Plan Review Details - Permit 01020913
Plan Review Stops For Permit 01020913
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-03-27 Cont ID  
Sent By jwitmer Date 2001-03-27 Time 19:27 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-05 Cont ID  
Sent By jwitmer Date 2001-03-05 Time 15:22 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-05 00:00:00PERMIT # 01020913
 244 CORTEZ RD
 O/B SINISCALCHI, TIMOTHY
 H 540-2672
 O 625-2590
  
 THE STANDARD BUILDING CODE USES THE
 PRESCRIPTIVE REQUIREMENTS FOR BUILDINGS
 THAT AREN'T DESIGNED BY A ARCH. OR ENG.
 HURRICANE RESISTANT RESIDENTIAL CONSTRUC
 TION SSTD 10-97
  
 1)-303.3.3.2 WALL ANCHORAGE (110MPH)ARE
 TO ANCHORED 18"USING 1/2" BOLTS, WITH
 A MINIMUM EMBEDMENT OF 6". THE WASHER IS
 2'X2"X1/8".
  
 2)- STUD SPACING REQUIREMENT WILL DEPEND
 ON THE TYPE OF SPECIES OF WOOD & GRADE
 OF WOOD TO BE USED.
 110 MPH / 8 FT LENGTHFB VALUE FOR STUD
 12" O.C. / 1350
 16" O.C. / 1800
 24" O.C. / 2350THESE ARE MIN VALUES
 REQUIRED
 EXAMPLES OF WOOD & VALUES
 FIR SELECT 3850
 #12600
 #22350
 SPRUCE SELECT 3450
 #12400
 #21400
 SOUTHERN PINE
 SELECT 5250
 #13400
 #22750
  
 TABLE 305C MINIMUM WALL HEADER REQUIRE-
 MENTS MAXIMUM HEADER SPAN 6'-0" REQUIRES
 (2) FULL LENGTH STUDS AT EACH END OF A
 HEADER.
  
 305.3.1 UPLIFT LOADS ARE TO FIGURED
 AFTER THE DETERMINATION OF WOOD SPECIES,
 GRADE & SPACING IS DECIDED.
  
 3)- A FEW DETAILS ARE INCLUDED TO SHOW
 DIFFERENT ANCHORS THAT ARE AVAILABLE.
 DETAIL #1 REFLECTS THE ANCHORAGE OF THE
 BOTTOM & TOP PLATES. DETAIL #2 DEPICTS
 A WINDOW OPENING,THE ADDITIONAL FRAMING
 REQUIRED,THE HEAVIER ANCHORAGE REQUIRED
 AT OPENINGS TRANSFERRING THE LOADS BACK
 INTO THE SLAB. THERE IS ALSO ADDITIONAL
 STRAPPING REQUIREMENTS FOR THE HEADER AS
 WELL AS THE ADDITIONAL STUDDING.NOTICE
 THE DOUBLED HEADER STUDS AS WELL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-03-11 Cont ID  
Sent By dpalmer Date 2001-03-11 Time 09:40 Rev Time 0.00
Received By dpalmer Date 2001-03-11 Time 09:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-03-15 Cont ID  
Sent By ndenmark Date 2001-03-15 Time 12:58 Rev Time 0.25
Received By ndenmark Date 2001-03-15 Time 12:58 Sent To  
Notes
2001-03-15 00:00:00NO MECHANICAL SHOWN

Review Stop Z ZONING
Rev No 1 Status P Date 2001-02-26 Cont ID  
Sent By sgraham Date 2001-02-26 Time 14:14 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***