Plan Review Details - Permit 01020521
Plan Review Stops For Permit 01020521
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-04-03 Cont ID  
Sent By jwitmer Date 2001-04-03 Time 15:38 Rev Time 0.25
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-03 00:00:00BUILDING ISSUE DATE 2/14 BY MISTAKE JW

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-05-08 Cont ID  
Sent By dpalmer Date 2001-05-08 Time 10:07 Rev Time 0.00
Received By dpalmer Date 2001-05-08 Time 10:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-06 Cont ID  
Sent By dpalmer Date 2001-04-06 Time 08:10 Rev Time 0.00
Received By dpalmer Date 2001-04-06 Time 08:10 Sent To  
Notes
2001-04-06 00:00:00******************** UNSAT ************
  
 1)NOTE:PLANS NEED TO HAVE BRANCH
 CIRCUIT#`S NEED TO BE SHOWN ON PLANS
 ANDSUBMIT PANEL SCHEDULE THAT
 CORRELATESWITH #`S ON PLANS.
  
 2)NOTE: PLANS SHOW NEW ADDED LOAD. WHAT
 ABOUT EXSITING LOAD?
 ALSO PLANS SHOW ADDING CIRCUITS TO
 PANELIN ADJACENT SPACE. THIS IS NOT
 PERMITTED
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-03-30 Cont ID  
Sent By mcarsill Date 2001-03-30 Time 10:00 Rev Time 0.00
Received By mcarsill Date 2001-03-30 Time 10:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-05-09 Cont ID  
Sent By pkrauss Date 2001-05-09 Time 16:44 Rev Time 0.35
Received By pkrauss Date 2001-05-09 Time 16:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-04-03 Cont ID  
Sent By pkrauss Date 2001-04-03 Time 11:06 Rev Time 0.30
Received By pkrauss Date 2001-04-03 Time 11:06 Sent To  
Notes
2001-04-03 00:00:00*******************DENIED***************
  
  
 MECHANICAL PERMIT REQUIRED. PLANS NEED
 TO INDICATE CONDENSATE DRAIN LINE.
 ALSO AN AUXILIARY DRAIN PAN WITH
 OVERFLOW PROTECTION REQUIRED AS PER
 1997 SMC 304.8.6.
  
 NOTE 5 ON THE AIR CONDITIONING
 SPECIFICATION, INDICATES 105 CFM MAKE
 UP VENTALATION AIR,PLANS NEED TO
 REFLECT LOCATION OF MAKE UP AIR.SHOW
 O.A. CALCULATION AS PER ASHRAE 62-89.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-02-14 Cont ID  
Sent By ydavis Date 2001-02-14 Time 08:31 Rev Time 0.25
Received By ydavis Date   Time   Sent To  
Notes
2001-02-14 00:00:002/14/01 OKAY PER RYAN N. YD