Plan Review Details - Permit 01021042
Plan Review Stops For Permit 01021042
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-03-30 Cont ID  
Sent By mamini Date 2001-03-29 Time 08:06 Rev Time 1.00
Received By mamini Date 2001-03-29 Time 08:06 Sent To  
Notes
2001-03-29 00:00:00PASSED:
 1. RESPONSES TO PREVIOUS REVIEW COMMENTS
 DATED 2-28-01 SATISFACTORY, LETTERS/
 DOCUMENTATIONS PROVIDED.
  
  
 IF ANY QUESTIONS PLEASE CONTACT 561-
 659-8096 EXT. 8492

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-02-28 Cont ID  
Sent By mamini Date 2001-02-28 Time 15:37 Rev Time 1.00
Received By mamini Date 2001-02-28 Time 15:16 Sent To  
Notes
2001-02-28 00:00:00FAILED:
 1. ANY WORK PERFORMED IN CITY R.O.W AN
 "APPLICATION FOR CONSTRUCTION WITHIN
 PUBLIC RIGHTS-OF-WAY" MUST BE SUBMITTED
 TO CITY ENGINEER RECHARD D. PETTMAN.
 ALSO SUBMIT SHOP DRAWING ON ALL
 MATERIALS TO PUBLIC UTILITIES
 ENGINEERING SERVICES DEPARTMENT.
 ATTENTION: PROJECT SPECIALIST
 MANNY GONZALEZ 1000 45TH STREET WPB,
 FL 33407
 IF ANY QUESTION CONTACT 569 8096 EXT.
 8492

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-03-27 Cont ID  
Sent By mcarsill Date 2001-03-27 Time 10:33 Rev Time 0.00
Received By mcarsill Date 2001-03-27 Time 10:33 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 2 Status P Date 2001-03-30 Cont ID  
Sent By lsmith Date 2001-03-30 Time 14:30 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-03-30 00:00:00PER MEC

Review Stop FS  
Rev No 1 Status F Date 2001-02-27 Cont ID  
Sent By mcarsill Date 2001-02-27 Time 13:38 Rev Time 0.00
Received By mcarsill Date 2001-02-27 Time 13:38 Sent To  
Notes
2001-02-27 00:00:001) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL ELECTRICAL, MECHANICAL AND SERVICE
 ROOMS. ALSO ALL VERTICAL SHAFTS ARE
 TO PROTECTED WITH SPRINKLERS.
 2) ALL FIRE STANDPIPES ARE TO BE
 EQUIPPED WITH 2 1/2 TO 1 1/2 REDUCERS.
 3) STANDPIPE SYSTEM TO PROVIDE 65 PSI
 AT THE ROOF WHILE FLOWING WATER VIA
 THE STANDPIPES.
 4) NO CUT SHEETS PROVIDED ON FIRE
 SPRINKLERS, PIPING AND VALVES PLANNED
 FOR USE. PLEASE PROVIDE THESE ITEMS
 ON NEXT SUBMISSION.
 5) PLEASE PROVIDE MORE DETAILS ON FIRE
 PUMP AND EMERGENCY GENERATOR. MORE
 DETAILS ARE NEEDED ON THE FIRE PUMP
 CONTROLLER AND APPURTENANT EQUIPMENT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910