Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-01-19 Cont ID  
Sent By ndenmark Date 2001-01-19 Time 13:56 Rev Time 0.25
Received By ndenmark Date 2001-01-19 Time 13:56 Sent To  
Notes
2001-01-19 00:00:00PROVISO:
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR W/
 NOTIFICATION BY HORN AND STROBE REQUIRED
 PER 1996 NFPA 90A 4-4.4