| Plan Review Stops For Permit 01020018 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-03-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-03-20 |
Time |
14:22 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-02-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-02-08 |
Time |
15:54 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-02-08 00:00:00 | NORTHWOOD UNIVERSITY | | | 2600 N MILITARY TRAIL | | | PERMIT # 01020018 | | | 1)- SBC 104.2.2 ADDITIONAL INFORMATION | | | REQUIRED, BUILDING CODE SUMMARY IS USING | | | THE WRONG CODE, WE USE THE 1997 | | | STANDARD BUILDING CODE AND THE 1997 | | | EDITION OF THE FL ACCESSIBILITY CODE. | | | THE CONSTRUCTION TYPES LISTED ON THE | | | PLAN DO NOT MATCH THE CONSTRUCTION TYPES | | | THAT WE CURRENTLY USE IN THE STANDARD | | | BUILDING CODE. THE OTHER ISSUE THAT MAY | | | CAUSE A ISSUE WOULD BE THE "YES" TO | | | BEING LOCATED IN A FIRE DISTRICT. | | | 2)- THE PLANS (A-1) INDICATE A NEW | | | STOREFRONT SYSTEM, IS THIS SYSTEM ON THE | | | INTERIOR OF THE STRUCTURE, OR IS THIS | | | A EXTERIOR WALL? GLAZYING SYSTEMS ON THE | | | EXTERIOR WILL REQUIRE APPROVAL REPORTS | | | FOR HIGH WIND AREAS. THE CITY ACCEPTS | | | DADE COUNTY PRODUCT APPROVALS OR REPORTS | | | FROM THE STANDARD BUILDING CODE CONGRESS | | | INTERNATIONAL (SBCCI). | | | 3)- THERE IS A NOTE ON THE PLAN "LOWER | | | LOBBY" IS THERE A CHANGE IN ELEVATION? | | | 4)- FL ACESSIBILITY CODE 5.2 COUNTERS | | | & BARS; SATISFY THIS REQUIREMENT. | | | 5)- FL ACCESSIBILITY CODE 5.4 DINING | | | AREAS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | PHONE (561)659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-05-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-08 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-08 |
Time |
12:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-02-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-16 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-16 |
Time |
16:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-05-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-10 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-10 |
Time |
13:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-03-13 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-13 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-13 |
Time |
12:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-02-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-02-06 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-02-06 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2001-02-06 00:00:00 | 1) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 2) EXIT SIGNS, EMERGENCY LIGHTING, AND | | | FIRE ALARM EQUIPMENT NOT SHOWN E-1. | | | BUILDING CODE SUMMARY BOX INDICATES | | | THAT THESE ITEMS ARE PRESENT. | | | 3) PROVIDE PERMIT AND SHOP DRAWINGS FOR | | | ANY FIRE SPRINKLER REMODEL WORK PLANNED. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-02-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-02-20 |
Time |
09:26 |
Rev Time |
0.33 |
| Received By |
pkrauss |
Date |
2001-02-20 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2001-02-20 00:00:00 | *****************DENIED***************** | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW.SUBMIT PLANS WITH MECHANICAL | | | PERMIT APPLICATION. | | | | | | PHK 2/20/01 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2001-03-26 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-03-26 |
Time |
15:32 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-26 00:00:00 | NO PLUMBING PER CONTRACTOR.J LEACH | | | SAID TO POST "N".IF ANY PLUMBING | | | IS REQUIRED IN FUTURE A SEPARATE PERMIT | | | AND DRAWINGS WILL BE REQUIRED. LS 3/26/0 | | | 1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-02-21 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-02-21 |
Time |
14:47 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2001-02-21 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2001-02-21 00:00:00 | DENIED; | | | | | | 1.NOT ENOUGH INFORMATION. SUBMIT | | | INFORMATION ON KITCHEN EQUIPMENT. |
|
|