| 2001-02-05 00:00:00 | DENIED |
| | |
| | 1)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) SITE SPECIFIC ENGINEERING (PRODUCT |
| | APPROVAL) REQUIRES THE WET SIGNATURE, |
| | DATE AND EMBOSSED SEAL OF THE ENGINEER |
| | CERTIFYING THE PRODUCT AND OF THE |
| | DESIGN PROFESSIONAL OF RECORD. |
| | |
| | 4) FOUNDATION FOR PRIVACY WALL AT REAR |
| | OF STRUCTURE AS SHOWN IN DETAIL 1 ON |
| | SHEET A-8 WILL ENCROACH ON ADJACENT |
| | LOT AT ZERO LOT LINE. PLEASE REVISE. |
| | |
| | 5) ONE HOUR RATED GLASS BLOCK IS |
| | REQUIRED AT ZERO LOT LINE. 2112.1.2 OF |
| | 1997 SBC. |
| | |
| | 6) THE ONE (1) EGRESS DOOR REQUIRED IS |
| | TO BE OF THE SIDE SWINGING TYPE AND |
| | PROVIDE NOT LESS THAN A 32" WIDE CLEAR |
| | OPENING. 1997 SBC 1012.1 |
| | |
| | 7) EXTERIOR WALL LOCATIONS ON SITE PLAN |
| | S-1 DO NOT CORRESPOND WITH THE OTHER |
| | DRAWINGS. PLEASE CORRECT. |
| | |
| | 8) THE MEAN ROOF HEIGHT LISTED ON THE |
| | DESIGN COMPLIANCE FORM AS 15' IS NOT |
| | CORRECT,THE ACTUAL MEAN ROOF HEIGHT IS |
| | APPROXIMATELY 22'. THIS WILL CHANGE THE |
| | BASIC VELOCITY PRESSURE. PLEASE CORRECT. |
| | |
| | 9) PROVIDE 2 CURRENT COMPLETE COPIES OF |
| | SBCCI OR METRO DADE PRODUCT APPROVALS |
| | FOR: |
| | - ARCHED FIXED GLASS WINDOWS |
| | - SLIDING GLASS DOORS |
| | |
| | 10)PROVIDE MANUFACTURER'S SPECIFICATIONS |
| | AND UL LISTNG FOR BBQ. |
| | |
| | 11)PROVIDE REVISED INSTALLATION SCHEDULE |
| | AND KEY PLAN THAT CORRESPONDS WITH PLANS |
| | |
| | 12)PROVIDE ENGINEERING FOR BUTT GLASS |
| | ASSEMBLY PER 97 SBC 2406.2. |
| | |
| | |
| | IF YOU HAVE QUESTIONS CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |