| Plan Review Stops For Permit 01020317 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-06-12 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-06-12 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-07 00:00:00 | OK W/ HC LAYOUT COPIED FROM MANUAL |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-03-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-03-07 |
Time |
12:11 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-07 00:00:00 | PERMIT # 01020317 | | | 446 NORTHWOOD RD | | | HATCHEY CONSTRUCTION | | | 588-8288 | | | | | | 1)- FL HANDICAPPED CODE 4.1.6.2.2(3)A: | | | SHOW RAMP AT FRONT ENTRY OF BUILDING. | | | HANDICAPPED RAMP SLOPE MAY BE BETWEEN | | | 1:10 & 1:12 IS ALLOWED FOR A MAXIMUM | | | RISE OF 6 INCHES. | | | | | | (2)- FL HANDICAPPED CODE 4.16: | | | THE FLOOR PLAN AND THE HANDICAPPED | | | TOLIET DETAILHAVE DISCREPANCIES IN | | | SIZE AND LAY OUT. | | | | | | (3)- NOTE 5&6 SHOW THE REPLACEMENT OF | | | WINDOWS WHICH WILL REQUIRE A ACCEPTANCE | | | REPORT, EITHER SBCCI OR DADE COUNTY | | | PRODUCT APPROVAL (2 COPIES). | | | | | | (4)- NOTE #14: SBC 1204.2 WALLS & FLOORS | | | OF ALL PUBLIC RESTROOMS SHALL BE LINED | | | WITH NONABSORBANT MATERIAL TO A HEIGTH | | | OF 4 FT. ABOVE THE FLOOR. | | | | | | (5)- THE STOREFRONT DOOR AND WINDOWS | | | ARE TO BE UNDER SEPERATE PERMIT AND | | | FEES. 2 COPIES OF AN PRODUCT ACCEPTANCE | | | REPORT WILL BE REQUIRED. S.B.C.C.I. | | | REPORT OR DADE COUNTY WILL BE ACCEPTABLE | | | IF THE REPORT HASN,T HAD LARGE MISSLE | | | IMPACT TESTING STORM SHUTTERS WILL BE RE | | | QUIRED THAT HAVE THE LARGE MISSLE TEST- | | | ING WITH REPORT. | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-07-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-05 |
Time |
18:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-05 |
Time |
18:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2001-06-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-07 |
Time |
19:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-07 |
Time |
19:11 |
Sent To |
|
|
| Notes |
| 2001-06-07 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT THE SAME NOTES | | | FROM FIRST AND SECOND REVIEW STILL | | | STAND. NO ELECTRICAL COMMENTS WERE | | | ADDRESSED FROM PREVIOUS REVIEWS/COMMENTS | | | | | | | | | PLEASE SUBMIT INFORMATION FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-04-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-26 |
Time |
21:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-26 |
Time |
21:00 |
Sent To |
|
|
| Notes |
| 2001-04-26 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT NOTES FROM | | | FIRST REVIEW WERE NOT ADDRESSED??? | | | | | | PLEASE NOTE THAT PLANS NEED TO BE | | | CORRECTED AND RE-DRAWN. PER 104.2 AND | | | 104.2.7 OF MODEL COUNTY-WIDE AND | | | CITY-WIDE | | | ADMINISTRATIVE CODE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION AND | | | ADDRESS NOTES FROM FIRST REVIEW. IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-03-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-06 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-06 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2001-03-06 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | | #`S ON PLANS AND CORRELATE WITH A | | | SUBMITTED PANEL SCHEDULE. | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | PER 220 AND INCLUDE ALL KITCHEN | | | EQUIPMENT ETC. PLEASE NOTE ALL | | | CONTINUOUS ARE AT 125%. | | | | | | 3)NOTE: PLEASE PROVIDE CLARIFICATION ON | | | MAIN DISCONNECT? PANEL SHOWN AS MLO. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVEIEW. | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-05-02 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-05-02 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2001-07-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-06 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-06 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-05-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-25 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-25 |
Time |
08:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-04-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-24 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-24 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2001-04-24 00:00:00 | 1) STILL NO INFORMATION ON THE GAS | | | INSTALLATION PROVIDED WITH PLANS. | | | 2) STILL NO INTERIOR FINISH INFORMATION | | | PROVIDED WITH PLANS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096, EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-03-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-09 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-09 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2001-03-09 00:00:00 | 1) IS THE HOOD AND EXTINGUISHING SYSTEM | | | NEW OR EXISTING. PLEASE CLARIFY. IF NEW | | | SEPARATE PLANS AND PERMITS REQUIRED FOR | | | THE HOOD, DUCT AND EXTINGUISHING SYSTEM. | | | 2) THE PLANS APPEAR TO INDICATE THE | | | INSTALLATION OF GAS. PLEASE CLEARLY | | | SHOW ON THE DRAWINGS. | | | 3) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR THE | | | SPACE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2001-06-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-09 |
Time |
07:37 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2001-06-09 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2001-06-09 00:00:00 | ********************DENIED************** | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW.PLEASE SUBMIT PLANS WITH | | | MECHANICAL PERMIT APPLICATION. | | | | | | ADDITIONAL MECHANICAL PERMIT REQUIRED | | | FOR HOOD, FIRE SUPRESSION AND WALK-IN | | | COOLERS.PLEASE SUBMIT PLANS AND | | | MANUFACTURER DETAILS WITH PERMIT | | | APPLICATION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2001-04-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-27 |
Time |
12:06 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2001-04-27 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2001-04-27 00:00:00 | ******************DENIED**************** | | | | | | NO MECHANICAL PLANS SUBMITTED FOR | | | REVIEW PLEASE SUBMIT PLANS WITH | | | MECHANICAL PERMIT APPLICATION. | | | | | | ADDITIONAL MECHANICAL PERMITS REQUIRED | | | FOR HOOD, FIRE SUPPRESSION AND WALK-IN | | | COOLERS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, CONTACT PATTY | | | KRAUSS AT (561) 659-8096 EXT.8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-03-22 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-03-22 |
Time |
13:31 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2001-03-22 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2001-03-22 00:00:00 | INSUFFICIENT INFORMATION PROVIDED FOR | | | REVIEW | | | PROVIDE PLANS AT TIME OF MECHANICAL | | | PERMIT APPLICATION PRIOR TO ANY | | | MECHANICAL WORK BEING DONE. | | | SEPARATE PERMIT REQUIRED FOR GREASE HOOD | | | AND DUCTWORK. PROVIDE DETAILED PLANS AT | | | TIME OF PERMIT APPLICATION FOR HOOD | | | PRIOR TO ANY WORK BEING DONE ON THE | | | HOOD SYSTEM. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-07-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-07-10 |
Time |
15:04 |
Rev Time |
1.50 |
| Received By |
jleech |
Date |
2001-07-10 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-06-09 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-06-09 |
Time |
15:31 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-09 00:00:00 | PLUMBING PLAN REVIEW"DENIED" | | | (1) PROVISO DATED 5-6-01 WITHDRAWN DUE | | | TO REVISION DATED 5-23 01,UNSAT. | | | (2) PLUMBING REVISION,TO BE SIGNED AND | | | SEALED BY ENGINEER OF RECORD. | | | THIS DESIGN IS TO COMPLY WITH STD PLBG. | | | CODE 94,SEC 921,HORZONTAL WASTE & VENT | | | SYSTEM.MOP SINK CAN NOT BE DELETED WITH- | | | OUT DEPT OF HOTEL BUSINESS REGULATION | | | APPROVAL. | | | (3) GAS DRAWGING NOT APPROVED,SEE GAS | | | PERMIT APPLICATION REQUIRMENTS, ANSWER | | | EA ITEM CIRCLED, SHOW LOCATION OF EMERG- | | | ENCY GAS SOLENOID, FOR HOOD SHUT DOWN, | | | THIS IS TO BE BELOW CEILING, WITH MANUAL | | | SOV UP STREAM OF SOLENOID VALVE, WITH A | | | UNION DOWN STREAM. SGC 97 SEC 403. | | | DRWG TO BE SIGNED & SEALED BY ENGINEER | | | OF RECORD. SEPERATE PERMIT IS REQUIRED. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS 561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-05-06 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-05-06 |
Time |
13:58 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-06 00:00:00 | PLUMBING PLAN REVIEW PROVISO WITHDRAWN | | | DUE TO REVISION SUBMITTED5-23-01PES | | | SEPERATE GAS PERMIT WITH DRAWING REQ. | | | NUMBER OF FLR SINKS SHOWN FOR I/D WASTE. | | | WATER PIPING AND WTR/HTR,TO BE CK BY | | | FIELD INSPECTOR | | | END OF COMMENTS PAUL SCHMITZ |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-03-16 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-16 |
Time |
16:22 |
Rev Time |
0.50 |
| Received By |
pschmitz |
Date |
2001-03-16 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2001-03-16 00:00:00 | DENIED; | | | | | | 1.GREASE TRAP TO BE SIZED BY RODNEY | | | COMPO, 835-7423 | | | WASTE ORD. #2938-96 | | | | | | 2.SHOW LINE DRAWING WHERE PLUMBING IS TO | | | INSTALLED. | | | | | | 3.FLOOR SINK IS TO BE USED INPLACE OF A | | | FLOOR DRAIN. | | | | | | 4.SEPARATE PERMIT REQUIRED FOR GAS. GAS | | | DRAWINGS REQUIRED WITH PERMIT | | | APPLICATION. | | | | | | 5.WHAT SIZE IS WATER HEATER?. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-03-05 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-02-12 |
Time |
10:39 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-02-12 00:00:00 | MUST PROVIDE A SITE PLANS SHOWING | | | PARKING,LANDSCAPING & SETBACK | | | PHONE NUMBER FOR CONTRACTOR DOES NOT | | | WORK |
|
|