| Plan Review Stops For Permit 01020724 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-03-22 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-03-22 |
Time |
11:51 |
Rev Time |
0.25 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-03-20 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-03-20 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-20 00:00:00 | BUILDING COMMENTS | | | ----------------- | | | | | | SUBMIT COPY OF SURVEY, CONFIRMING | | | PROPERTY LINE SEPERATION AT NEW EXHAUST | | | THRU EXTERIOR WALL. | | | | | | | | | L. MARTINEZ | | | 659-8096 | | | #8456 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2001-03-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-20 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-20 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2001-03-20 00:00:00 | ************** NOTE *********** | | | | | | | | | 1)NOTE: PLANS STILL NEED TO OUTLINE | | | THE LOCATION OF ART 516. | | | | | | 2)NOTE: PLEASE SUBMIT THE LOAD CALCULATI | | | ON REQUESTED ON FIRST REVIEW. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION ON | | | NEW PLANS AND PERMIT APPLICATION. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REIVEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-03-15 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2001-03-15 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2001-03-15 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2001-03-15 00:00:00 | PLANS CALL FOR 20 AMP FAN AND AN | | | ADDITIONAL SET CALL FOR A 40 AMP FAN? | | | WHICH ONE ARE YOU GOING TO USE? | | | SUBMIT LOAD CALCULATION FOR THE SPACE | | | SHOWING THAT THE SERVICE IS OF | | | SUFFICIENT SIZE!!! | | | PLEASE OUTLINE ON THE PLANS THE CLASS | | | LOCATION AND WHAT CLASS IS BEING USED! |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-03-14 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-03-14 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
ndenmark |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-14 00:00:00 | NO ENGINEERING REQUIRED |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-03-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-14 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-14 |
Time |
13:21 |
Sent To |
|
|
| Notes |
| 2001-03-14 00:00:00 | 1) FIRE SUPPRESSION SYSTEM WILL REQUIRE | | | SEPARATE PLAN AND PERMIT PRIOR TO | | | INSTALLATION. | | | 2) A MINIMUM OF THREE FEET SHALL BE | | | PROVIDED AROUND THE SPRAY BOOTH. NO | | | COMBUSTIBLE STORAGE ALLOWED IN THIS | | | AREA. | | | 3) SINCE NO PAPERWORK WAS PROVIDED WITH | | | PLANS, A LABEL IS TO BE VISIBLE DURING | | | INSPECTION OF IT. | | | 4) LIGHT FIXTURES TO COMPLY WITH NFPA 33 | | | REQUIREMENTS. | | | 5) INTAKE FILTERS TO COMPLY WITH UL 900. | | | 6) SPRAY BOOTH TO BE BONDED AND | | | GROUNDED | | | 7) SEPARATE PERMIT REQUIRED FOR THE | | | ELECTRICAL EQUIPMENT INSTALLATION. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-02-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-02-20 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-02-20 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2001-02-20 00:00:00 | 1) WHAT IS THE SPRAY BOOTH GOING TO BE | | | USED FOR. | | | 2) WHAT FIRE PROTECTION IS PLANNED FOR | | | THE BOOTH. | | | 3) WHERE CAN MORE DETAILS BE LOCATED FOR | | | THE PREFABRICATED BOOTH. | | | 4) HOW IS THE SPRAY BOOTH GOING TO BE | | | GROUNDED. | | | 5) WHERE CAN THE CFM AMOUNT FOR THE FAN | | | BE LOCATED. | | | 6) THE METAL DUCT MUST EXTEND A MINIMUM | | | OF SIX FEET FROM THE ROOF. | | | 7) HOW IS THE DUCT BEING SUPPORTED | | | 8) HOW DOES MAKE-UP AIR ENTER THE SPRAY | | | BOOTH. | | | | | | PLEASE SHOW COMPLETE COMPLIANCE WITH | | | NFPA 33 FOR THE BOOTH AND EXHAUST DUCT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-03-14 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-03-14 |
Time |
15:25 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2001-03-14 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2001-03-14 00:00:00 | SEE FIRE REVIEW PROVISO NOTES | | | SUPPRESSION SYSTEM INCLUDING ELECTRICAL | | | INTERLOCKS TO BE TESTED PRIOR TO FINAL | | | BEING ISSUED ON BOOTH. | | | SEPARATE PERMITS REQUIRED FOR | | | MECHANICAL, ELECTRICAL AND FOR THE | | | SUPPRESSION SYSTEM. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-03-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-07 |
Time |
16:38 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-03-07 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2001-03-07 00:00:00 | ******************DENIED**************** | | | | | | PROVIDE INFORMATION ON WHAT TYPE OF | | | SPRAY BOOTH AND LOCATION INSIDE THE | | | BUILDING | | | | | | SHOW COMPLIANCE WITH CHAPTER 5 OF NFPA | | | 33, PERFORMACE REQUIREMENTS, MAKE UP | | | AIR (WHERE IS IT COMING FROM AND HOW | | | MANY CFM IS THE EXHAUST FAN - NFPA | | | 33-12, 5-3) WHERE IS THE EXHAUST IS | | | RELATION TO MAKE UP AIR. | | | | | | PROVIDE INFORMATION ON DISTRIBUTION | | | SYSTEM USED IN PAINT SPRAY BOOTH, | | | HOSES, PIPING SYSTEM, SHUT OFF VALVES | | | ETC.INDICATE WHERE A PUMP IS USED TO | | | SUPPLY LIQUID FOR THE SPRAY APPLICAITON | | | PROCESS. (NFPA 33-14, 6-4.1 THRU 6-4.6) | | | | | | SHOW LOCATION OF ELECTRIC DEVICES IN | | | SPRAY AREA, ALSO LIGHTING DETAIL ARE | | | THE LIGHTS FOR INSIDE SPRAY BOOTH OR | | | OUTSIDE. | | | | | | INDICATE WHERE THE BOOTH GROUNDED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2001-03-14 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-03-14 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
ndenmark |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-14 00:00:00 | NO PLUMBING REQUIRED FOR PAINT SPRAY | | | BOOTH |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-03-22 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-03-22 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|