Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-04-10 Cont ID  
Sent By mcarsill Date 2001-04-10 Time 09:10 Rev Time 0.00
Received By mcarsill Date 2001-04-10 Time 09:10 Sent To  
Notes
2001-04-10 00:00:001) SMOKE DETECTORS WHEN INSTALLED SHALL
 BE A MINIMUM OF THREE FEET FROM ANY
 AIR CONDITIONING DIFFUSERS.
 2) DUCT SMOKE DETECTORS ARE REQUIRED IN
 HVAC SYSTEMS OVER 2000 CFM'S. WHEN
 ACTIVATED, DUCT SMOKE DETECTORS SHALL
 CAUSE THE FIRE ALARM SYSTEM TO ACTIVATE
 AND CAUSE ASSOCIATED HVAC EQUIPMENT TO
 SHUT DOWN.
 3) THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS ARE TO BE MONITORED BY A
 LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 4) SYSTEM IS TO BE TESTED IN THE
 PRESENCE OF FIRE RESCUE PERSONNEL.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-03-30 Cont ID  
Sent By mcarsill Date 2001-03-30 Time 12:54 Rev Time 0.00
Received By mcarsill Date 2001-03-30 Time 12:54 Sent To  
Notes
2001-03-30 00:00:001) PLANS STILL NOT SIGNED AND SEALED.
 VALUE OVER 5,000.00 DOLLARS AND
 CONTAINS ENGINEERING FIRMS TITLE BLOCK.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-01-30 Cont ID  
Sent By mcarsill Date 2001-01-30 Time 12:55 Rev Time 0.00
Received By mcarsill Date 2001-01-30 Time 12:54 Sent To  
Notes
2001-01-30 00:00:001) PLANS NOT SIGNED AND SEALED. VALUE
 OVER 5,000.00 DOLLARS. VALUE LISTED ON
 PERMIT APPLICATION 16,000.00 DOLLARS.
 PLEASE HAVE PLANS SIGNED AND SEALED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910