Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-02-22 Cont ID  
Sent By pkrauss Date 2001-02-22 Time 13:00 Rev Time 0.45
Received By pkrauss Date 2001-02-22 Time 13:00 Sent To  
Notes
2001-02-22 00:00:00PROVISO:DUCT SMOKE DETECTORS MUST BE
 TESTED TO SHOW COMPLIANCE WITH NFPA
 90A-12, 4.4.4.3, FAN SHUT DOWN WITH
 NOTIFICATION TO NORMALLY OCCUPIED AREAS
 BY ALARM/STROBE.
  
 AHU-5 IN THE COPY/FILE WORKROOM (ROOM
 234), SHALL HAVE ACCESS/CLEARANCE FOR
 MAINTENANCE AND SERVICE AS PER 1997 SMC
 304.2.1 AND 304.2.3.
  
 REVIEW DONE UNDER MASTER 01011195.