| Plan Review Stops For Permit 01011197 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-02-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-02-22 |
Time |
13:00 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-02-22 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2001-02-22 00:00:00 | PROVISO:DUCT SMOKE DETECTORS MUST BE | | | TESTED TO SHOW COMPLIANCE WITH NFPA | | | 90A-12, 4.4.4.3, FAN SHUT DOWN WITH | | | NOTIFICATION TO NORMALLY OCCUPIED AREAS | | | BY ALARM/STROBE. | | | | | | AHU-5 IN THE COPY/FILE WORKROOM (ROOM | | | 234), SHALL HAVE ACCESS/CLEARANCE FOR | | | MAINTENANCE AND SERVICE AS PER 1997 SMC | | | 304.2.1 AND 304.2.3. | | | | | | REVIEW DONE UNDER MASTER 01011195. |
|
|
|