Plan Review Details - Permit 01011378
Plan Review Stops For Permit 01011378
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-02-06 Cont ID  
Sent By jwitmer Date 2001-02-06 Time 07:08 Rev Time 0.75
Received By jwitmer Date 2001-02-06 Time 06:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-13 Cont ID  
Sent By dpalmer Date 2001-03-13 Time 12:15 Rev Time 0.00
Received By dpalmer Date 2001-03-13 Time 12:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-02-15 Cont ID  
Sent By dpalmer Date 2001-02-15 Time 07:17 Rev Time 0.00
Received By dpalmer Date 2001-02-15 Time 07:17 Sent To  
Notes
2001-02-15 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
 PANEL AIC RATINGS WERE SUBMITTED BUT
 NOT FOR MAINS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION. IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-02-22 Cont ID  
Sent By lsmith Date 2001-02-22 Time 15:28 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-02-06 Cont ID  
Sent By mcarsill Date 2001-02-06 Time 10:12 Rev Time 0.00
Received By mcarsill Date 2001-02-06 Time 10:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-02-23 Cont ID  
Sent By pkrauss Date 2001-02-23 Time 16:35 Rev Time 0.33
Received By pkrauss Date 2001-02-23 Time 16:35 Sent To  
Notes
2001-02-23 00:00:00NO MECHANICAL - USING EXISTING HVAC
 SYSTEM, MOVING TWO GRILLES AND ADDING
 THREE GRILLES TO A 16 1/2 TON SYSTEM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-03-22 Cont ID  
Sent By jleech Date 2001-03-22 Time 16:10 Rev Time 0.50
Received By jleech Date 2001-03-22 Time 16:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-02-26 Cont ID  
Sent By jleech Date 2001-02-26 Time 16:01 Rev Time 1.00
Received By jleech Date 2001-02-26 Time 16:01 Sent To  
Notes
2001-02-26 00:00:00DENIED;
  
 1.SHOW SQ. FT. OF UNIT USING 407.1.3 FOR
 DEDUCTABLE FLOOR SPACE AND SHOW
 MINIMUM PLUMBING FACILITIES PER. 94
 SPC TABLE 407.
  
 2.DRINKING FOUNTAIN REQUIRED PER. TABLE
 407.DRINKING FOUNTAIN SHALL COMPLY
 WITH FACBC SEC. 4.1.3 (10) AND 4.15.
 PROVISIONS SHALL BE MADE FOR PEOPLE
 WHO HAVE TROUBLE BENDING OR STOOPING.
  
 3.HANDICAP BATHROOM MUST 5'-9" NOT 5'-6"
 FACBC 4.17.3.
  
 4.LOUNGE SINK SHALL COMPLY WITH FACBC
 4.24 THRU 4.24.7.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-02-22 Cont ID  
Sent By lsmith Date 2001-02-22 Time 15:28 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***