Plan Review Details - Permit 01020406
Plan Review Stops For Permit 01020406
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-05-01 Cont ID  
Sent By dpalmer Date 2001-05-01 Time 12:04 Rev Time 0.00
Received By dpalmer Date 2001-05-01 Time 12:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-02-28 Cont ID  
Sent By dpalmer Date 2001-02-28 Time 21:43 Rev Time 0.00
Received By dpalmer Date 2001-02-28 Time 21:43 Sent To  
Notes
2001-02-28 00:00:00************** REVISION REQ`D*********8
  
  
 1)NOTE; PLEASE NOTE THAT THE SERVICE
 RISER DIAGRAM DOES NOT CORRELATE WITH
 THE
 PLANS. PNE SHOWS MAIN DISCONNECT AND
 THE OTHER PANEL WITH MAIN.
  
 2)NOTE: PLEASE NOTE OUTLET SPACING TO
 MEET CODE FOR KITCHEN COUNTERSPACE PER
 210-52-C-1.
  
  
 PLEASE SUBMIT REVISED PLANS FOR REVIEW B
 EFORE FINAL INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-02-28 Cont ID  
Sent By jleech Date 2001-02-28 Time 19:10 Rev Time 0.33
Received By jleech Date 2001-02-28 Time 19:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-11-27 Cont ID  
Sent By jleech Date 2001-11-27 Time 19:49 Rev Time 0.33
Received By jleech Date 2001-11-27 Time 19:49 Sent To  
Notes
2001-11-27 00:00:00REVISED PLUMBING RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-05-02 Cont ID  
Sent By kstevens Date 2001-05-02 Time 08:50 Rev Time 0.25
Received By kstevens Date 2001-05-02 Time 08:50 Sent To  
Notes
2001-05-02 00:00:00REVIEW NOTES
  
 SUBMIT REVISED SANITARY RISER DIAGRAM
 BEFORE ROUGH INSPECTIONS. RISER DIAGRAM
 SUBMITTED DOES NOT COMPLY WITH CODE.
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-02-27 Cont ID  
Sent By jleech Date 2001-02-27 Time 19:18 Rev Time 0.25
Received By kstevens Date 2001-02-27 Time 19:18 Sent To  
Notes
2001-02-27 00:00:00PROVISO:
 REVISE SANITARY RISER DIAGRAM
 REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-04-27 Cont ID  
Sent By rmcdouga Date 2001-04-27 Time 11:09 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-03-16 Cont ID  
Sent By rmcdouga Date 2001-03-16 Time 16:20 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-03-16 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE IMPORTANCE FACTOR GIVEN ON THE
 DESIGN CERTIFICATION FORM ON SHEET S1
 IS INCORRECT. TABLE 6-2 OF ASCE 7-95
 DOES NOT LIST 1.05. PLEASE CORRECT.
  
 3) PROVIDE A REVISED ROOF FRAMING PLAN.
 SEE TRUSS NOTES.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-02-13 Cont ID  
Sent By sgraham Date 2001-02-13 Time 13:14 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***