| Plan Review Stops For Permit 01020747 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-06-21 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-06-21 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-21 00:00:00 | REVISION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-03-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-03-29 |
Time |
18:23 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-29 00:00:00 | PROVISO:THE STOREFRONT GLAZYING WILL | | | REQUIRE PRODUCT TESTING FOR LARGE MISSLE | | | RESISTANT TESTING. GLAZYING SYSTEM OR | | | STORM SHUTTERS WILL BE REQUIRED UNDER A | | | SEPERATE PERMIT WITH SEPERATE FEE. | | | JWITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-02-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-02-26 |
Time |
16:24 |
Rev Time |
4.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-02-26 00:00:00 | PERMIT # 01020747 | | | 700 S ROSEMARY / 204 | | | BORRACCI BUILDERS 276-6562 | | | | | | 1)- SBC 903.1 SPRINKLER DRAWINGS & | | | LAYOUT REQUIRED FOR PERMIT. | | | | | | 2)- SBC 104.2.2- ADD. INFO. REQUIRED: | | | LAYOUT OF FIXTURES, TABLES & CHAIRS TO | | | SHOW THE PATH OF EGRESS. THE BACK EGRESS | | | DOOR LEADS TO WHERE? | | | | | | 3)- DOOR SCHEDULE : RATINGS ON THE DOOR | | | & FRAME FOR DOOR # 107 IS NOT GIVEN. | | | | | | 4)- FL ACC CODE 4.13.9 DOOR HARDWARE, | | | LEVER OPERATED MECHANISMS, & U SHAPED | | | HANDLES ARE ACCEPTABLE DESIGNS. | | | | | | 5)- SHEET A401 WALL SEC #5 1/2" PLYWOOD | | | HAS TO BE FIRE RATED. | | | | | | 6)- SBC 1606.4.1/ 1707.4.1 STOREFRONT | | | GLASS TO BE IMPACT RESISTANT GLAZING OR | | | STORM SHUTTERS. | | | | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | (561) 659 -8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-06-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2001-06-01 |
Time |
09:25 |
Rev Time |
1.30 |
| Received By |
jleahy |
Date |
2001-06-01 |
Time |
09:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-04-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-05 |
Time |
21:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-05 |
Time |
21:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-03-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-01 |
Time |
18:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-01 |
Time |
18:56 |
Sent To |
|
|
| Notes |
| 2001-03-01 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE THE REQ`MENTS FOR | | | TAPPED CONDUCTORS IN 240-21-C,1,2,3. | | | YOU ARE ALSO SHOWING TAPPING CONDUCTORS | | | THAT ARE ALREADY CONSIDERED TAPPED CONDU | | | CTORS? THERE MUST BE SEPARATE RUNS FOR | | | EACH ONE TO EACH PANEL. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCUALTIONS | | | NONE SHOWN. PLEASE NOTE ALL CONTINUOUS | | | LOADS ARE TO FIGURED AT 125%. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-03-02 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-03-02 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-05-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-29 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-29 |
Time |
13:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-03-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-27 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-27 |
Time |
13:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-02-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-02-21 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-02-21 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2001-02-21 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | WITH PLANS. PLEASE PROVIDE FIRE | | | SPRINKLER DRAWINGS. | | | 2) PLEASE PROVIDE SEPARATE PLANS AND | | | PERMITS FOR FIRE ALARM EQUIPMENT SHOWN | | | ON DRAWINGS. PLEASE BE ADVISED THAT | | | MANUAL PULL STATIONS ARE NOT REQUIRED | | | AND CAN BE ELIMINATED. DUCT SMOKE | | | DETECTORS WHEN ACTIVATED ARE TO CAUSE | | | THE AIR HANDLING EQUIPMENT TO SHUT DOWN | | | AND ACTIVATE THE FIRE ALARM SYSTEM. | | | 3) THE OCCUPANT LOAD FOR THE OUTSIDE | | | CAFE WILL BE DETERMINED BY THIS OFFICE. | | | 4) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR THE | | | WALLS AND CEILING OF THE STORE. | | | 5) THIS OFFICE HAS CONCERNS OVER THE | | | SMOKE DEVELOPMENT INFORMATION PRESENTED | | | IN THE TEST DATA PROVIDED BY UTC, INC. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-06-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-04 |
Time |
11:45 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-06-04 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2001-06-04 00:00:00 | REVISION ON FAN COIL 02 AND 03. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-03-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-28 |
Time |
14:19 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-03-28 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2001-03-28 00:00:00 | ******************PROVISO*************** | | | | | | DUCT SMOKE DETECTORS SHALL BE TESTED. | | | (NFPA 90A 4-4.4.1) | | | | | | FAN SHUTDOWN WITH NOTIFICATION TO ALARM/ | | | STROBE. (NFPA 90A 40-4.4.3) | | | | | | ON PRINT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-03-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-09 |
Time |
12:45 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-03-09 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2001-03-09 00:00:00 | *******************DENIED*************** | | | | | | NEED AIR BALANCE SCHEDULE AND | | | INFORMATION ON AIR HANDLER UNITS OR FAN | | | COILS BOTH ARE MENTIONED. | | | | | | INDICATE WHERE OUTSIDE AIR IS SUPPLIED | | | TO FN01 FH4ANF003, AN ACCESS PANEL IS | | | INDICATED ON THE DRAWING M1 IS THIS | | | ALSO THE RETURN..PLEASE CLARIFY. | | | | | | NOTE:AS PER 1997 SMC 506.1 - 10' | | | MINIMUM BETWEEN EXHAUST AND FRESH AIR | | | INTAKE.UNLESS THE EXHAUST IS 24" ABOVE | | | FRESH AIR INTAKE - 1997 SMC 405. | | | | | | NO COMBUSTIBLES ABOVE CEILING IN RETURN | | | AIR PLENUM - 1997 SMC 609.1.1. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-06-03 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-06-03 |
Time |
09:11 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-03 00:00:00 | PLUMBING PLAN REVIEWPROVISOSHT P-3 | | | SHT A203, EQUIPMENT SCHEDULE,SINKS #12 & | | | #39 ARE LISTED AS PREP SINKS, IF SO | | | INDIRECT WASTE REQ."FLR SINK". | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS 561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-04-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-04-13 |
Time |
07:34 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
2001-04-13 |
Time |
07:34 |
Sent To |
|
|
| Notes |
| 2001-04-13 00:00:00 | PROVISO; | | | | | | NEW PLUMBING SANITARY RISER DIAGRAM | | | REQUIRED. SHOW DISHWASHER AND 3 COMPART- | | | MENT SINK WEASTING INTO FLOOR SINKS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-04-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-04-09 |
Time |
18:51 |
Rev Time |
1.75 |
| Received By |
pschmitz |
Date |
2001-04-09 |
Time |
18:51 |
Sent To |
|
|
| Notes |
| 2001-04-09 00:00:00 | DENIED; | | | | | | 1.PLAN REVIEW NOTE 2 FROM 2/20/01, SHT | | | A-201 SHOW 5'TURNING RADIUS, NOT | | | ADDRESSED ON REVISED PLANS.SEE SEC. | | | FACBC 4.2.3. | | | | | | 2.NOTE 4 FROM 2/20/01 WATER HEATER TO BE | | | READLY ACCESSIBLE.SEC 501.7. INSTALL | | | HEATER ON FLOOR OR SHOW A DETAIL WITH | | | A FIXED SHIPS LADDER . | | | | | | 3.DISHWASHER SHALL DISCHARGE INDIRECTLY | | | INTO THE DRAINAGE SYSTEM. 94 SPC 409. | | | 1.2. FLOOR SINKS ARE PROPERLY TRAPPED | | | AND VENTED FIXTURES. | | | | | | 4.THREE COMPARTMENT SINKS WHEN USED FOR | | | FOOD PREP. SHALL DISCHARGE INDIRECTLY | | | INTO A FLOOR SINK. SEC. 804.1 | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8096 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-03-04 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-03-04 |
Time |
13:30 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-04 00:00:00 | PLUMBING PLAN REVIEWDENIED | | | REFERENCESSTD PLBG CODE-94 FACBC 97 | | | (1) SHT A-201 CONTACT DEPT.OF BUSINESS | | | REGULATION,HOTEL & RESTAURANT DIVISION. | | | PRIOR TO PLBG PLAN REVIEW, FOR THEIR | | | COMMENTS & REVIEW.954 958-5520. | | | (2) SHT A-201 REST RM.#1,2, SHOW 5' | | | TURNING RADIUS,NOT CUTTING INTO WATER | | | CLOSET CLEAR FLR SPACE. SEC 4.16.2 | | | (3) SHT A-201 DRINKING FOUNTAIN , MAKE | | | PROVISION FOR PEOPLE WHO HAVE TROUBLE | | | BENDING SEC 4.1.3 (10) (A) CUP DISPENSER | | | (4)SHT P-2 WATER HEATER TO BE READLY | | | ACCESSIBLE,SEC501.7 SHOW A DETAIL OF A | | | WORKING PLAT FORM WITH FIXED SHIPS | | | LADDER IN PLACE. | | | (5) SHT P-3 ALL INDIRECT WASTE TO FLOOR | | | SINKS SEC 802, NO HUB DRAINS. | | | (6) SHT P-3 AIR CHAMBERS, COMPLY WITH | | | SEC 607.8.3 ACCESSIBLE & RE-CHARGE-ABLE. | | | (7) SHT P-3 PLUMBING NOTE #5 DWV IN THIS | | | BUILDING HAS BEEN SCH 40 PVC PIPE. | | | END OF COMMENTS,PAUL SCHMITZ,QUESTIONS | | | 561-659-8096 X 8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-03-02 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-03-02 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|