACH APARTMENT.
  
 3.PLEASE PROVIDE DETAIL OF DRYER VENT
 TERMINATING IN THE SHAFT AND RISER
 TO THE ROOF.
  
 4.PLEASE PROVIDE DETAILS ON KITCHEN
 HOOD.
  
 5.IN "GENERAL HEATING, VENTILATION &
 AIR CONDITIONING NOTES", #13 F.,
 SHOULD READ "NON-COMBUSTIBLE"
 MATERIAL IS TO BE PROVIDED IN
 PLENUM SIDE.

Review Stop P PLUMBING
Rev No 6 Status P Date 2001-12-16 Cont ID  
Sent By pschmitz Date 2001-12-16 Time 10:47 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-16 00:00:00COMPLETE SET OF REVISIONS,PES

Review Stop P PLUMBING
Rev No 5 Status F Date 2001-11-21 Cont ID  
Sent By kstevens Date 2001-11-21 Time 10:27 Rev Time 0.50
Received By kstevens Date 2001-11-21 Time 10:27 Sent To  
Notes
2001-11-21 00:00:00REVISION DENIED
 REFERENCE: SPC-94 - FHA AMEND 98 DESIGN
 MANUAL
  
 1) REVISION PAGES DO NOT MATCH PAGE NUM-
 BERS IN MASTER SET REVIEWED FOR PERMIT.
  
 2) ALL REVISIONS SHALL BE DATED AND IN-
 DICATED WITH EITHER A CLOUD, DART, OR
 TRIANGLE FOR REVIEW.
  
 3) PLEASE RESUBMIT REVISION WITH MATCH-
 ING PAGE NUMBERS AND SHOW WHAT IS BEING
 REVISED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-10-27 Cont ID  
Sent By kstevens Date 2001-10-27 Time 07:32 Rev Time 0.50
Received By kstevens Date 2001-10-27 Time 07:32 Sent To  
Notes
2001-10-27 00:00:00REVISIONS GOOD FOR BLDGS 3, 5, 8, 10, &
 12 ONLY. BLDG # 1 REQD TO HAVE SEPARATE
 REVISION. BLDG DRAIN EXITING BLDG IS
 MOVED TO THE RIGHT APPROX. 10' AND A
 C/O HAS BEEN ADDED TO BLDG DRAIN ON LEFT
 SIDE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-09-07 Cont ID  
Sent By pschmitz Date 2001-09-07 Time 15:19 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-09-07 00:00:00PLUMBING PLAN REVIEW APPROVED PREVIOUS
 COMMENTS ADDRESSED.PES

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-08-18 Cont ID  
Sent By kstevens Date 2001-08-18 Time 13:57 Rev Time 0.00
Received By kstevens Date 2001-08-18 Time 13:57 Sent To  
Notes
2001-08-18 00:00:00DENIED
  
 1) PREVIOUS COMMENTS FOR PLUMBINGS #'S
 1 - 2 - 5 & 6 NOT ADDRESSED.
  
 2) COMMENT # 3 DETAIL FOR CONDENSATE
 STILL SHOWS VENT IN PLENUM ON PLUMBING
 PAGES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-07-14 Cont ID  
Sent By jleech Date 2001-07-14 Time 10:10 Rev Time 4.00
Received By jleech Date 2001-07-14 Time 10:10 Sent To  
Notes
2001-07-14 00:00:00DENIED;
  
 1.BUILDING TYPE I, II, III, AND IV SHALL
 COMPLY WITH 94 SPC SEC. 710.2.4,
 CLEANOUTS; SHOW ALL CLEANOUT LOCATIONS
 ON PLANS.
  
 2.PAGE 105 PIPE SIZING FOR SANITARY
 PIPING IS NOT TO CODE. SEE TABLE 714.1
 NOTE 3.
  
 3.PAGE P105 AND P106 CONDENSATE PIPING
 SHALL NOT BE VENTED IN A/H CLOSET IF
 CLOSET IS A PLENUM. VENTS SHALL BE
 ABOVE THE CEILING.
  
 4.BACKFLOW PREVENTERS REQUIRED ON EACH
 BUILDING DOMESTIC WATER SUPPLY. NOT
 ADDRESSED ON TYPE II BUILDING. NOTE
 SHOULD BE NEXT TO SYMBOL DENOTING
 SIZE AND TYPE.
  
 5.PAGE P102 VENTS THRU ROOF ARE NOT
 PERMITED TO PENETRATE THE FIRE RATED
 ROOF ASSEMBLY 97 SBC 704.4.2.
  
  
 6.PAGE P-105 WATER RISER DIAGRAM. AIR
 CHAMBERS. REFUR TO 94 SPC 607.8.2 AND
 607.8.3 HAMMER ARRESTORS SHALL BE
 INSTALLED PER MANUFACTORS
 RECOMENDATIONS.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-03 Cont ID  
Sent By jwitmer Date 2001-10-03 Time 10:51 Rev Time 0.00
Received By jwitmer Date 2001-10-03 Time 10:51 Sent To  
Notes
2001-10-03 00:00:00AS PER M. SANCHEUZ 10/3/01
 ZON PER MICHAEL SANCHEUZ MASTER01021195