| Plan Review Stops For Permit 01020495 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2001-06-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-06-08 |
Time |
07:06 |
Rev Time |
0.25 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-08 00:00:00 | TRUSS DRAWINGS OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-04-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-04-09 |
Time |
13:49 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-03-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-03-27 |
Time |
17:26 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-27 00:00:00 | BUILDING PLAN REVIEW | | | 1)- MISSING PRODUCT APPROVALS | | | A) STORAGE DOOR | | | B) ENTRY DOOR GAME ROOM | | | C) GAME ROOM WINDOWS & MULLIAN REPORT | | | | | | 2)- MISSING INFO FOR THE GIRDER FOR | | | ANCHORAGE. | | | | | | 3)- GABLE END DETAIL NO INFO: IS THERE | | | A GABLE TRUSS OR A RAKED BEAM NEED INFO. | | | | | | 4)- CONTRACTOR ELECTS TO APPLY FOR THE | | | STORM SHUTTER PERMIT LATER WITH | | | ADDITIONAL FEES. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | | | | | | | (561) 659- 8096 EX 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-03-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-03-05 |
Time |
09:00 |
Rev Time |
2.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-05 00:00:00 | PERMIT # 01020495 | | | 426 34TH STREET | | | CARTIER-MCDONALD CONT. | | | 793-4033 | | | | | | 1)- FOR PRODUCT APPROVAL REPORTS WE RE- | | | QUIRE (2) COPIES OF EACH REPORT. | | | | | | 2)- SBC 1606.2.6.2: COMPONENTS & CLADD- | | | ING, ALL OPENINGS WINDOWS & DOORS RE- | | | QUIRE TESSTING REPORTS FOR WIND.DOORS | | | WITH GLAZED OPENINGS WILL REQUIRE NOT | | | ONLY TESTING FOR WIND BUT FOR LARGE MIS- | | | SLE IMPACT TESTING, OR STORM SHUTTERS | | | THAT HAVE UNDERGONE AND ACHEVIED TESTING | | | APPROVAL, THE CITY ACCEPTS S.B.C.C.I. | | | REPORTS AS WELL AS DADE COUNTY PRODUCT | | | APPROVAL REPORTS. | | | | | | 3)- 104.2.2ADDMINISTRATIVE CODE: | | | ADDITIONAL INFORMATION REQUIRED; THERE | | | ISN'T A TRUSS LAYOUT PLAN OF THE COTTAGE | | | WHAT IS THE UPLIFT ON THE GIRDER THAT | | | WILL BE REQUIRED TO CARRY THE ROOF LOADS | | | | | | 4)- 104.2.2 ADMINISTRATIVE CODE: | | | ADDITIONAL INFORMATION REQUIRED: THE | | | PLAN DOES NOT REFLECT THE GABLE END | | | ATTACHMENT TO THE BEAM. | | | | | | 5)- 104.2.2 ADMINISTRATIVE CODE: | | | ADDITIONAL INFORMATION REQUIRED: THERE | | | IS NO DETAILS ON PORCH STOOP OVERHANG, | | | FRAMING. ATTACHMENT, & BEAM? | | | | | | 6)- 1606.4.1 / 1707.4.1 COUNTY WIDE | | | AMENDMENTS WIL REQUIRE APPROVED STORM | | | SHUTTERS OVER ALL GLAZED OPENINGS. A | | | COPY OF THE CITIES POLICY AND WHAT INFOR | | | MATION WILL BE REQUIRED FOR THE INSTALA- | | | TION SCHEDULE. | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-08-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-02 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-02 |
Time |
16:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-04-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-09 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-09 |
Time |
10:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-03-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-22 |
Time |
21:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-22 |
Time |
21:41 |
Sent To |
|
|
| Notes |
| 2001-03-22 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT PER F.A.C. | | | F.S. 471.025 / 481.221 ALL CHANGES ON | | | SIGNED AND SEALED DOCUMENTS ARE TO BE | | | SIGNED/INITIALED AND DATED BY THE ARCH/ | | | ENGINEER OF RECORD. | | | | | | 2)NOTE: PLEASE PROVIDE INFORMATION FOR | | | NEW RISER DIAGRAM SUBMITTED. NO WIRE | | | SIZES,CONDUIT SIZES FOR DISCONNECTS, | | | PANELS. | | | | | | 3)NOTE: PLEASENOTE 373-8 FOR | | | DISC/PANELS BEING USED AS RACEWAYS.FEED | | | FOR 100A DISCONNECT IS SHOWN GOING | | | THROUGH, 150A. | | | | | | 4)NOTE: PLEASE SHOW WHERE NEW SERVICE | | | ISGOING TO BE. HOUSE/OR COTTAGE. | | | CONDUIT SIZES UNDERGROUND.ETC | | | IF SERVICE FOR COTTAGE IS COMING FROM | | | MAIN HOUSE THEN LOAD CALCULATIONS OF | | | EXSITING NEEDS TO BE SUBMITTED AND | | | INCLUDE NEW COTTAGE LOAD. | | | | | | 5)NOTE: PLEASE NOTE, STILL NEED THE AIC | | | RATINGS OF ANY NEW EQUIPMENT. PER 110-9 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, OR | | | IF I CAN BE OF ANY ASSISTANCE. PLEASE | | | CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-02-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-16 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-16 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2001-02-16 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT A REVISED RISER | | | DIAGRAM. SEPARATE METER FOR GUEST | | | COTTAG IS NOT PERMITTED. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 3) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IFTHERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-07-28 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2001-07-28 |
Time |
13:20 |
Rev Time |
0.33 |
| Received By |
hmoser |
Date |
2001-07-28 |
Time |
13:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-02-21 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-02-21 |
Time |
14:42 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2001-02-21 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2001-02-21 00:00:00 | PROVISO; | | | A/C EQUIPMENT INFORMATION REQUIRED | | | BEFORE FINAL A/C INSPECTION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2001-02-21 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-02-21 |
Time |
14:45 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2001-02-21 |
Time |
14:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-02-14 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-02-14 |
Time |
16:00 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|