| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-02-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-02-02 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-02-02 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2001-02-02 00:00:00 | 1) SMOKE DETECTORS WHEN INSTALLED ARE | | | TO BE A MINIMUM OF THREE FEET FROM | | | AIR CONDITIONER DIFFUSERS. | | | 2) THE COMBINATION SYSTEM FIRE/SECURITY | | | SHALL MEET ALL OF THE REQUIREMENTS OF | | | NFPA 72, SECTION 2-4.7 COMBINATION | | | SYSTEM. ALSO NFPA 72, SECTION 2-4.7.1 | | | AND 2-4.7.2 ARE TO BE FOLLOWED. | | | 3) SYSTEM TO BE MONITORED BY A LICENSED | | | UL LISTED CENTRAL STATION APPROVED BY | | | THE FIRE RESCUE DEPARTMENT. | | | 4) ANY HOOD DUCT AND EXTINGUISHING | | | SYSTEMS CONTAINED IN THE BUILDING ARE | | | TO BE CONNECTED TO THE FIRE ALARM | | | SYSTEM. | | | 5) PLEASE EXPLAIN SMOKE DETECTOR | | | ARRANGEMENT FOR HOLD-OPEN DOORS IN | | | BUILDING. PLEASE REFER TO NFPA 72, | | | SECTION 5-11.7.4 SMOKE DETECTORS FOR | | | DOOR RELEASE SERVICE. PLEASE SEE | | | 5-11.7.4.1-5-11.7.4.4.1. | | | 6) DUCT SMOKE DETECTOR INSTALLATION TO | | | COMPLY WITH NFPA 72. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|