| 2001-01-24 00:00:00 | 1) FIRE DEPARTMENT CONNECTION TO BE NO | | | MORE THAN 150 FEET FROM A FIRE HYDRANT. | | | 2) ENTIRE BUILDING IS TO BE COMPLETELY | | | FIRE SPRINKLER PROTECTED. THIS INCLUDES | | | ALL ELECTRICAL,MECHANICAL AND SERVICE | | | ROOMS. | | | 3) UNDEGROUND AND OVERHEAD FIRE | | | SPRINKLER PIPING TO BE PRESSURE TESTED | | | FOR TWO HOURS AT 200 PSI. | | | 4) FIRE SPRINKLER SYSTEM IS REQUIRED TO | | | BE SUPURVISED BY A LICENSED UL LISTED | | | CENTRAL STATION APPROVED BY THE FIRE | | | RESCUE DEPARTMENT. | | | 5) SPARE HEAD BOX AND WRENCH REQUIRED | | | PER NFPA 13. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|