Plan Review Details - Permit 01010661
Plan Review Stops For Permit 01010661
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-05-11 Cont ID  
Sent By dpalmer Date 2001-05-11 Time 08:44 Rev Time 0.00
Received By dpalmer Date 2001-05-11 Time 08:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-25 Cont ID  
Sent By dpalmer Date 2001-01-25 Time 14:34 Rev Time 0.00
Received By dpalmer Date 2001-01-25 Time 14:34 Sent To  
Notes
2001-01-25 00:00:00************* UNSAT *******************
 1)NOTE: PLEASE NOTE PER STATE STATUES
 PLANS ARE TO BE SIGNED AND SEALED PER
 481.221/471.025.
  
 2)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 4)NOTE: PLEASE NOTE THAT NO ELECTRICAL
 RISER DIAGRAM WAS SUBMITTED. NO PANEL
 SCHEDULES. ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVEIW.
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-01-20 Cont ID  
Sent By jleech Date 2001-01-20 Time 12:01 Rev Time 0.25
Received By jleech Date 2001-01-20 Time 12:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-10-12 Cont ID  
Sent By kstevens Date 2002-10-12 Time 07:46 Rev Time 0.00
Received By kstevens Date 2002-10-12 Time 07:46 Sent To  
Notes
2002-10-12 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-05-02 Cont ID  
Sent By kstevens Date 2001-05-02 Time 09:56 Rev Time 0.25
Received By kstevens Date 2001-05-02 Time 09:56 Sent To  
Notes
2001-05-02 00:00:00REVIEW NOTES.PASSED
  
 RESUBMITTED WITH NO CHANGES TO ORIGINAL
 PLAN REVIEW OF 1-20-01

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-01-20 Cont ID  
Sent By jleech Date 2001-01-20 Time 12:01 Rev Time 0.25
Received By jleech Date 2001-01-20 Time 12:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-12-05 Cont ID  
Sent By rmcdouga Date 2001-12-05 Time 13:13 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-06-04 Cont ID  
Sent By rmcdouga Date 2001-06-04 Time 11:56 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-06-04 00:00:00*************BUILDING UNSAT*************
  
 1) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALMBEACH CO.,THE PERMIT PLANS STAMPED
 BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
 SBC 104.2.2
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE DESIGN CERTIFICATION FORM
 CONTAINS INCORRECT DATA. THE ACCEPTED
 DESIGN STANDARDS FOR THE CITY OF WEST
 PALM BEACH ARE ASCE 7-95 OR 97 STANDARD
 BUILDING CODE (CHAPTER 16). THE
 IMPORTANCE FACTOR FOR 1997 SBC IS 1.0 &
 THE WIND SPEED IS 110 MPH. PLEASE
 REVIEWAND CORRECT THE FORM.
  
 4) THE WINDOW AND DOOR DESIGN PRESSURE
 SCHEDULE WAS CALCULATED USING ASCE
 7-93,THIS IS NOT AN ACCEPTED DESIGN
 STANDARD OF THE CITY OF WPB. PLEASE USE
 EITHER
 97 SBC SECTION 1606 OR ASCE 7-95 FOR
 DESIGN CALCULATIONS.
  
 5) SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) FOR BENCHMARK & LEGEND
 EXTERIOR DOOR MUST HAVE THE ORIGIONAL
 WET SIGNATURE (NOT A COPY), EMBOSSED
 SEAL AND DATE OF THE ENGINEER CERTIFYING
 THE PRODUCT AND THE WET SIGNATURE,
 EMBOSSED SEAL AND DATE OF THE DESIGNER
 OF RECORD OF THE STRUCTURE. ALSO THE JOB
 /SITE LOCATION IS REQUIRED.(SEE CITY OF
 WPB FORM ATTACHED.)
  
 6) PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLIES PER 1997 SBC 2406.2.
 DETAILED SHOP DRAWINGS, SPECIFICATIONS &
 RATIONAL ANALYSIS PREPARED BY ENGINEER
 EXPERIENCED IN THIS WORK IS REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-02-14 Cont ID  
Sent By rmcdouga Date 2001-02-14 Time 10:56 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-02-14 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE PLANS THAT HAVE RAISED SEAL
 AND ORIGINAL SIGNATURE OF DESIGNER OF
 RECORD.
  
 4) PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLIES PER 1997 SBC 2406.2.
  
 5) SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND OF THE
 DESIGNPROFESSIONAL OF RECORD.
  
 6) PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 - ARCH TOP FIXED GLASS WINDOWS
  
 7) PROVIDE SAFETY GLASS PER 1997 SBC SEC
 2405.2.1 IN BATHROOM BETWEEN BEDROOMS
 #2 & #3 AND FIXED GLASS WINDOW IN LIVING
 ROOM THAT IS WITHIN 2' RADIUS OF DOOR.
  
 8) DESIGN CERTIFICATION FORM IS
 INNCORRECT. VALUES FOR BASIC VELOCITY
 PRESSURE AND IMPORTANCE FACTOR APPEAR TO
 BE FROM ASCE 7-88. THE CITY OF WPB
 REQUIRES STRUCTURAL DESIGN TO BE BASED
 ON 97 SBC SEC. 1606 OR ASCE 7-95. PLEASE
 CHECK YOUR CALCULATIONS AND CORRECT
 CERTIFICATION FORM.
  
 9) PROVIDE POSITIVE AND NEGATIVE
 WIND PRESSURES FOR ALL EXTERIOR OPENINGS
 ON THE PLANS.
  
 10)UPLIFT AND REACTION VALUES FOR GIRDER
 AND TRUSSES IN THE KITCHEN AREA ON SHEET
 6 ARE ILLEGIBLE. PLEASE CLARIFY.
  
 11)UPLIFT AND REACTION VALUES ARE NOT
 INDICATED FOR ALL OF THE TRUSSES AND
 GIRDERS ON SHEET 6, PLEASE PROVIDE THEM
 AND CLARIFY WHICH VALUES APPLY TO WHICH
 TRUSSES.
  
 12)PROVIDE STRUCTURAL DETAILS INDICATING
 METHOD OF SUPPORT FOR ROOF ASSEMBLY AT
 RIGHT REAR CORNER OF STRUCTURE. SEE
 SHEET 6.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-01-19 Cont ID  
Sent By sgraham Date 2001-01-19 Time 07:40 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***