Plan Review Details - Permit 01011254
Plan Review Stops For Permit 01011254
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-14 Cont ID  
Sent By rmcdouga Date 2001-06-14 Time 09:15 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-06-14 00:00:00*************BUILDING UNSAT*************
 REVISION TO ADD CHIMNEY SURROUND
  
 ADDITIONAL INFORMATION IS REQUIRED
 PER 97 SBC SECT.102.4.1.
  
 1) PROVIDE DETAIL OF CEILING INSULATION
 AT PROPOSED CHIMNEY THAT COMPLIES WITH
 FL ENERGY CODE.
  
 2) INDICATE IF CHIMNEY IS TO BE
 FUNCTIONING OR NOT. IF FUNCTIONAL,
 INDICATE PURPOSE FOR WHICH IT WILL BE
 USED AND PROVIDE ALL PERTINENT
 INFORMATION FOR FLUE AND APPLIANCE.
  
 3) INDICATE OVERALL HEIGHT OF THIS
 STRUCTURE.
  
 4) INDICATE WALL AND ROOFING MATERIALS.
 (COMPONENTS AND CLADDING)
  
 5) INDICATE FIREBLOCKING &
 DRAFTSTOPPINGBETWEEN CHIMNEY AND ATTIC
 SPACE.
  
 6) PROVIDE STRUCTRAL DESIGN
 CALCULATIONS FOR BEARING, UPLIFT AND
 MOMENT.
  
 7) INDICATE THE TYPE AND LOCATION OF
 CONNECTORS USED TO SUPPORT AND PROVIDE
 CONTINOUS TIE TO STRUCTURE.
  
 8) PROVIDE STRUCTURAL ANALYSIS OF
 TRUSSES TO ENSURE THEIR ABILITY TO
 HANDLE THE ADDITIONAL LOADS THAT WILL
 BE IMPOSED BY THE CHIMNEY SURROUND.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-04-09 Cont ID  
Sent By dpalmer Date 2001-04-09 Time 19:17 Rev Time 0.00
Received By dpalmer Date 2001-04-09 Time 19:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-03-22 Cont ID  
Sent By dpalmer Date 2001-03-22 Time 20:38 Rev Time 0.00
Received By dpalmer Date 2001-03-22 Time 20:38 Sent To  
Notes
2001-03-22 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 FROM FIRST REVIEW WERE ADDRESSED.
 CLARIFICATION FOR LOADS/PANEL SIZES/
 ETC.
  
 2)NOTE: PLEASE NOTE THAT ALL CHANGES
 ON PLANS THAT ARE SIGNED AND SEALED
 DOCUMENTS, NEED TO HAVE EACH CHANGE
 INITIALED AND DATED BY ARCH/ ENGINEER
 OF RECORD. SOME CHANGES WERE NOT THE
 SAME ON BOTH SHEETS AND CLARIFICATIONS
 WERE NOT ADDRESSED.F.S. 481.221/471.025
 COUNTYWIDE AND CITYWIDE CODE:104.2.
 PLEASE RE-DRAW PLANS AND SUBMIT FOR
 REVIEW AS REQUESTED AND DONE ON
 PREVIOUSSUBMITTALS. THIS IS THE SAME
 THING THAT HAS HAPPENED BEFORE. ONCE
 AGAIN, IF THERE ARE ANY QUESTIONS,
 CLARIFICATIONS, OR IF A MEETING IS
 NEEDED TO GO OVER NOTES EITHER BY PHONE
 OR IN PERSON. PLEASE DO NOT HESITATE IN
 CALLING.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-02-06 Cont ID  
Sent By dpalmer Date 2001-02-06 Time 17:31 Rev Time 0.00
Received By dpalmer Date 2001-02-06 Time 17:31 Sent To  
Notes
2001-02-06 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 2) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 3) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 4) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
  
 5) NOTE: PLEASE SHOW ALL OUTLETS
 SERVINGKITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
  
 6)NOTE: PLEASENOTE, PLANS ONLY SHOW
 ONE MAIN AND ONE PANELSCHEDULE.
 PLEASE CORRLATE.
  
 7)NOTE: PLEASE NOTE THAT THE RISER
 DIAGRAMS AND PANEL SCHEUDULES DO NOT
 CORRELATE.
 TOTALS/240AMPS ???
 200A EQUIPMENT WITH OVER 200A LOADS??
 250A PANELS ON PANEL SCH AND 200A ON
 RISER.????
 150A PANEL AND 100A ON RISER???
 WHAT SIZE IS METERCAN??
 104A LOAD ON 100A MLO OR 150A???
 ETC ETC,,
  
 8) NOTE: PLEASE SHOW GROUNDING
 ELECTRODE GOING TO BLDG STEEL REQ`D
 PER 250-50
  
 9)NOTE: MISSING HALL OUTLET PER 210-52H
  
 10)NOTE: MISSING WHIRLPOOL ON PANEL
 SCHEDULE THAT IS SHOWN ON PLAN??
  
 PLEASE SUBMIT ALL THEABOVE
 INFORMATIONFOR REVIEW. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-20 Cont ID  
Sent By pkrauss Date 2001-08-20 Time 16:12 Rev Time 0.35
Received By pkrauss Date 2001-08-20 Time 16:12 Sent To  
Notes
2001-08-20 00:00:00MECH PERMIT 01011255

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-02-06 Cont ID  
Sent By jleech Date 2001-02-06 Time 08:21 Rev Time 0.33
Received By jleech Date 2001-02-06 Time 08:21 Sent To  
Notes
2001-02-06 00:00:00PROVISO;
 ENERGY CAULK OR A/C EQUIPMENT NEED
 TO BE THE SAME SEER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-02-06 Cont ID  
Sent By jleech Date 2001-02-06 Time 08:24 Rev Time 0.25
Received By jleech Date 2001-02-06 Time 08:24 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-04-02 Cont ID  
Sent By rmcdouga Date 2001-04-02 Time 14:25 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-04-02 00:00:00************BUILDING PROVISO************
  
 1) PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLIES. 97 SBC 2406.2.
  
 2) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS.
  
 3) ARCHITECT TO PROVIDE SIGNED AND
 SEALED DETAIL OF FOOTINGS INDICATING
 FOOTING DIMENSIONS AND REINFORCEMENT FOR
 COLUMNS LOCATED AT COVERED PORCH ON
 FRONT ELEVATION.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-03-01 Cont ID  
Sent By rmcdouga Date 2001-03-01 Time 09:01 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-03-01 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLIES PER 1997 SBC 2406.2.
  
 4) PROVIDE KEY PLANS AND INSTALLATION
 SCHEDULE INDICATING THE SPECIFIC TYPES
 OF ANCHORS TO BE USED FOR STORM PANELS.
  
 5) PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 - ARCHED FIXED GLASS WINDOWS
 - FRENCH DOORS WITH SIDELITES (ASSEMBLY)
  
 6) ON SHEET A-2,FOOTING F5 IS NOT LISTED
 ON THE FOOTING SCHEDULE AND F4 DOES NOT
 LIST THE NUMBER OF #5 BARS REQUIRED.
 PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-02-02 Cont ID  
Sent By sgraham Date 2001-02-02 Time 14:34 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***