Plan Review Details - Permit 01020495
Plan Review Stops For Permit 01020495
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-06-08 Cont ID  
Sent By jwitmer Date 2001-06-08 Time 07:06 Rev Time 0.25
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-08 00:00:00TRUSS DRAWINGS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-04-09 Cont ID  
Sent By jwitmer Date 2001-04-09 Time 13:49 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-03-27 Cont ID  
Sent By jwitmer Date 2001-03-27 Time 17:26 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-27 00:00:00BUILDING PLAN REVIEW
 1)- MISSING PRODUCT APPROVALS
 A) STORAGE DOOR
 B) ENTRY DOOR GAME ROOM
 C) GAME ROOM WINDOWS & MULLIAN REPORT
  
 2)- MISSING INFO FOR THE GIRDER FOR
 ANCHORAGE.
  
 3)- GABLE END DETAIL NO INFO: IS THERE
 A GABLE TRUSS OR A RAKED BEAM NEED INFO.
  
 4)- CONTRACTOR ELECTS TO APPLY FOR THE
 STORM SHUTTER PERMIT LATER WITH
 ADDITIONAL FEES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
  
  
 (561) 659- 8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-05 Cont ID  
Sent By jwitmer Date 2001-03-05 Time 09:00 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-05 00:00:00PERMIT # 01020495
 426 34TH STREET
 CARTIER-MCDONALD CONT.
 793-4033
  
 1)- FOR PRODUCT APPROVAL REPORTS WE RE-
 QUIRE (2) COPIES OF EACH REPORT.
  
 2)- SBC 1606.2.6.2: COMPONENTS & CLADD-
 ING, ALL OPENINGS WINDOWS & DOORS RE-
 QUIRE TESSTING REPORTS FOR WIND.DOORS
 WITH GLAZED OPENINGS WILL REQUIRE NOT
 ONLY TESTING FOR WIND BUT FOR LARGE MIS-
 SLE IMPACT TESTING, OR STORM SHUTTERS
 THAT HAVE UNDERGONE AND ACHEVIED TESTING
 APPROVAL, THE CITY ACCEPTS S.B.C.C.I.
 REPORTS AS WELL AS DADE COUNTY PRODUCT
 APPROVAL REPORTS.
  
 3)- 104.2.2ADDMINISTRATIVE CODE:
 ADDITIONAL INFORMATION REQUIRED; THERE
 ISN'T A TRUSS LAYOUT PLAN OF THE COTTAGE
 WHAT IS THE UPLIFT ON THE GIRDER THAT
 WILL BE REQUIRED TO CARRY THE ROOF LOADS
  
 4)- 104.2.2 ADMINISTRATIVE CODE:
 ADDITIONAL INFORMATION REQUIRED: THE
 PLAN DOES NOT REFLECT THE GABLE END
 ATTACHMENT TO THE BEAM.
  
 5)- 104.2.2 ADMINISTRATIVE CODE:
 ADDITIONAL INFORMATION REQUIRED: THERE
 IS NO DETAILS ON PORCH STOOP OVERHANG,
 FRAMING. ATTACHMENT, & BEAM?
  
 6)- 1606.4.1 / 1707.4.1 COUNTY WIDE
 AMENDMENTS WIL REQUIRE APPROVED STORM
 SHUTTERS OVER ALL GLAZED OPENINGS. A
 COPY OF THE CITIES POLICY AND WHAT INFOR
 MATION WILL BE REQUIRED FOR THE INSTALA-
 TION SCHEDULE.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-08-02 Cont ID  
Sent By dpalmer Date 2001-08-02 Time 16:53 Rev Time 0.00
Received By dpalmer Date 2001-08-02 Time 16:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-04-09 Cont ID  
Sent By dpalmer Date 2001-04-09 Time 10:18 Rev Time 0.00
Received By dpalmer Date 2001-04-09 Time 10:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-03-22 Cont ID  
Sent By dpalmer Date 2001-03-22 Time 21:41 Rev Time 0.00
Received By dpalmer Date 2001-03-22 Time 21:41 Sent To  
Notes
2001-03-22 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PER F.A.C.
 F.S. 471.025 / 481.221 ALL CHANGES ON
 SIGNED AND SEALED DOCUMENTS ARE TO BE
 SIGNED/INITIALED AND DATED BY THE ARCH/
 ENGINEER OF RECORD.
  
 2)NOTE: PLEASE PROVIDE INFORMATION FOR
 NEW RISER DIAGRAM SUBMITTED. NO WIRE
 SIZES,CONDUIT SIZES FOR DISCONNECTS,
 PANELS.
  
 3)NOTE: PLEASENOTE 373-8 FOR
 DISC/PANELS BEING USED AS RACEWAYS.FEED
 FOR 100A DISCONNECT IS SHOWN GOING
 THROUGH, 150A.
  
 4)NOTE: PLEASE SHOW WHERE NEW SERVICE
 ISGOING TO BE. HOUSE/OR COTTAGE.
 CONDUIT SIZES UNDERGROUND.ETC
 IF SERVICE FOR COTTAGE IS COMING FROM
 MAIN HOUSE THEN LOAD CALCULATIONS OF
 EXSITING NEEDS TO BE SUBMITTED AND
 INCLUDE NEW COTTAGE LOAD.
  
 5)NOTE: PLEASE NOTE, STILL NEED THE AIC
 RATINGS OF ANY NEW EQUIPMENT. PER 110-9
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS, OR
 IF I CAN BE OF ANY ASSISTANCE. PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-02-16 Cont ID  
Sent By dpalmer Date 2001-02-16 Time 09:29 Rev Time 0.00
Received By dpalmer Date 2001-02-16 Time 09:29 Sent To  
Notes
2001-02-16 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT A REVISED RISER
 DIAGRAM. SEPARATE METER FOR GUEST
 COTTAG IS NOT PERMITTED.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IFTHERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-28 Cont ID  
Sent By hmoser Date 2001-07-28 Time 13:20 Rev Time 0.33
Received By hmoser Date 2001-07-28 Time 13:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-02-21 Cont ID  
Sent By jleech Date 2001-02-21 Time 14:42 Rev Time 0.25
Received By jleech Date 2001-02-21 Time 14:42 Sent To  
Notes
2001-02-21 00:00:00PROVISO;
 A/C EQUIPMENT INFORMATION REQUIRED
 BEFORE FINAL A/C INSPECTION.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-02-21 Cont ID  
Sent By jleech Date 2001-02-21 Time 14:45 Rev Time 0.25
Received By jleech Date 2001-02-21 Time 14:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-02-14 Cont ID  
Sent By sgraham Date 2001-02-14 Time 16:00 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***