Plan Review Details - Permit 01020403
Plan Review Stops For Permit 01020403
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-25 Cont ID  
Sent By dpalmer Date 2001-04-25 Time 07:18 Rev Time 0.00
Received By dpalmer Date 2001-04-25 Time 07:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-02-28 Cont ID  
Sent By dpalmer Date 2001-02-28 Time 22:05 Rev Time 0.00
Received By dpalmer Date 2001-02-28 Time 22:05 Sent To  
Notes
2001-02-28 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 4)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 DOES NOT CORRELATE WITH PLANS. MAINS/PAN
 ELS/DISCONNECTS ETC.? PLEASE SUBMIT CLAR
 IFICATION.
  
 5)NOTE: PLEASE NOTE THAT NO MAIN DISCONN
 ECT IS SHOWN ON RISER DIAGRAM WHICH IS R
 EQ`D BY 225-31.
  
 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL PER 250-50.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-20 Cont ID  
Sent By pkrauss Date 2001-08-20 Time 16:28 Rev Time 0.30
Received By pkrauss Date 2001-08-20 Time 16:28 Sent To  
Notes
2001-08-20 00:00:00MECH PERMIT 01020412

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-03-01 Cont ID  
Sent By jleech Date 2001-03-01 Time 06:56 Rev Time 0.33
Received By jleech Date 2001-03-01 Time 06:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-11-14 Cont ID  
Sent By kstevens Date 2001-11-14 Time 17:36 Rev Time 0.50
Received By kstevens Date 2001-11-14 Time 17:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-03-01 Cont ID  
Sent By jleech Date 2001-03-01 Time 06:56 Rev Time 0.25
Received By jleech Date 2001-03-01 Time 06:56 Sent To  
Notes
2001-02-27 00:00:00PROVISO:
 REVISED SANITARY RISER DIAGRAM
 REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2001-10-26 Cont ID  
Sent By rmcdouga Date 2001-10-26 Time 10:53 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-10-26 00:00:00************BUILDING PROVISO************
  
 FENCE EXTENSION IS OK PROVIDED IT DOES
 NOT BLOCK THE PATH OF EGRESS FROM THE
 STRUCTURES ON LOTS 70 AND 71 TO COMMON
 AREA.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-05-03 Cont ID  
Sent By rmcdouga Date 2001-05-03 Time 13:42 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-05-03 00:00:00PROVISO
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ROOFING MATERIAL FOR FLAT ROOF AREAS

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-05-03 Cont ID  
Sent By rmcdouga Date 2001-03-09 Time 11:26 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-03-09 00:00:00TRUSSES UNSAT
  
 1) GE1 AND T1 ARE FOR PITCHED ROOF AND
 FLAT ROOF IS SHOWN ON PRINTS.
  
 2) TRUSS LAYOUT AND DRAWINGS INDICATE A
 VAULTED CEILING IN THE GARAGE. THIS IS
 NOT INDICATED ON PLANS.
  
 3) NO ANCHORS ARE INDICATED FOR THE (2)
 INTERIOR BEARING POINTS FOR T-14 OR THE
 (1) INTERIOR BEARING POINT FOR T-15.
  
 4) THE UPLIFT AT POINT 1 FOR T-16 IS
 1519# ON TRUSS DRAWINGS THE SCHEDULE
 VALUE OF 1450# IS EXCEEDED.
  
 5) THE UPLIFT AT T-29 EXCEEDS ANCHOR
 SCHEDULE VALUE.
  
 6) TURRENT FRAMING PLAN ON S1 INDICATES
 TA-6 THIS IS NOT LISTED ON SCHEDULE.
  
 7) TRUSS DRAWINGS GIVES UPLIFT OF 1457#
 FOR EACH END OF TG-1, TA-9 ANCHOR
 INDICATED ON PLANS ONLY PROVIDE FOR
 545#.
  
 PLEASE REVIEW AND CORRECT ANY ERRORS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-03-09 Cont ID  
Sent By rmcdouga Date 2001-03-09 Time 10:07 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-03-09 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) DESIGN CERTIFICATION CRITERIA ON
 SHEET S1 IS IN ERROR.
 MIXING OF PROVISIONS FROM ASCE 7
 AND SBC 1606.2 SHALL NOT BE PERMITTED.
 97 SBC 1606.1.2 PLEASE CORRECT.
  
 3) THE PERCENT OF OPENINGS ALLOWED BY
 97 SBC TABLE 600 IS EXCEDED ON FRONT
 ELEVATION OF STRUCTURE. FOR A HORIZONTAL
 SEPARATION OF 8', 20% OF THE WALL AREA
 (FLOOR TO CEILING)IS ALLOWED AS OPENINGS
 PLEASE REVIEW AND CORRECT.
  
 4) TRUSS LAYOUT AND PLANS DO NOT AGREE.
 AT GARAGE.PLEASE REVIEW AND CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 2 Status P Date 2001-10-25 Cont ID  
Sent By sgraham Date 2001-10-25 Time 13:13 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-02-13 Cont ID  
Sent By sgraham Date 2001-02-13 Time 13:11 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***