Plan Review Details - Permit 01020747
Plan Review Stops For Permit 01020747
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-06-21 Cont ID  
Sent By hpiskura Date 2001-06-21 Time 16:17 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-06-21 00:00:00REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-03-29 Cont ID  
Sent By jwitmer Date 2001-03-29 Time 18:23 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-29 00:00:00PROVISO:THE STOREFRONT GLAZYING WILL
 REQUIRE PRODUCT TESTING FOR LARGE MISSLE
 RESISTANT TESTING. GLAZYING SYSTEM OR
 STORM SHUTTERS WILL BE REQUIRED UNDER A
 SEPERATE PERMIT WITH SEPERATE FEE.
 JWITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-02-26 Cont ID  
Sent By jwitmer Date 2001-02-26 Time 16:24 Rev Time 4.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-02-26 00:00:00PERMIT # 01020747
 700 S ROSEMARY / 204
 BORRACCI BUILDERS 276-6562
  
 1)- SBC 903.1 SPRINKLER DRAWINGS &
 LAYOUT REQUIRED FOR PERMIT.
  
 2)- SBC 104.2.2- ADD. INFO. REQUIRED:
 LAYOUT OF FIXTURES, TABLES & CHAIRS TO
 SHOW THE PATH OF EGRESS. THE BACK EGRESS
 DOOR LEADS TO WHERE?
  
 3)- DOOR SCHEDULE : RATINGS ON THE DOOR
 & FRAME FOR DOOR # 107 IS NOT GIVEN.
  
 4)- FL ACC CODE 4.13.9 DOOR HARDWARE,
 LEVER OPERATED MECHANISMS, & U SHAPED
 HANDLES ARE ACCEPTABLE DESIGNS.
  
 5)- SHEET A401 WALL SEC #5 1/2" PLYWOOD
 HAS TO BE FIRE RATED.
  
 6)- SBC 1606.4.1/ 1707.4.1 STOREFRONT
 GLASS TO BE IMPACT RESISTANT GLAZING OR
 STORM SHUTTERS.
  
 JIM WITMER
 BUILDING PLAN REVIEW
 (561) 659 -8096 EX 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-06-01 Cont ID  
Sent By jleahy Date 2001-06-01 Time 09:25 Rev Time 1.30
Received By jleahy Date 2001-06-01 Time 09:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-05 Cont ID  
Sent By dpalmer Date 2001-04-05 Time 21:24 Rev Time 0.00
Received By dpalmer Date 2001-04-05 Time 21:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-01 Cont ID  
Sent By dpalmer Date 2001-03-01 Time 18:56 Rev Time 0.00
Received By dpalmer Date 2001-03-01 Time 18:56 Sent To  
Notes
2001-03-01 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE SEE THE REQ`MENTS FOR
 TAPPED CONDUCTORS IN 240-21-C,1,2,3.
 YOU ARE ALSO SHOWING TAPPING CONDUCTORS
 THAT ARE ALREADY CONSIDERED TAPPED CONDU
 CTORS? THERE MUST BE SEPARATE RUNS FOR
 EACH ONE TO EACH PANEL.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3)NOTE: PLEASE SHOW LOAD CALCUALTIONS
 NONE SHOWN. PLEASE NOTE ALL CONTINUOUS
 LOADS ARE TO FIGURED AT 125%.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-03-02 Cont ID  
Sent By lsmith Date 2001-03-02 Time 16:09 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-05-29 Cont ID  
Sent By mcarsill Date 2001-05-29 Time 13:14 Rev Time 0.00
Received By mcarsill Date 2001-05-29 Time 13:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-03-27 Cont ID  
Sent By mcarsill Date 2001-03-27 Time 13:34 Rev Time 0.00
Received By mcarsill Date 2001-03-27 Time 13:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-02-21 Cont ID  
Sent By mcarsill Date 2001-02-21 Time 13:06 Rev Time 0.00
Received By mcarsill Date 2001-02-21 Time 13:06 Sent To  
Notes
2001-02-21 00:00:001) NO FIRE SPRINKLER DRAWINGS INCLUDED
 WITH PLANS. PLEASE PROVIDE FIRE
 SPRINKLER DRAWINGS.
 2) PLEASE PROVIDE SEPARATE PLANS AND
 PERMITS FOR FIRE ALARM EQUIPMENT SHOWN
 ON DRAWINGS. PLEASE BE ADVISED THAT
 MANUAL PULL STATIONS ARE NOT REQUIRED
 AND CAN BE ELIMINATED. DUCT SMOKE
 DETECTORS WHEN ACTIVATED ARE TO CAUSE
 THE AIR HANDLING EQUIPMENT TO SHUT DOWN
 AND ACTIVATE THE FIRE ALARM SYSTEM.
 3) THE OCCUPANT LOAD FOR THE OUTSIDE
 CAFE WILL BE DETERMINED BY THIS OFFICE.
 4) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR THE
 WALLS AND CEILING OF THE STORE.
 5) THIS OFFICE HAS CONCERNS OVER THE
 SMOKE DEVELOPMENT INFORMATION PRESENTED
 IN THE TEST DATA PROVIDED BY UTC, INC.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-06-04 Cont ID  
Sent By pkrauss Date 2001-06-04 Time 11:45 Rev Time 0.35
Received By pkrauss Date 2001-06-04 Time 11:43 Sent To  
Notes
2001-06-04 00:00:00REVISION ON FAN COIL 02 AND 03.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-28 Cont ID  
Sent By pkrauss Date 2001-03-28 Time 14:19 Rev Time 0.45
Received By pkrauss Date 2001-03-28 Time 13:54 Sent To  
Notes
2001-03-28 00:00:00******************PROVISO***************
  
 DUCT SMOKE DETECTORS SHALL BE TESTED.
 (NFPA 90A 4-4.4.1)
  
 FAN SHUTDOWN WITH NOTIFICATION TO ALARM/
 STROBE. (NFPA 90A 40-4.4.3)
  
 ON PRINT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-03-09 Cont ID  
Sent By pkrauss Date 2001-03-09 Time 12:45 Rev Time 0.45
Received By pkrauss Date 2001-03-09 Time 12:26 Sent To  
Notes
2001-03-09 00:00:00*******************DENIED***************
  
 NEED AIR BALANCE SCHEDULE AND
 INFORMATION ON AIR HANDLER UNITS OR FAN
 COILS BOTH ARE MENTIONED.
  
 INDICATE WHERE OUTSIDE AIR IS SUPPLIED
 TO FN01 FH4ANF003, AN ACCESS PANEL IS
 INDICATED ON THE DRAWING M1 IS THIS
 ALSO THE RETURN..PLEASE CLARIFY.
  
 NOTE:AS PER 1997 SMC 506.1 - 10'
 MINIMUM BETWEEN EXHAUST AND FRESH AIR
 INTAKE.UNLESS THE EXHAUST IS 24" ABOVE
 FRESH AIR INTAKE - 1997 SMC 405.
  
 NO COMBUSTIBLES ABOVE CEILING IN RETURN
 AIR PLENUM - 1997 SMC 609.1.1.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-06-03 Cont ID  
Sent By pschmitz Date 2001-06-03 Time 09:11 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-03 00:00:00PLUMBING PLAN REVIEWPROVISOSHT P-3
 SHT A203, EQUIPMENT SCHEDULE,SINKS #12 &
 #39 ARE LISTED AS PREP SINKS, IF SO
 INDIRECT WASTE REQ."FLR SINK".
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS 561-659-8096X8233

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-04-13 Cont ID  
Sent By jleech Date 2001-04-13 Time 07:34 Rev Time 1.50
Received By pschmitz Date 2001-04-13 Time 07:34 Sent To  
Notes
2001-04-13 00:00:00PROVISO;
  
 NEW PLUMBING SANITARY RISER DIAGRAM
 REQUIRED. SHOW DISHWASHER AND 3 COMPART-
 MENT SINK WEASTING INTO FLOOR SINKS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-04-09 Cont ID  
Sent By jleech Date 2001-04-09 Time 18:51 Rev Time 1.75
Received By pschmitz Date 2001-04-09 Time 18:51 Sent To  
Notes
2001-04-09 00:00:00DENIED;
  
 1.PLAN REVIEW NOTE 2 FROM 2/20/01, SHT
 A-201 SHOW 5'TURNING RADIUS, NOT
 ADDRESSED ON REVISED PLANS.SEE SEC.
 FACBC 4.2.3.
  
 2.NOTE 4 FROM 2/20/01 WATER HEATER TO BE
 READLY ACCESSIBLE.SEC 501.7. INSTALL
 HEATER ON FLOOR OR SHOW A DETAIL WITH
 A FIXED SHIPS LADDER .
  
 3.DISHWASHER SHALL DISCHARGE INDIRECTLY
 INTO THE DRAINAGE SYSTEM. 94 SPC 409.
 1.2. FLOOR SINKS ARE PROPERLY TRAPPED
 AND VENTED FIXTURES.
  
 4.THREE COMPARTMENT SINKS WHEN USED FOR
 FOOD PREP. SHALL DISCHARGE INDIRECTLY
 INTO A FLOOR SINK. SEC. 804.1
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8096

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-03-04 Cont ID  
Sent By pschmitz Date 2001-03-04 Time 13:30 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-03-04 00:00:00PLUMBING PLAN REVIEWDENIED
 REFERENCESSTD PLBG CODE-94 FACBC 97
 (1) SHT A-201 CONTACT DEPT.OF BUSINESS
 REGULATION,HOTEL & RESTAURANT DIVISION.
 PRIOR TO PLBG PLAN REVIEW, FOR THEIR
 COMMENTS & REVIEW.954 958-5520.
 (2) SHT A-201 REST RM.#1,2, SHOW 5'
 TURNING RADIUS,NOT CUTTING INTO WATER
 CLOSET CLEAR FLR SPACE. SEC 4.16.2
 (3) SHT A-201 DRINKING FOUNTAIN , MAKE
 PROVISION FOR PEOPLE WHO HAVE TROUBLE
 BENDING SEC 4.1.3 (10) (A) CUP DISPENSER
 (4)SHT P-2 WATER HEATER TO BE READLY
 ACCESSIBLE,SEC501.7 SHOW A DETAIL OF A
 WORKING PLAT FORM WITH FIXED SHIPS
 LADDER IN PLACE.
 (5) SHT P-3 ALL INDIRECT WASTE TO FLOOR
 SINKS SEC 802, NO HUB DRAINS.
 (6) SHT P-3 AIR CHAMBERS, COMPLY WITH
 SEC 607.8.3 ACCESSIBLE & RE-CHARGE-ABLE.
 (7) SHT P-3 PLUMBING NOTE #5 DWV IN THIS
 BUILDING HAS BEEN SCH 40 PVC PIPE.
 END OF COMMENTS,PAUL SCHMITZ,QUESTIONS
 561-659-8096 X 8233

Review Stop Z ZONING
Rev No 1 Status N Date 2001-03-02 Cont ID  
Sent By lsmith Date 2001-03-02 Time 16:10 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***