Plan Review Details - Permit 01020942
Plan Review Stops For Permit 01020942
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-12 Cont ID  
Sent By jwitmer Date 2001-04-12 Time 15:36 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-12 00:00:00PROVISO: IMPACT FEES TO BE PAID JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-06 Cont ID  
Sent By hpiskura Date 2001-03-06 Time 15:12 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-03-06 00:00:00THIS BUILDING APPEARS TO EXCEED THE
 16000 FEET IN AREA ALLOTTED BY TABLE
 500 FOR TYPE IV CONSTRUCTION EVEN WITH
 AREA INCREASES APPLIED.PLEASE PROVIDE
 A SURVEYSO THAT COMPLIANCE MAY BE
 DETERMINED.
  
 SBC F102.2.5 REQUIRES CERTAIN BUILDINGS
 LOCATED IN THE FIRE DISTRICT TO BE
 ONE HOUR PROTECTED.PLEASE REVISE AS
 NECESSARY
  
 ALSO SHOW THE FIRE RATED MIXED OCCUPANCY
 SEPARTION REQUIRED BY SBC 704.1.
  
 THE MEZZANINE SHOWN ON SHEET A4.1 DOES
 NOT MEET THE CRITERIA FOR A MEZZANINE
 CONTAINED IN SBC 503.2.3 AND IS A STORY.
  
 TWO INDEPENDENT MEANS OF EGRESS ARE
 REQUIRED FROM THE SECOND FLOOR.SEE
 SBC 1004.2.1 AND SBC 1027.1.SEE ALSO
 "EXIT DISCHARGE" REQUIEMENTS OF SBC
 1010.1.
  
 THE EXIT STAIRS ARE REQUIED TO BE
 ENCLOSED BY SBC 1006.1 AND THE STORAGE
 AREA UNDER THE STAIRS REQUIRES ONE HOUR
 RATING IN ACCORDANCE WITH SBC 1006.1.
  
 SHOW THE TYPE AND QUANTITY OF MATERIALS
 TO BE STORED SO THAT COMPLIANCE WITH SBC
 312.2 MAY BE DETERMINED.
  
 INDICATE WHERE OR PROVIDE AS NECESARY,
 THE FIRE RATED SEPARATION REQUIRED BY
 SBC 411.5.3.
  
 THE NEW GLAZING MUST COMPLY WITH THE
 CITY'S HURRICANE MISSILE IMPACT
 RESISTANCE POLICY.
  
 IMPACT FEES MUST BE PAID TO THE COUNTY
 FOR THE CITY, ON THE PROPOSED NEW AREA.
 CALL 233-5025 FOR MORE INFORMATION.
  
 SHOW HOW THE VENTILATION FOR THE NEW
 AREA WILL BE PROVIDED.SEE SMC 403
 (MECHANICAL CODE).

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2001-04-25 Cont ID  
Sent By dpalmer Date 2001-04-25 Time 19:17 Rev Time 0.00
Received By dpalmer Date 2001-04-25 Time 19:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-04-16 Cont ID  
Sent By dpalmer Date 2001-04-16 Time 14:15 Rev Time 0.00
Received By dpalmer Date 2001-04-16 Time 14:15 Sent To  
Notes
2001-04-16 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ORIGINAL
 COMMENTS WERE NOT ADDRESSED. PLEASE
 SUBMIT ELECTRICAL DETAIL.
  
 IF THERE ARE NAY QUESTIONS, PLEASE CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-07 Cont ID  
Sent By dpalmer Date 2001-03-07 Time 21:10 Rev Time 0.00
Received By dpalmer Date 2001-03-07 Time 21:10 Sent To  
Notes
2001-03-07 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT NO ELECTRICAL
 DETAILS WERE SUBMITTED FOR COMPLETE
 REVIEW. PLEASE NOTE THAT NEW WALLS/MEZZ
 ETC WILL REQ` ELEC.
  
 PLEASE SUBMIT INFORMATION FOR REVIEW,
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-04-26 Cont ID  
Sent By mcarsill Date 2001-04-26 Time 11:27 Rev Time 0.00
Received By mcarsill Date 2001-04-26 Time 11:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-04-11 Cont ID  
Sent By mcarsill Date 2001-04-11 Time 09:07 Rev Time 0.00
Received By mcarsill Date 2001-04-11 Time 09:07 Sent To  
Notes
2001-04-11 00:00:001) PLAN REVIEW COMMENTS NOT ADEQUATELY
 ADDRESSED. PLEASE PROVIDE THE
 NECESSARY INFORMATION.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-03-09 Cont ID  
Sent By mcarsill Date 2001-03-09 Time 14:58 Rev Time 0.00
Received By mcarsill Date 2001-03-01 Time 12:47 Sent To  
Notes
2001-03-09 00:00:001) WRONG LIFE SAFETY CODE REFERENCED
 ON PLANS. SHOULD READ 1985 EDITION
 INSTEAD OF 1997 EDITION.
 2) STORAGE ROOMS OR AREAS TO BE
 SEPARATED FROM OTHER PARTS OF THE
 BUILDING BY AT LEAST ONE HOUR AND ALL
 OPENINGS SHALL BE PROTECTED BY
 SELF-CLOSING FIRE DOORS. RE: NFPA 101,
 THE LIFE SAFETY CODE, 1985 EDITION,
 SECTION 27-3.2, PROTECTION FROM HAZARDS.
 3) PLEASE EXPLAIN RATIONALE FOR A
 SINGLE MEANS OF EGRESS FROM THE SECOND
 FLOOR.
 4) NO EMERGENCY LIGHTING SHOWN FOR THE
 SECOND FLOOR.
 5) NO INTERIOR FINISH INFORMATION SHOWN
 ON THE PLANS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-04-20 Cont ID  
Sent By pkrauss Date 2001-04-20 Time 11:33 Rev Time 0.25
Received By pkrauss Date 2001-04-20 Time 11:33 Sent To  
Notes
2001-04-20 00:00:00NO MECHANICAL PLANS FOR REVIEW.
  
 PLEASE SUBMIT PLANS WITH MECHANICAL
 PERMIT APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-03-09 Cont ID  
Sent By pkrauss Date 2001-03-09 Time 12:13 Rev Time 0.30
Received By pkrauss Date 2001-03-09 Time 12:06 Sent To  
Notes
2001-03-09 00:00:00******************DENIED****************
  
 NO MECHANICAL PLANS FOR REVIEW.
 MECHANICAL NOTE ON DWG. A3.1 #5 STATES
 MECHANICAL CONTRACTOR TO RELOCATE
 EXISTING HVAC SUPPLY AND RETURN
 DIFFUSERS & DUCTWORK TO ACCOMMODATE NEW
 CONSTRUCTION.REBALANCE SYSTEM UPON
 COMPLETION OF WORK.
  
 SUBMIT MECHANICAL PLANS WITH MECHANICAL
 PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-05-02 Cont ID  
Sent By mmclean Date 2001-05-02 Time 13:10 Rev Time 0.00
Received By mmclean Date 2001-05-02 Time 13:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-05-02 Cont ID  
Sent By mmclean Date 2001-05-02 Time 13:10 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
***NONE***