| Plan Review Stops For Permit 01011346 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-01-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-30 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-30 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2001-01-30 00:00:00 | 1) THE FIRE ALARM SYSTEM WHEN ACTIVATED | | | IS TO BE AUDIBLE THROUGHOUT. | | | 2) SYSTEM TO BE CLASS A, STYLE D WIRED. | | | 3) DUCT SMOKE DETECTORS WHEN ACTIVATED | | | IS TO CAUSE THE FIRE ALARM SYSTEM TO | | | ACTIVATE AND SHUT DOWN THE AIR | | | CONDITIONING EQUIPMENT. | | | 4) SMOKE DETECTORS WHEN INSTALLED ARE TO | | | BE A MINIMUM OF THREE FEET FROM AIR | | | CONDITONER DIFFUSERS. | | | 5) SYSTEM TO BE MONITORED BY A LICENSED | | | UL LISTED CENTRAL STATION APPROVED BY | | | THE FIRE RESCUE DEPARTMENT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|