Plan Review Details - Permit 01010669
Plan Review Stops For Permit 01010669
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-01-31 Cont ID  
Sent By jwitmer Date 2001-01-31 Time 14:48 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-29 Cont ID  
Sent By jwitmer Date 2001-01-29 Time 15:20 Rev Time 4.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-29 00:00:002415 MEDINA WAY
 O/B WALSH, THOMAS
 1)- SHEET A-4 DETAIL #6 NOTE STUCCO OVER
 WIRE LATH, SBC 103.7.2.1 A 6" FULL CLEAR
 INSPECTION SPACE OF THE FOUNDATION
 SIDEWALL IS REQUIRED BETWEEN WOOD SIDING
 STUCCO WITH WIRE LATH DOWN TO THE TOP OF
 THE SOD, MULCH OR SOIL.
 2)- SBC 104.2.2- ADDITIONAL INFORMATION
 REQUIRED:
 A)- SHEET A-3 DETAIL #5 SHOWS A DETAIL
 OF THE 6"X6" POST ANCHORED TO THE
 FOUNDATION, THIS DETAIL WILL MEAN THAT
 THE POST WILL NOT SIT ON THE STEM WALL
 BUT WILL BE BURIED IN THE SOIL APPR. 8"?
 B)- SHEET A-4 DETAIL #6, WILL REQUIRE
 OVERFLOW SCUPPERS ON THE FLAT DECK WITH
 PARAPET WALLS, (SBC 1517.6.4.3).
 C)- SBC 1804.6.2.2- CRAWL SPACE
 REQUIRES ACCESS OPENINGS.
 D)- DISCREPANCY, SHEEET A-1 VS A-5.
 THE SHEET A-5 SHOWS DETAILS #2/4 WITH
 NOTE BEDROOM #3 EXISTING WHILE SHEET A-1
 PROPOSED 2 STORY ADDITION?
 3)- SBC 1707.5, PRODUCT APPROVAL IS RE-
 QUIRED FOR ROOF TILE, AND FOR FLAT ROOFS
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX.8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-01-23 Cont ID  
Sent By dpalmer Date 2001-01-23 Time 10:28 Rev Time 0.00
Received By dpalmer Date 2001-01-23 Time 10:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-01-20 Cont ID  
Sent By jleech Date 2001-01-20 Time 13:49 Rev Time 0.25
Received By jleech Date 2001-01-20 Time 13:49 Sent To  
Notes
2001-01-20 00:00:00ADDITION TO EXISTING HOUSE TWO DROPS.

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-01-20 Cont ID  
Sent By jleech Date 2001-01-20 Time 13:50 Rev Time 0.01
Received By jleech Date 2001-01-20 Time 13:50 Sent To  
Notes
2001-01-20 00:00:00NO PLUMBING SHOWN ON DRAWINGS.

Review Stop Z ZONING
Rev No 2 Status P Date 2001-01-31 Cont ID  
Sent By jwitmer Date 2001-01-31 Time 14:53 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-31 00:00:00ZONING: PER S. GRAHAM

Review Stop Z ZONING
Rev No 1 Status F Date 2001-01-24 Cont ID  
Sent By sgraham Date 2001-01-24 Time 16:27 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-01-24 00:00:00NEED HISTORIC APPROVAL