Plan Review Details - Permit 01020109
Plan Review Stops For Permit 01020109
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-04-03 Cont ID  
Sent By jwitmer Date 2001-04-03 Time 10:26 Rev Time 0.33
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-03-30 Cont ID  
Sent By jwitmer Date 2001-03-30 Time 07:37 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-30 00:00:00BUILDING PLAN REVIEW
 01020109
 302 DATURA 2ND FLOOR
 A-SERVICE GLASS & MIRROR
 (954) 561-8213
  
 1)- SBC 1203.1.5 REQUIRES THAT VENTILA-
 TION WILL BE PROVIDED FOR INTERIOR ROOMS
 SKYLIGHTS,VENTS, LOUVERS OR MECHANICAL
 VENTILATION MAY BE SUBSTITUTED FOR
 WINDOWS WHEN APPROVED BY THE BUILDING
 OFFICIAL, PROVIDED ADEQUITE LIGHT &
 VENTILAATION IS PROVED TO MEET THE
 REQUIREMENTS OF THIS CHAPTER.
  
 2)- THE NOTE FOR HANDICAPPED ACCESSIBL-
 ITY IN THE LOUNGE WAS DELETED. NOTES 13
 & 15 DELT WITH THIS ISSUE.THE 1997
 FLORIDA ACCESSIBILITY CODE 4.1.6.2.2
 DEALS WITH THE 20% DISPROPORTIONATE
 COST. 20% OF THE CONTRACT VALUE GOES
 TOWARDS UPGRADING BUILDINGS FOR HANDICAP
 PED ACCESSIBILITY. SINCE THE CONTRACT
 VALUE IS $30,000.00 / $6,000.00 WWOULD
 BE SPENT IN UP GRADES. THE BUILDING DOES
 HAVE AN ELEVATOR FOR VERTICAL ACCESSIBIL
 ITY, (II) AN ACCESSIBILE ROUTE TO THE
 ALTERED AREA, WOULD BE THE NEXT ELEMENT
 TO REVIEW. THIS WOULD INCLUDE THE LOUNGE
 AREA. (III) THE THIRD AREA WOULD BE AT
 LEAST (1) ACCESSIBILE RESTROOM FOR EACH
 SEX OR A SINGLE UNISEX RESTROOM.
  
 SHOW HOW THE $6,000.00 DOLLARS WILL BE
 USED. A COPY OF THE DISPROPORTION COST
 IS ENCLOSED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-03-20 Cont ID  
Sent By hpiskura Date 2001-03-20 Time 15:35 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-03-20 00:00:00ITEMS #3 AND #5 NOT ADDRESSED FROM
 FIRST CHECKLIST

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-02-12 Cont ID  
Sent By hpiskura Date 2001-02-12 Time 13:16 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-02-12 00:00:001 THE PLANS SHOW WORK ON THE SECOND
 FLOOR AND THE APPLICATION SAYS THIRD
 FLOOR.PLEASE CLARIFY.
  
 2 SHOW HOW TENANT SEPARATION WILL BE
 ACCOMPLISHED AT THE AREA SHOWN AS
 "EXISTING RECEPTION" NEAR GRID LINES
 (3) AND (B).
 SEE SBC 704.3.
  
 3SHOW HOW VENTILATION WILL BE PROVIDED
 FOR THE INTERIOR ROOMS.SEE SBC 1203.
  
 4THIS BUILDING IS OF TYPE II
 CONSTRUCTION AND CANNOT USE WOOD STUDS
 AS SHOWN IN "TYPICAL INTERIOR
 PARTITION"SEE SBC 609.2.1. AND SBC
 604.
  
 5SHOW THE LOUNGE,NOTES 13 AND 15, AS
 BEING HANDICAP ACCESSIBLE.
  
 HAROLD PISKURA
 659-8096 X 8219

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-04-09 Cont ID  
Sent By dpalmer Date 2001-04-09 Time 18:15 Rev Time 0.00
Received By dpalmer Date 2001-04-09 Time 18:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-03-12 Cont ID  
Sent By dpalmer Date 2001-03-12 Time 18:29 Rev Time 0.00
Received By dpalmer Date 2001-03-12 Time 18:29 Sent To  
Notes
2001-03-12 00:00:00************ UNSAT ********************
  
 1)NOTE: PLEASE NOTE THAT PER F.A.C
 ALL PLANS CONTAINING TITLE BLOCK ARE TO
 BE SIGNED AND SEALED BY THE
 ARCH/ENGINEER OF RECORD PER F.S.
 471.025 AND 481.221
  
 2) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
 PLEASE CLARIFY IF LOADS ARE SHOWN AT
 125%.
  
 3)NOTE: PLEASE SEE SHEET 2, BRANCH
 CIRCUIT #`SW ARE NOT SHOWN. NEED TO
 SHOW AND CORRELATE WITH PANEL SCHEDULE
 THAT IS
 SUBMITTED. ON FIRST SET OF REVIEW NOTES.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-02-14 Cont ID  
Sent By dpalmer Date 2001-02-14 Time 20:29 Rev Time 0.00
Received By dpalmer Date 2001-02-14 Time 20:29 Sent To  
Notes
2001-02-14 00:00:00************** UNSAT *****************
  
 1)NOTE; PLEASE SUBMIT PLANS SHOWING ALL
 NEW BRANCH CIRCUIT #`S AND CORRELATING
 PANEL SCHEDULES.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 FOR ANY NEW LOADS ADDING TO EXISTING
 PANELS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-02-27 Cont ID  
Sent By lmartine Date 2001-02-27 Time 08:04 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-03-09 Cont ID  
Sent By mcarsill Date 2001-03-09 Time 15:51 Rev Time 0.00
Received By mcarsill Date 2001-03-09 Time 15:51 Sent To  
Notes
2001-03-09 00:00:001) INTERIOR FINISH IN EXITS SHALL BE
 CLASS A OR B. INTERIOR FINISH IN
 OFFICE AREAS SHALL BE CLASS A, B, OR C.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-02-21 Cont ID  
Sent By mcarsill Date 2001-02-21 Time 15:49 Rev Time 0.00
Received By mcarsill Date 2001-02-21 Time 15:49 Sent To  
Notes
2001-02-21 00:00:001) PEMIT APPLICATION INDICATES WORK
 ON THE THIRD FLOOR BUT THE PLANS
 REFER TO THE SECOND FLOOR. PLEASE
 CLARIFY.
 2) ARE THERE ANY FIRE SPRINKLERS IN
 THE SPACE PRESENTLY OR ARE ANY PLANNED.
 3) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION.
 4) PLEASE PROVIDE OCCUPANT LOAD
 CALCULATIONS FOR TENANT SPACE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-02-27 Cont ID  
Sent By lmartine Date 2001-02-27 Time 08:05 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-02-27 Cont ID  
Sent By lmartine Date 2001-02-27 Time 08:06 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-02-27 Cont ID  
Sent By lmartine Date 2001-02-27 Time 08:07 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***