Plan Review Details - Permit 01010657
Plan Review Stops For Permit 01010657
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-11 Cont ID  
Sent By dpalmer Date 2001-03-11 Time 14:45 Rev Time 0.00
Received By dpalmer Date 2001-03-11 Time 14:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-25 Cont ID  
Sent By dpalmer Date 2001-01-25 Time 14:56 Rev Time 0.00
Received By dpalmer Date 2001-01-25 Time 14:56 Sent To  
Notes
2001-01-25 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 4) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF
 DISCONNECTAND PANEL(S). EQUIPMENT
 GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 6)NOTE: PLEASE NOTE THAT PLANS SHOW TWO
 PANELS AND RISER DIAGRAM SHOWS ONLY
 ONE?. PLEASE CLARIFY.
  
 8)NOTE: PLEASE NOTE MISSING OUTLETS FOR
 210-52H.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS PLEAS
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-01-20 Cont ID  
Sent By jleech Date 2001-01-20 Time 11:37 Rev Time 0.25
Received By jleech Date 2001-01-20 Time 11:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-01-20 Cont ID  
Sent By jleech Date 2001-01-20 Time 11:38 Rev Time 0.25
Received By jleech Date 2001-01-20 Time 11:38 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-03-30 Cont ID  
Sent By rmcdouga Date 2001-03-30 Time 09:26 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-03-30 00:00:00************BUILDING PROVISO************
  
 1) SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND OF THE DESIGN
 PROFESSIONAL OF RECORD. THE FORM THAT
 WAS SUBMITTED FOR BENCHMARK/LEGEND DOORS
 IS NOT ACCEPTABLE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-02-05 Cont ID  
Sent By rmcdouga Date 2001-02-05 Time 14:11 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-02-05 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND OF THE
 DESIGN PROFESSIONAL OF RECORD.
  
 4) FOUNDATION FOR PRIVACY WALL AT REAR
 OF STRUCTURE AS SHOWN IN DETAIL 1 ON
 SHEET A-8 WILL ENCROACH ON ADJACENT
 LOT AT ZERO LOT LINE. PLEASE REVISE.
  
 5) ONE HOUR RATED GLASS BLOCK IS
 REQUIRED AT ZERO LOT LINE. 2112.1.2 OF
 1997 SBC.
  
 6) THE ONE (1) EGRESS DOOR REQUIRED IS
 TO BE OF THE SIDE SWINGING TYPE AND
 PROVIDE NOT LESS THAN A 32" WIDE CLEAR
 OPENING. 1997 SBC 1012.1
  
 7) EXTERIOR WALL LOCATIONS ON SITE PLAN
 S-1 DO NOT CORRESPOND WITH THE OTHER
 DRAWINGS. PLEASE CORRECT.
  
 8) THE MEAN ROOF HEIGHT LISTED ON THE
 DESIGN COMPLIANCE FORM AS 15' IS NOT
 CORRECT,THE ACTUAL MEAN ROOF HEIGHT IS
 APPROXIMATELY 22'. THIS WILL CHANGE THE
 BASIC VELOCITY PRESSURE. PLEASE CORRECT.
  
 9) PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 - ARCHED FIXED GLASS WINDOWS
 - SLIDING GLASS DOORS
  
 10)PROVIDE MANUFACTURER'S SPECIFICATIONS
 AND UL LISTNG FOR BBQ.
  
 11)PROVIDE REVISED INSTALLATION SCHEDULE
 AND KEY PLAN THAT CORRESPONDS WITH PLANS
  
 12)PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLY PER 97 SBC 2406.2.
  
  
 IF YOU HAVE QUESTIONS CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 2 Status P Date 2001-04-02 Cont ID  
Sent By sgraham Date 2001-03-30 Time 10:57 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-01-19 Cont ID  
Sent By sgraham Date 2001-01-19 Time 07:42 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***