Plan Review Details - Permit 01020706
Plan Review Stops For Permit 01020706
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-19 Cont ID  
Sent By hpiskura Date 2001-04-19 Time 11:21 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-02-27 Cont ID  
Sent By hpiskura Date 2001-02-27 Time 07:28 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-02-27 00:00:001)SHEET S3 SECTIONS 1/S3 AND AND 3/S3
 HAVE CONFLICTING INFORMATION AS TO THE
 PRECAST SIZES.PLEASE CLARIFY.SEE
 SBC 104.2.
  
 2) HOW WILL THE ANCHOR BOLTS SHOWN ON S3
 TYPICAL COLUMN FOOTING BE PLACED IN
 THEEXISTING SLAB?
  
 3)CLEARLY NOTE THE CONCURRENT
 EXTENSION OF THE FIRE SPRINKLER SYSTEM.
 SEE SBC 903.2.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-23 Cont ID  
Sent By dpalmer Date 2001-04-23 Time 18:43 Rev Time 0.00
Received By dpalmer Date 2001-04-23 Time 18:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-01 Cont ID  
Sent By dpalmer Date 2001-03-01 Time 18:13 Rev Time 0.00
Received By dpalmer Date 2001-03-01 Time 18:13 Sent To  
Notes
2001-03-01 00:00:00*************** UNSAT ****************
  
 1NOTE: PLEASE SUBMIT PLANS SHOWING ALL
 BRANCH CIRCUIT #`S. ALL CIRCUIT ARE TO C
 ORRELATE WITH SUBMITTED PANEL SCHEDULES.
  
 2)NOTE: PLEASE SUBMIT AND SHOW LOAD
 CALCULATIONS PER 220. PLEASE NOTE THAT
 ALL CONTINUOUS LOADS ARE TO BE SHOWN AT
 125%.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-04-27 Cont ID  
Sent By pkrauss Date 2001-04-27 Time 10:56 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-04-16 Cont ID  
Sent By mcarsill Date 2001-04-16 Time 12:49 Rev Time 0.00
Received By mcarsill Date 2001-04-16 Time 12:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-02-23 Cont ID  
Sent By mcarsill Date 2001-02-23 Time 15:50 Rev Time 0.00
Received By mcarsill Date 2001-02-23 Time 15:49 Sent To  
Notes
2001-02-23 00:00:001) PARTIAL SITE PLAN DOES NOT IDENTIFY
 EXISTING FIRE HYDRANT LOCATIONS.
 2) PLEASE PROVIDE SEATING DIAGRAM.
 3) PLEASE INDICATE IF FIRE SPRINKLERS
 ARE PLANNED FOR THE LUNCHROOM.
 4) EXITS FROM THE LUNCHROOM ARE NOT
 PROPERLY SEPARATED FROM ONE ANOTHER.
 5) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 6) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION FOR THE WALLS AND CEILINGS.
 7) ANY CHANGES IN ELEVATIONS LESS THAN
 21 INCHES SHALL BE BY RAMPS.
  
 CAPATIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-04-26 Cont ID  
Sent By pkrauss Date 2001-04-26 Time 15:40 Rev Time 0.35
Received By pkrauss Date 2001-04-26 Time 15:35 Sent To  
Notes
2001-04-26 00:00:00MECHANICAL PERMIT REQUIRED PRIOR TO ANY
 MECHANICAL WORK BEING DONE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-03-02 Cont ID  
Sent By pkrauss Date 2001-03-02 Time 12:31 Rev Time 0.45
Received By pkrauss Date 2001-03-02 Time 12:17 Sent To  
Notes
2001-03-02 00:00:00******************DENIED****************
  
 PROVIDE AIR BALANCE SCHEDULE AND OUTSIDE
 AIR CALCULATIONS AS PER ASHRAE 62-89.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-04-26 Cont ID  
Sent By kstevens Date 2001-04-26 Time 18:45 Rev Time 0.15
Received By kstevens Date 2001-04-26 Time 18:44 Sent To  
Notes
2001-04-26 00:00:00PLAN REVIEW APPROVED 3-4-01 BY
 PAUL SCHMITZ BUT NOT ENTERED INTO
 COMPUTER. (KEN STEVENS)

Review Stop Z ZONING
Rev No 1 Status P Date 2001-02-22 Cont ID  
Sent By sgraham Date 2001-02-22 Time 09:02 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***