Plan Review Details - Permit 01010696
Plan Review Stops For Permit 01010696
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-01-19 Cont ID  
Sent By hpiskura Date 2001-01-19 Time 13:17 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-01 Cont ID  
Sent By dpalmer Date 2001-03-01 Time 17:32 Rev Time 0.00
Received By dpalmer Date 2001-03-01 Time 17:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-25 Cont ID  
Sent By dpalmer Date 2001-01-25 Time 22:33 Rev Time 0.00
Received By dpalmer Date 2001-01-25 Time 22:33 Sent To  
Notes
2001-01-25 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`SON PLANS, PLEASE CORRELATE WITH
 PANEL SCHEDULES.
  
 2)NOTE: NOT ENOUGH INFORMATION ON PANEL
 SCHEDULES.
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE. ROOF TOP? EXISTING?
  
 4)NOTE: PLEASE NOTE MEANS OF DISCONNECT
 ON LOAD SIDE OF TRANSFORMER REQ`D FOR
 SEPARATELY DERIVED SYSTEM.
  
 5)NOTE: PLEASE SHOW GROUNDING FOR
 TRANSFORMER AND ENTIRE ELECTRICAL
 SERVICE.
 GENERATOR ETC.
  
 6)NOTE: PLEASE SHOW VOLTAGES ON ALL NEW
 EQUIPMENT AND PANELS WITH NEW ITEMS.
 PLEASE SEE F.A.C. SECTION 553-79-6A
 ALL WORK CONTAINING 277/480 ON SERVICES
 ARE TO BE SIGNED AND SEALED BY A "PE"
  
 7)NOTE: PANEL SCSCHEDULES ARE TO BE
 MOREDETAILED.
  
  
 8)NOTE: SUBMIT LOAD CALCULATIONS, NOTE
 ALL CONTINUOUS LOADS ARE TO BE SHOWN AT
 125%. (LIGHTING) LARGEST MOTOR) ECT.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-01-23 Cont ID  
Sent By mcarsill Date 2001-01-23 Time 08:32 Rev Time 0.00
Received By mcarsill Date 2001-01-23 Time 08:32 Sent To  
Notes
2001-01-23 00:00:001) INTERIOR FINISH ON WALLS AND CEILING
 TO BE AT LEAST CLASS C.
 2) PROVIDE MORE DETAILS ON GENERATOR.
 3) PROVIDE PERMIT AND SHOP DRAWINGS FOR
 FIRE ALARM SYSTEM REMODEL.
 4) PROVIDE PERMIT AND SHOP DRAWINGS FOR
 FIRE SPRINKLER REMODEL.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-02-22 Cont ID  
Sent By pkrauss Date 2001-02-22 Time 16:35 Rev Time 0.40
Received By pkrauss Date 2001-02-22 Time 16:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-02-06 Cont ID  
Sent By ndenmark Date 2001-02-06 Time 11:25 Rev Time 0.25
Received By ndenmark Date 2001-02-06 Time 11:25 Sent To  
Notes
2001-02-06 00:00:00**************DENIED********************
 MECHANICAL APPLICATION APPLIED FOR WITH
 THIS PERMIT AND THERE IS NO MECHANICAL
 SHOWN ON THE PLAN TO REVIEW. PROVIDE
 INFORMATION ON MECHANICAL TO BE DONE
 WITH THIS PROJECT.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-03-03 Cont ID  
Sent By jleech Date 2001-03-03 Time 13:53 Rev Time 0.75
Received By jleech Date 2001-03-03 Time 13:53 Sent To  
Notes
2001-03-03 00:00:00PROVISO;
  
 U.L. FIRE SAFING ASSEMBLY REQUIRED FOR
 PVC PIPES PENETRATING RATED WALLS AND
 CEILINGS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-30 Cont ID  
Sent By jleech Date 2001-01-30 Time 13:01 Rev Time 1.00
Received By jleech Date 2001-01-30 Time 13:01 Sent To  
Notes
2001-01-30 00:00:00DENIED;
  
 1.HANDICAP TOILET STALL SHALL COMPLY
 WITH DEPARTMENT OF COMMUNITY AFFAIRS
 RULE 9B-7.00042 FLA. ADMIN. CODE.
 CLEAR FLOOR SPACE FOR TOILET IS 59"X
 60" TO EDGE OF LAVITORY.
  
 2.DRINKING FOUNTAIN TO COMPLY WITH FACBC
 4.1.3(10) AND 4.15. PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 3.SHOW SQ. FOOTAGE OF OFFICE AND
 CALCULATE MINIMUM FIXTURES REQUIRED
 PER SPC TABLE 407.
  
 4.PLUMBING RISER.
 A.FLOOR DRAINS ARE UNVENTED.
 B.URINAL CAN FLUSH PAST A LAV.
  
 5.LIST U.L. FIRE SAFING ASSEMBIES TO BE
 USED FOR ANY PENETRATIONS OF FIRE WALL
 OR CIELINGS.
  
 6.KITCHEN SINK SHALL COMPLY WITH FACBC
 4.24.1 THRU 4.24.7.
  
 7.SHOW WATER RISER DIAGRAM.
  
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT 8377