Plan Review Details - Permit 01020317
Plan Review Stops For Permit 01020317
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-06-12 Cont ID  
Sent By hpiskura Date 2001-06-12 Time 16:40 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-05-07 00:00:00OK W/ HC LAYOUT COPIED FROM MANUAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-07 Cont ID  
Sent By jwitmer Date 2001-03-07 Time 12:11 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-07 00:00:00PERMIT # 01020317
 446 NORTHWOOD RD
 HATCHEY CONSTRUCTION
 588-8288
  
 1)- FL HANDICAPPED CODE 4.1.6.2.2(3)A:
 SHOW RAMP AT FRONT ENTRY OF BUILDING.
 HANDICAPPED RAMP SLOPE MAY BE BETWEEN
 1:10 & 1:12 IS ALLOWED FOR A MAXIMUM
 RISE OF 6 INCHES.
  
 (2)- FL HANDICAPPED CODE 4.16:
 THE FLOOR PLAN AND THE HANDICAPPED
 TOLIET DETAILHAVE DISCREPANCIES IN
 SIZE AND LAY OUT.
  
 (3)- NOTE 5&6 SHOW THE REPLACEMENT OF
 WINDOWS WHICH WILL REQUIRE A ACCEPTANCE
 REPORT, EITHER SBCCI OR DADE COUNTY
 PRODUCT APPROVAL (2 COPIES).
  
 (4)- NOTE #14: SBC 1204.2 WALLS & FLOORS
 OF ALL PUBLIC RESTROOMS SHALL BE LINED
 WITH NONABSORBANT MATERIAL TO A HEIGTH
 OF 4 FT. ABOVE THE FLOOR.
  
 (5)- THE STOREFRONT DOOR AND WINDOWS
 ARE TO BE UNDER SEPERATE PERMIT AND
 FEES. 2 COPIES OF AN PRODUCT ACCEPTANCE
 REPORT WILL BE REQUIRED. S.B.C.C.I.
 REPORT OR DADE COUNTY WILL BE ACCEPTABLE
 IF THE REPORT HASN,T HAD LARGE MISSLE
 IMPACT TESTING STORM SHUTTERS WILL BE RE
 QUIRED THAT HAVE THE LARGE MISSLE TEST-
 ING WITH REPORT.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-07-05 Cont ID  
Sent By dpalmer Date 2001-07-05 Time 18:49 Rev Time 0.00
Received By dpalmer Date 2001-07-05 Time 18:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-06-07 Cont ID  
Sent By dpalmer Date 2001-06-07 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2001-06-07 Time 19:11 Sent To  
Notes
2001-06-07 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT THE SAME NOTES
 FROM FIRST AND SECOND REVIEW STILL
 STAND. NO ELECTRICAL COMMENTS WERE
 ADDRESSED FROM PREVIOUS REVIEWS/COMMENTS
  
  
 PLEASE SUBMIT INFORMATION FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-04-26 Cont ID  
Sent By dpalmer Date 2001-04-26 Time 21:00 Rev Time 0.00
Received By dpalmer Date 2001-04-26 Time 21:00 Sent To  
Notes
2001-04-26 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT NOTES FROM
 FIRST REVIEW WERE NOT ADDRESSED???
  
 PLEASE NOTE THAT PLANS NEED TO BE
 CORRECTED AND RE-DRAWN. PER 104.2 AND
 104.2.7 OF MODEL COUNTY-WIDE AND
 CITY-WIDE
 ADMINISTRATIVE CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION AND
 ADDRESS NOTES FROM FIRST REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-06 Cont ID  
Sent By dpalmer Date 2001-03-06 Time 10:08 Rev Time 0.00
Received By dpalmer Date 2001-03-06 Time 10:08 Sent To  
Notes
2001-03-06 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS AND CORRELATE WITH A
 SUBMITTED PANEL SCHEDULE.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER 220 AND INCLUDE ALL KITCHEN
 EQUIPMENT ETC. PLEASE NOTE ALL
 CONTINUOUS ARE AT 125%.
  
 3)NOTE: PLEASE PROVIDE CLARIFICATION ON
 MAIN DISCONNECT? PANEL SHOWN AS MLO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVEIEW.
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-05-02 Cont ID  
Sent By lsmith Date 2001-05-02 Time 14:18 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-07-06 Cont ID  
Sent By mcarsill Date 2001-07-06 Time 10:58 Rev Time 0.00
Received By mcarsill Date 2001-07-06 Time 10:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-05-25 Cont ID  
Sent By mcarsill Date 2001-05-25 Time 08:32 Rev Time 0.00
Received By mcarsill Date 2001-05-25 Time 08:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-04-24 Cont ID  
Sent By mcarsill Date 2001-04-24 Time 15:47 Rev Time 0.00
Received By mcarsill Date 2001-04-24 Time 15:47 Sent To  
Notes
2001-04-24 00:00:001) STILL NO INFORMATION ON THE GAS
 INSTALLATION PROVIDED WITH PLANS.
 2) STILL NO INTERIOR FINISH INFORMATION
 PROVIDED WITH PLANS.
  
 CAPTAIN MIKE CARSILLO
 659-8096, EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-03-09 Cont ID  
Sent By mcarsill Date 2001-03-09 Time 14:16 Rev Time 0.00
Received By mcarsill Date 2001-03-09 Time 14:16 Sent To  
Notes
2001-03-09 00:00:001) IS THE HOOD AND EXTINGUISHING SYSTEM
 NEW OR EXISTING. PLEASE CLARIFY. IF NEW
 SEPARATE PLANS AND PERMITS REQUIRED FOR
 THE HOOD, DUCT AND EXTINGUISHING SYSTEM.
 2) THE PLANS APPEAR TO INDICATE THE
 INSTALLATION OF GAS. PLEASE CLEARLY
 SHOW ON THE DRAWINGS.
 3) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR THE
 SPACE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2001-06-09 Cont ID  
Sent By pkrauss Date 2001-06-09 Time 07:37 Rev Time 0.25
Received By pkrauss Date 2001-06-09 Time 07:32 Sent To  
Notes
2001-06-09 00:00:00********************DENIED**************
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE SUBMIT PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 ADDITIONAL MECHANICAL PERMIT REQUIRED
 FOR HOOD, FIRE SUPRESSION AND WALK-IN
 COOLERS.PLEASE SUBMIT PLANS AND
 MANUFACTURER DETAILS WITH PERMIT
 APPLICATION.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-04-27 Cont ID  
Sent By pkrauss Date 2001-04-27 Time 12:06 Rev Time 0.30
Received By pkrauss Date 2001-04-27 Time 12:06 Sent To  
Notes
2001-04-27 00:00:00******************DENIED****************
  
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW PLEASE SUBMIT PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 ADDITIONAL MECHANICAL PERMITS REQUIRED
 FOR HOOD, FIRE SUPPRESSION AND WALK-IN
 COOLERS.
  
  
 IF YOU HAVE ANY QUESTIONS, CONTACT PATTY
 KRAUSS AT (561) 659-8096 EXT.8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-03-22 Cont ID  
Sent By ndenmark Date 2001-03-22 Time 13:31 Rev Time 0.25
Received By ndenmark Date 2001-03-22 Time 13:31 Sent To  
Notes
2001-03-22 00:00:00INSUFFICIENT INFORMATION PROVIDED FOR
 REVIEW
 PROVIDE PLANS AT TIME OF MECHANICAL
 PERMIT APPLICATION PRIOR TO ANY
 MECHANICAL WORK BEING DONE.
 SEPARATE PERMIT REQUIRED FOR GREASE HOOD
 AND DUCTWORK. PROVIDE DETAILED PLANS AT
 TIME OF PERMIT APPLICATION FOR HOOD
 PRIOR TO ANY WORK BEING DONE ON THE
 HOOD SYSTEM.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-07-10 Cont ID  
Sent By jleech Date 2001-07-10 Time 15:04 Rev Time 1.50
Received By jleech Date 2001-07-10 Time 15:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-06-09 Cont ID  
Sent By pschmitz Date 2001-06-09 Time 15:31 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-09 00:00:00PLUMBING PLAN REVIEW"DENIED"
 (1) PROVISO DATED 5-6-01 WITHDRAWN DUE
 TO REVISION DATED 5-23 01,UNSAT.
 (2) PLUMBING REVISION,TO BE SIGNED AND
 SEALED BY ENGINEER OF RECORD.
 THIS DESIGN IS TO COMPLY WITH STD PLBG.
 CODE 94,SEC 921,HORZONTAL WASTE & VENT
 SYSTEM.MOP SINK CAN NOT BE DELETED WITH-
 OUT DEPT OF HOTEL BUSINESS REGULATION
 APPROVAL.
 (3) GAS DRAWGING NOT APPROVED,SEE GAS
 PERMIT APPLICATION REQUIRMENTS, ANSWER
 EA ITEM CIRCLED, SHOW LOCATION OF EMERG-
 ENCY GAS SOLENOID, FOR HOOD SHUT DOWN,
 THIS IS TO BE BELOW CEILING, WITH MANUAL
 SOV UP STREAM OF SOLENOID VALVE, WITH A
 UNION DOWN STREAM. SGC 97 SEC 403.
 DRWG TO BE SIGNED & SEALED BY ENGINEER
 OF RECORD. SEPERATE PERMIT IS REQUIRED.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS 561-659-8096X8233

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-05-06 Cont ID  
Sent By pschmitz Date 2001-05-06 Time 13:58 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-06 00:00:00PLUMBING PLAN REVIEW PROVISO WITHDRAWN
 DUE TO REVISION SUBMITTED5-23-01PES
 SEPERATE GAS PERMIT WITH DRAWING REQ.
 NUMBER OF FLR SINKS SHOWN FOR I/D WASTE.
 WATER PIPING AND WTR/HTR,TO BE CK BY
 FIELD INSPECTOR
 END OF COMMENTS PAUL SCHMITZ

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-03-16 Cont ID  
Sent By jleech Date 2001-03-16 Time 16:22 Rev Time 0.50
Received By pschmitz Date 2001-03-16 Time 16:21 Sent To  
Notes
2001-03-16 00:00:00DENIED;
  
 1.GREASE TRAP TO BE SIZED BY RODNEY
 COMPO, 835-7423
 WASTE ORD. #2938-96
  
 2.SHOW LINE DRAWING WHERE PLUMBING IS TO
 INSTALLED.
  
 3.FLOOR SINK IS TO BE USED INPLACE OF A
 FLOOR DRAIN.
  
 4.SEPARATE PERMIT REQUIRED FOR GAS. GAS
 DRAWINGS REQUIRED WITH PERMIT
 APPLICATION.
  
 5.WHAT SIZE IS WATER HEATER?.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-03-05 Cont ID  
Sent By sgraham Date 2001-02-12 Time 10:39 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-02-12 00:00:00MUST PROVIDE A SITE PLANS SHOWING
 PARKING,LANDSCAPING & SETBACK
 PHONE NUMBER FOR CONTRACTOR DOES NOT
 WORK