Plan Review Details - Permit 01011457
Plan Review Stops For Permit 01011457
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-03-01 Cont ID  
Sent By mcarsill Date 2001-03-01 Time 15:22 Rev Time 0.00
Received By mcarsill Date 2001-03-01 Time 15:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-02-02 Cont ID  
Sent By mcarsill Date 2001-02-02 Time 09:38 Rev Time 0.00
Received By mcarsill Date 2001-02-02 Time 09:37 Sent To  
Notes
2001-02-02 00:00:001) SMOKE DETECTORS WHEN INSTALLED ARE
 TO BE A MINIMUM OF THREE FEET FROM
 AIR CONDITIONER DIFFUSERS.
 2) THE COMBINATION SYSTEM FIRE/SECURITY
 SHALL MEET ALL OF THE REQUIREMENTS OF
 NFPA 72, SECTION 2-4.7 COMBINATION
 SYSTEM. ALSO NFPA 72, SECTION 2-4.7.1
 AND 2-4.7.2 ARE TO BE FOLLOWED.
 3) SYSTEM TO BE MONITORED BY A LICENSED
 UL LISTED CENTRAL STATION APPROVED BY
 THE FIRE RESCUE DEPARTMENT.
 4) ANY HOOD DUCT AND EXTINGUISHING
 SYSTEMS CONTAINED IN THE BUILDING ARE
 TO BE CONNECTED TO THE FIRE ALARM
 SYSTEM.
 5) PLEASE EXPLAIN SMOKE DETECTOR
 ARRANGEMENT FOR HOLD-OPEN DOORS IN
 BUILDING. PLEASE REFER TO NFPA 72,
 SECTION 5-11.7.4 SMOKE DETECTORS FOR
 DOOR RELEASE SERVICE. PLEASE SEE
 5-11.7.4.1-5-11.7.4.4.1.
 6) DUCT SMOKE DETECTOR INSTALLATION TO
 COMPLY WITH NFPA 72.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910