Plan Review Details - Permit 01020724
Plan Review Stops For Permit 01020724
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-03-22 Cont ID  
Sent By lsmith Date 2001-03-22 Time 11:51 Rev Time 0.25
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-20 Cont ID  
Sent By lmartine Date 2001-03-20 Time 09:17 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-03-20 00:00:00BUILDING COMMENTS
 -----------------
  
 SUBMIT COPY OF SURVEY, CONFIRMING
 PROPERTY LINE SEPERATION AT NEW EXHAUST
 THRU EXTERIOR WALL.
  
  
 L. MARTINEZ
 659-8096
 #8456

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2001-03-20 Cont ID  
Sent By dpalmer Date 2001-03-20 Time 08:49 Rev Time 0.00
Received By dpalmer Date 2001-03-20 Time 08:49 Sent To  
Notes
2001-03-20 00:00:00************** NOTE ***********
  
  
 1)NOTE: PLANS STILL NEED TO OUTLINE
 THE LOCATION OF ART 516.
  
 2)NOTE: PLEASE SUBMIT THE LOAD CALCULATI
 ON REQUESTED ON FIRST REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION ON
 NEW PLANS AND PERMIT APPLICATION.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REIVEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-15 Cont ID  
Sent By jleahy Date 2001-03-15 Time 09:16 Rev Time 0.00
Received By jleahy Date 2001-03-15 Time 09:16 Sent To  
Notes
2001-03-15 00:00:00PLANS CALL FOR 20 AMP FAN AND AN
 ADDITIONAL SET CALL FOR A 40 AMP FAN?
 WHICH ONE ARE YOU GOING TO USE?
 SUBMIT LOAD CALCULATION FOR THE SPACE
 SHOWING THAT THE SERVICE IS OF
 SUFFICIENT SIZE!!!
 PLEASE OUTLINE ON THE PLANS THE CLASS
 LOCATION AND WHAT CLASS IS BEING USED!

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-03-14 Cont ID  
Sent By ndenmark Date 2001-03-14 Time 15:27 Rev Time 0.00
Received By ndenmark Date   Time   Sent To  
Notes
2001-03-14 00:00:00NO ENGINEERING REQUIRED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-03-14 Cont ID  
Sent By mcarsill Date 2001-03-14 Time 13:21 Rev Time 0.00
Received By mcarsill Date 2001-03-14 Time 13:21 Sent To  
Notes
2001-03-14 00:00:001) FIRE SUPPRESSION SYSTEM WILL REQUIRE
 SEPARATE PLAN AND PERMIT PRIOR TO
 INSTALLATION.
 2) A MINIMUM OF THREE FEET SHALL BE
 PROVIDED AROUND THE SPRAY BOOTH. NO
 COMBUSTIBLE STORAGE ALLOWED IN THIS
 AREA.
 3) SINCE NO PAPERWORK WAS PROVIDED WITH
 PLANS, A LABEL IS TO BE VISIBLE DURING
 INSPECTION OF IT.
 4) LIGHT FIXTURES TO COMPLY WITH NFPA 33
 REQUIREMENTS.
 5) INTAKE FILTERS TO COMPLY WITH UL 900.
 6) SPRAY BOOTH TO BE BONDED AND
 GROUNDED
 7) SEPARATE PERMIT REQUIRED FOR THE
 ELECTRICAL EQUIPMENT INSTALLATION.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-02-20 Cont ID  
Sent By mcarsill Date 2001-02-20 Time 11:30 Rev Time 0.00
Received By mcarsill Date 2001-02-20 Time 11:30 Sent To  
Notes
2001-02-20 00:00:001) WHAT IS THE SPRAY BOOTH GOING TO BE
 USED FOR.
 2) WHAT FIRE PROTECTION IS PLANNED FOR
 THE BOOTH.
 3) WHERE CAN MORE DETAILS BE LOCATED FOR
 THE PREFABRICATED BOOTH.
 4) HOW IS THE SPRAY BOOTH GOING TO BE
 GROUNDED.
 5) WHERE CAN THE CFM AMOUNT FOR THE FAN
 BE LOCATED.
 6) THE METAL DUCT MUST EXTEND A MINIMUM
 OF SIX FEET FROM THE ROOF.
 7) HOW IS THE DUCT BEING SUPPORTED
 8) HOW DOES MAKE-UP AIR ENTER THE SPRAY
 BOOTH.
  
 PLEASE SHOW COMPLETE COMPLIANCE WITH
 NFPA 33 FOR THE BOOTH AND EXHAUST DUCT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-14 Cont ID  
Sent By ndenmark Date 2001-03-14 Time 15:25 Rev Time 0.50
Received By ndenmark Date 2001-03-14 Time 15:25 Sent To  
Notes
2001-03-14 00:00:00SEE FIRE REVIEW PROVISO NOTES
 SUPPRESSION SYSTEM INCLUDING ELECTRICAL
 INTERLOCKS TO BE TESTED PRIOR TO FINAL
 BEING ISSUED ON BOOTH.
 SEPARATE PERMITS REQUIRED FOR
 MECHANICAL, ELECTRICAL AND FOR THE
 SUPPRESSION SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-03-07 Cont ID  
Sent By pkrauss Date 2001-03-07 Time 16:38 Rev Time 0.40
Received By pkrauss Date 2001-03-07 Time 16:38 Sent To  
Notes
2001-03-07 00:00:00******************DENIED****************
  
 PROVIDE INFORMATION ON WHAT TYPE OF
 SPRAY BOOTH AND LOCATION INSIDE THE
 BUILDING
  
 SHOW COMPLIANCE WITH CHAPTER 5 OF NFPA
 33, PERFORMACE REQUIREMENTS, MAKE UP
 AIR (WHERE IS IT COMING FROM AND HOW
 MANY CFM IS THE EXHAUST FAN - NFPA
 33-12, 5-3) WHERE IS THE EXHAUST IS
 RELATION TO MAKE UP AIR.
  
 PROVIDE INFORMATION ON DISTRIBUTION
 SYSTEM USED IN PAINT SPRAY BOOTH,
 HOSES, PIPING SYSTEM, SHUT OFF VALVES
 ETC.INDICATE WHERE A PUMP IS USED TO
 SUPPLY LIQUID FOR THE SPRAY APPLICAITON
 PROCESS. (NFPA 33-14, 6-4.1 THRU 6-4.6)
  
 SHOW LOCATION OF ELECTRIC DEVICES IN
 SPRAY AREA, ALSO LIGHTING DETAIL ARE
 THE LIGHTS FOR INSIDE SPRAY BOOTH OR
 OUTSIDE.
  
 INDICATE WHERE THE BOOTH GROUNDED.

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-03-14 Cont ID  
Sent By ndenmark Date 2001-03-14 Time 15:27 Rev Time 0.00
Received By ndenmark Date   Time   Sent To  
Notes
2001-03-14 00:00:00NO PLUMBING REQUIRED FOR PAINT SPRAY
 BOOTH

Review Stop Z ZONING
Rev No 1 Status N Date 2001-03-22 Cont ID  
Sent By lsmith Date 2001-03-22 Time 11:52 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***