Plan Review Details - Permit 01011170
Plan Review Stops For Permit 01011170
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-02-06 Cont ID  
Sent By jwitmer Date 2001-02-06 Time 07:54 Rev Time 0.75
Received By jwitmer Date 2001-02-06 Time 07:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-26 Cont ID  
Sent By dpalmer Date 2001-02-26 Time 12:42 Rev Time 0.00
Received By dpalmer Date 2001-02-26 Time 12:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-02-07 Cont ID  
Sent By dpalmer Date 2001-02-02 Time 15:21 Rev Time 0.00
Received By dpalmer Date 2001-02-02 Time 15:21 Sent To  
Notes
2001-02-02 00:00:00******************UNSAT ****************
  
 1)NOTE: PLEASE NOTE, COVER SHEET SHOWS
 E- SHEETS AND NONE WERE SUBMITTED??
 PLEASE SUBMIT.
 SHEET A2.01 DOES NOT HAVE ENOUGH
 ELECTRICAL DETAIL FOR REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-02-28 Cont ID  
Sent By lsmith Date 2001-02-28 Time 09:37 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-03-27 Cont ID  
Sent By mcarsill Date 2001-03-27 Time 16:27 Rev Time 0.00
Received By mcarsill Date 2001-03-27 Time 16:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-03-09 Cont ID  
Sent By mcarsill Date 2001-03-09 Time 13:34 Rev Time 0.00
Received By mcarsill Date 2001-03-09 Time 13:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-02-20 Cont ID  
Sent By mcarsill Date 2001-02-20 Time 14:57 Rev Time 0.00
Received By mcarsill Date 2001-02-20 Time 14:57 Sent To  
Notes
2001-02-20 00:00:001) WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ 1985 EDITION INSTEAD OF
 OF 1997 EDITION.
 2) NO FIRE SPRINKLER SYSTEM DRAWINGS
 PROVIDED WITH PLANS.
 3) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION WITH PLANS.
 4) PLEASE PROVIDE PERMIT AND SHOP
 DRAWINGS FOR FIRE ALARM REMODEL.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-04-10 Cont ID  
Sent By pkrauss Date 2001-04-10 Time 13:52 Rev Time 0.40
Received By pkrauss Date 2001-04-10 Time 12:57 Sent To  
Notes
2001-04-10 00:00:00****************HOLD********************
  
 ON DWG. M-1 NOTE 18., INDICATES HP-7
 WILL BE PUT INTO STORAGE BECAUSE THIS
 UNIT IS A VERTICLE UNIT AND SHOULD BE A
 HORIZONTAL UNIT - ENGINEER FAILED TO
 ASSIGN A UNIT SUPPLYING THIS AREA.
 SPOKE WITH ED (CATALFUMO) WILL GET A
 LETTER FROM ENGINEER TO CORRECT PROBLEM.
 4/10/01PHK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-02-13 Cont ID  
Sent By ndenmark Date 2001-02-13 Time 13:37 Rev Time 0.33
Received By ndenmark Date 2001-02-13 Time 13:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-04-25 Cont ID  
Sent By jleech Date 2001-04-25 Time 19:01 Rev Time 0.50
Received By jleech Date 2001-04-25 Time 19:01 Sent To  
Notes
2001-04-25 00:00:00DENIED;
  
 1.SHOW ICE MACHINE SPECIFCATIONS.
  
 2.PAN DRAIN SHALL BE 1". NOT SHOWN ON
 DRAWINGS.
  
 3.PRESSURE RELIEF VALVETO DISCHARGE TO
 DRAINAGE SYSTEM WERE IT CAN BE READLY
 OBSERVED BY BUILDING OCCUPENTS.
  
 4. ADD NOTE TO PLANS WATER HEATER SHALL
 BE READLY ACCESSIBLE.
  
 PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-04-16 Cont ID  
Sent By jleech Date 2001-04-16 Time 06:59 Rev Time 1.50
Received By jleech Date 2001-04-16 Time 06:59 Sent To  
Notes
2001-04-16 00:00:00DENIED;
  
 1.TRAP PRIMER REQUIRED FOR FLOOR DRAIN.
  
 2.PAN DRAIN SHALL BE 1" 507.8.2
  
 3.PRESSURE RELIEF VALVE TO DISCHARGE TO
 DRAINAGE SYSTEM WERE IT CAN BE READLY
 OBSERVED BY THE BUILDING OCCUPANTS
 SPC 507.8.4.
  
 4.WATER HEATER SHALL BE READLY ACCESIBLE
 501.7.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-02-04 Cont ID  
Sent By pschmitz Date 2001-02-04 Time 06:01 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-02-04 00:00:00PLUMBING PLAN REVIEWPROVISO
 (1) SHT A-802

Review Stop Z ZONING
Rev No 1 Status N Date 2001-02-28 Cont ID  
Sent By lsmith Date 2001-02-28 Time 09:37 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***