Plan Review Details - Permit 01020941
Plan Review Stops For Permit 01020941
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-23 Cont ID  
Sent By jwitmer Date 2001-04-23 Time 07:12 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-14 Cont ID  
Sent By jwitmer Date 2001-03-14 Time 11:40 Rev Time 4.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-14 00:00:00PERMIT #01020941
 420 OKEECHOBEE BLVD
 SUNCOAST AUTO BUILDERS
 (727) 561-0764
  
 1)- SBC 104.2.2: ADDITIONAL INFORMATION,
 SURVEY SIGNED,SEALED AND DATED LESS THAN
 ONE YEAR OLD.F102.2.6SITE PLAN TO SHOW A
 ASSUMED PROPERTY LINE BETWEEN BUILDINGS.
 2)- SBC 1606.4.1 COUNTY AMENDMENTS:
 FOR GLAZED OPENINGS, WINDOWS & DOORS
 TESTING REPORTS FOR LARGE MISSLE IMPACT
 RESISTANCE ARE REQUIRED,EITHER SBCCI OR
 DADE COUNTY ACCEPTED,WITH THE ASSOCIATED
 TECHNICAL DRAWINGS. GLAZED OPENINGS THAT
 HAVN'T RECEIVED APPROVAL FOR LARGE MIS-
 SLE IMPACT TESTING WILL REQUIRE STORM
 SHUTTERS WITH THIS APPROVAL.
 3)- SBC 1707.4 GLAZED OPENINGS ARE RE-
 QUIRED TO HAVE TESTING FOR 1 1/2 TIMES
 THE DESIGN PRESSURE.TESTING TO BE AN
 APPROVED LABORATORY AND LISTED OR CERTI-
 FIED FOR COMPLIANCE FOR COMPLIANCE BY A
 NATIONALLY RECOGNIZED WINDOW/DOOR
 CERTIFICATION PROGRAM, SBCCI OR DADE
 COUNTY.
  
 4)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 THE CITY REQUIRES INFORMATION ON THE
 BUCK ATTACHMENT TO THE CONCRETE COLUMNS
 AND MASONARY BLOCK UNITS.
  
 5)- FIRE DISTRICT! F102.4 ROOF COVERINGS
 SHALLCONFORM TO THE REQUIREMENTS OF
 CLASS A OR B ROOF COVERINGS.
  
 6)- SBC708.5 ROOF INSULATION RATING:
 FLAME SPREAD RATING & SMOKE DEVELOPMENT.
  
 7)- SBC 1606.3.2: INSULATION FASTENING
 SCHEDULE FOR THE ROOF.
  
 8)- SBC 606 TYPE IV CONSTRUCTION: NON-
 COMBUSTIBLE MATERIALS ARE TO BE USED IN
 THE PARAPET WALL, NO 1/2 " PLYWOOD
 ALLOWED. SBC 707-(3) DOES ALLOW FIRE RE-
 TARDANT TREATED WOOD.
  
 9)- SBC 1517 ROOF OVERFLOW SCUPPERS ARE
 TO BE NO LESS THAN 2" ABOVE THE ROF AND
 NOT MORE THAN 4" ABOVE THE ROOF SEE PLAN
 ARCH.4.2.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-21 Cont ID  
Sent By dpalmer Date 2001-08-21 Time 18:49 Rev Time 0.00
Received By dpalmer Date 2001-08-21 Time 18:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-03-13 Cont ID  
Sent By dpalmer Date 2001-03-13 Time 10:44 Rev Time 0.00
Received By dpalmer Date 2001-03-13 Time 10:44 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2001-08-22 Cont ID  
Sent By mamini Date 2001-08-22 Time 08:58 Rev Time 4.00
Received By mamini Date 2001-08-22 Time 08:57 Sent To  
Notes
2001-08-22 00:00:00PASSED :
 1. REVISION AS SUBMITTED, APPROVED.
 NOTE: PLAN WAS REVIEWED AT 45TH,
 ENGINEERING DEPARTMENT, JOSE DEL RIO.
  
 MOHAMMAD R. AMINI 659-8096 EXT. 8492

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-05-24 Cont ID  
Sent By mamini Date 2001-05-24 Time 11:39 Rev Time 1.00
Received By mamini Date 2001-05-24 Time 11:39 Sent To  
Notes
2001-05-24 00:00:00PASSED :
 1. RESPONSES TO PREVIOUS REVIEW COMMENTS
 DATED 5-23-01 SATISFACTORY. CALCULATIONS
 THAT WAS REQUESTED ARE SUBMITTED TO
 JOSE DEL RIO, APPROVED.
 IF ANY QUESTIONS PLEASE CONTACT 695-8096
 EXT. 8492

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-05-23 Cont ID  
Sent By mamini Date 2001-05-23 Time 16:11 Rev Time 0.00
Received By mamini Date 2001-05-23 Time 16:11 Sent To  
Notes
2001-05-23 00:00:00FAILED:
 1. PLEASE PROVIDE STORM WATER
 CALCULATINS FOR OUR REVIEW IF YOU HAVE
 NOT SUBMITTED TO JOSE DEL RIO, STORM
 WATER ENGINEER AT 1000 45TH STREET WEST
 PALM BEACH, FL 33407. SEE ATTACHED
 2. PLEASE PROVIDE CALCULATIONS FOR
 PERVIOUS AND IMPERVIOUS AREA FOR ENTIRE
 SITE DUE TO ALL PROPOSED CHANGES.THE
 TOTAL AMOUNT MUST BE EQUAL TO 100 % OF
 TOTAL SITE ACRES OR S.F.THIS DATA WILL
 BE USED TO CALCULATE STORM WATER CHARGES
 TO PROPERTY.PROVIDE THIS DATA ON A
 8 1/2 X 11 SHEET SIGNED & SEALED BY
 DESIGN ENGINEER. PLEASE INCLUDE NAME,
 ADDRESS AND PROPERTY CONTROL NUMBER.
 3. ANY NEW CONNECTION TO CITY UTILITY
 SERVICES REQUIRES A SEPARATE PERMIT
 THROUGH PUBLIC UTILITIES ENGINEERING
 SERVICES DEPARTMENT 1000 45TH STREET
 WEST PALM BEACH, FL 33407.
 4. POLLUTION PREVENTION PLAN MUST BE
 INSTALLED IN THE FIELD PRIOR TO ANY
 EARTH WORK / DEMOLITIONS WORK.PLANS
 MUST BE KEPT ON SITE THROUGH OUT THE
 CONSTRUCTION TIME.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-08-06 Cont ID  
Sent By mcarsill Date 2001-08-06 Time 13:55 Rev Time 0.00
Received By mcarsill Date 2001-08-06 Time 13:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-03-09 Cont ID  
Sent By mcarsill Date 2001-03-09 Time 12:39 Rev Time 0.00
Received By mcarsill Date 2001-03-09 Time 12:39 Sent To  
Notes
2001-03-09 00:00:001) WRONG LIFE SAFETY CODE REFERENCED
 ON PLANS. SHOULD READ 1985 EDITION
 INSTEAD OF 1997 EDITION.
 2) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS
 TO COMPLY WITH CITY CODE REQUIREMENTS.
 3) PROVIDE EXIT MARKINGS AND EMERGENCY
 LIGHTING.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-09-05 Cont ID  
Sent By pkrauss Date 2001-09-05 Time 08:46 Rev Time 0.40
Received By pkrauss Date 2001-09-05 Time 08:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-05-21 Cont ID  
Sent By pkrauss Date 2001-05-21 Time 16:41 Rev Time 0.35
Received By pkrauss Date 2001-05-21 Time 16:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-03-23 Cont ID  
Sent By pkrauss Date 2001-03-23 Time 09:29 Rev Time 0.40
Received By pkrauss Date 2001-03-23 Time 09:25 Sent To  
Notes
2001-03-23 00:00:00******************PROVISO***************
  
 NO COMBUSTIBLES ABOVE CEILING IN RETURN
 AIR PLENUM AS PER 1997 SMC 609.1.1.

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-08-20 Cont ID  
Sent By kstevens Date 2001-08-20 Time 18:02 Rev Time 0.00
Received By kstevens Date 2001-08-20 Time 18:02 Sent To  
Notes
2001-08-20 00:00:00DENIED
 REFERENCE 1994 SPC
  
 1) PAGE P-2 ISLAND SINK DETAIL.
 SINK NOT VENTED PROPERLY. THIS IS NOT A
 COMBINATION WASTE AND VENT SYSTEM. WATER
 CLOSETS ARE NOT ALLOWED. 921.2.1. NOT AN
 APPROVED SYSTEM. 921.1. VENT DOWN STREAM
 REQUIRED IF IT WERE APPROVED. 921.4.2
  
 2) PAGE P3.2 LAV DETAIL. LAV TO MEET
 FACBC - 97 REQUIREMENT 4.19.2, APRON TO
 BE 29" FROM FINISHED FLOOR.
  
 REVIEW KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-05-05 Cont ID  
Sent By pschmitz Date 2001-05-05 Time 12:55 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-05 00:00:00PLUMBING PROVISO SEE SHS P-1,3.1,4.2
 PES.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-03-24 Cont ID  
Sent By jleech Date 2001-03-24 Time 13:32 Rev Time 1.00
Received By jleech Date 2001-03-24 Time 13:32 Sent To  
Notes
2001-03-24 00:00:00DENIED;
  
 1.PAGE CS PLUMBING CODE IS THE 1994
 STANDARD PLUMBING CODE NOT 97.
  
 2.AIR CHAMBERS TO COMPLY WITH SPC
 607.8.2 AND 607.8.3.
  
 3.WATER HEATER TO BE READLY ACCESSIBLE.
 CABINET SHALL HAVE A HINGED DOOR.
 501.7.
  
 4.DRINFING FOUNTAINS SHALL COMPLY WITH
 FACBC 4.1.3 (10) AND 4.15 FOR PEOPLE
 WHO HAVE TROUBLE BENDING AND STOOPING.
  
 5.SHOW CLEAR FLOOR SPACE FOR LAVITORY.
 BATHROOM DOOR CANNOT SWING INTO CLEAR
 FLOOR SPACE. SEC. 4.19.3
  
 6.FLOOR PLAN SHOWS VANITY IN BATHROOM.
 SHEET 5.1 SHOWS WALL HUNG LAV. LAV.
 SHALL COMPLY WITH FACBC SEC. 4.19.2.
  
 7.CIVIL DRAWINGS NOT WITH PLANS SUBMITED
 SHOW WHERE POTABLE WATER COMES FROM
 AND WHERE RAIN WATER GOES.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop Z ZONING
Rev No 3 Status P Date 2001-08-29 Cont ID  
Sent By sgraham Date 2001-08-29 Time 09:30 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-08-29 00:00:00APPROVED BY RGRANBERRY

Review Stop Z ZONING
Rev No 2 Status P Date 2001-05-24 Cont ID  
Sent By sgraham Date 2001-04-20 Time 08:17 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-04-20 00:00:00MUST MEET LANDSCAPE REQUIREMENTS

Review Stop Z ZONING
Rev No 1 Status F Date 2001-03-08 Cont ID  
Sent By sgraham Date 2001-03-08 Time 07:56 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-03-08 00:00:00NEED APPROVAL OF MINOR AMENDENT BY
 PLANNING