Plan Review Details - Permit 01011146
Plan Review Stops For Permit 01011146
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-01-30 Cont ID  
Sent By hpiskura Date 2001-01-30 Time 08:35 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-01 Cont ID  
Sent By dpalmer Date 2001-03-01 Time 19:31 Rev Time 0.00
Received By dpalmer Date 2001-03-01 Time 19:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-02-01 Cont ID  
Sent By dpalmer Date 2001-02-01 Time 17:26 Rev Time 0.00
Received By dpalmer Date 2001-02-01 Time 17:26 Sent To  
Notes
2001-02-01 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 FOR SERVICE.215-5
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IFTHERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-03-13 Cont ID  
Sent By hpiskura Date 2001-03-13 Time 13:01 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-02-08 Cont ID  
Sent By mcarsill Date 2001-02-08 Time 08:32 Rev Time 0.00
Received By mcarsill Date 2001-02-08 Time 08:32 Sent To  
Notes
2001-02-08 00:00:001) DOOR LEADING INTO WAITING ROOM 001
 TO BE AT 45 MINUTE FIRE RATED.
 CLOSING DEVICES REQUIRED ON ALL RATED
 FIRE DOORS.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2001-06-07 Cont ID  
Sent By pkrauss Date 2001-06-07 Time 09:36 Rev Time 0.30
Received By pkrauss Date 2001-06-07 Time 09:20 Sent To  
Notes
2001-06-07 00:00:00********************DENIED**************
  
  
 DID RATING OF WALL CHANGE...IF SO, WAS
 IT SUBMITTED TO BUILDING PLAN REVIEW.
  
 DAMPER MAY NOT BE REMOVED UNLESS IT
 MEETS THE REQUIREMENTS OF 1997 SMC
 610.1.3 ITEM 3.
  
 1.DUCT SHALL NOT EXCEED 100 SQ INCHS.
 2.SHALL BE OF 0.0217" MIN. STEEL.
 3.DUCT SHALL CONTINUE W/NO OPENINGS
 FOR 5' FROM THE RATED WALL &
 4.DUCT SHALL BE INSTALLED ABOVE
 CEILING.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-09 Cont ID  
Sent By pkrauss Date 2001-03-09 Time 13:36 Rev Time 0.25
Received By pkrauss Date 2001-03-09 Time 13:36 Sent To  
Notes
2001-03-09 00:00:00PROVISO:AS PER NANCY'S REVIEW 2/6/01
  
 ALL FOUR SECTIONS OF 1997 610.1.3 (3)
 INCLUDING 100 SQ. IN., ABOVE CEILING,
 MINIMUM 26 GA. AND EXTEND FOR 5 FT. ON
 EACH SIDE OF THE RATED WALL BEFORE ANY
 OPENINGS IN THE DUCT.
  
 APPROVED AS PER NCD 2/6/01.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-02-06 Cont ID  
Sent By ndenmark Date 2001-02-06 Time 14:48 Rev Time 0.33
Received By ndenmark Date 2001-02-06 Time 14:48 Sent To  
Notes
2001-02-06 00:00:00PROVISO:
 ALL FOUR SECTIONS OF 1997 SMC 610.1.3
 (3) INCLUDING MAXIMUM 100SQ. IN., ABOVE
 CEILING, MIN. 26 GA. AND EXTEND FOR 5
 FT. ON EACH SIDE OF THE RATED WALL
 BEFORE ANY OPENINGS IN THE DUCT.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-03-10 Cont ID  
Sent By jleech Date 2001-03-10 Time 06:23 Rev Time 0.75
Received By jleech Date 2001-03-10 Time 06:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-02-04 Cont ID  
Sent By pschmitz Date 2001-02-04 Time 07:46 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-02-04 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) SHT A-1
 PLUMBING PLAN REVIEWDENIED
 CODE REFERENCES SPC 94,FACBC 97
 (1A) SHT.A-1 BREAK RM.#010 SEC.4.13.6
 MANEUVERING CLEARANCE AT DOORS.
 SEC. 4.24.5 DOOR SWING INTO CLEAR FLOOR
 SPACE OF SINK,
 (B) BREAK RM. SINK SEC. 4.24 MAX HIGTH
 34" FF, CLEAR FLR SPACE 30"X48" KNEE
 CLEARANCE 19".
 (2A) SHT M-1 SEC.303,LIST MATERIALS,
 SPECIFICATIONS.
 (B) WATER PIPE RISER,AIR CHAMBERS TO BE
 READLY ACCESSIBLE,RECHARGEABLE,
 SEC 607.8.3
 (C) SANITARY RISER SEC 908.1 EACH
 FIXTURE TRAP SHALL HAVE A PROTECTING
 VENT. W/C & F/D, RM 005.
 (D) WATER HEATERS ABOVE CEILING,SHALL BE
 READLY ACCESSIBLE SEC 501.7, SHOW A
 DETAIL OF A WORKING PLATFORM WITH A
 FIXED SHIPS LADDER IN PLACE.
 END OF COMMENTS,CONTACT PAUL SCHMITZ
 561-659-8096 X 8233

Review Stop Z ZONING
Rev No 1 Status N Date 2001-03-13 Cont ID  
Sent By hpiskura Date 2001-03-13 Time 13:00 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***