Plan Review Details - Permit 01011057
Plan Review Stops For Permit 01011057
Review Stop FS  
Rev No 3 Status P Date 2001-05-25 Cont ID  
Sent By mcarsill Date 2001-05-25 Time 08:04 Rev Time 0.00
Received By mcarsill Date 2001-05-25 Time 08:04 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 2 Status P Date 2001-03-09 Cont ID  
Sent By mcarsill Date 2001-03-09 Time 13:50 Rev Time 0.00
Received By mcarsill Date 2001-03-09 Time 13:50 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 1 Status P Date 2001-01-24 Cont ID  
Sent By mcarsill Date 2001-01-24 Time 10:08 Rev Time 0.00
Received By mcarsill Date 2001-01-24 Time 10:08 Sent To  
Notes
2001-01-24 00:00:001) FIRE DEPARTMENT CONNECTION TO BE NO
 MORE THAN 150 FEET FROM A FIRE HYDRANT.
 2) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL ELECTRICAL,MECHANICAL AND SERVICE
 ROOMS.
 3) UNDEGROUND AND OVERHEAD FIRE
 SPRINKLER PIPING TO BE PRESSURE TESTED
 FOR TWO HOURS AT 200 PSI.
 4) FIRE SPRINKLER SYSTEM IS REQUIRED TO
 BE SUPURVISED BY A LICENSED UL LISTED
 CENTRAL STATION APPROVED BY THE FIRE
 RESCUE DEPARTMENT.
 5) SPARE HEAD BOX AND WRENCH REQUIRED
 PER NFPA 13.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910