Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-11 Cont ID  
Sent By dpalmer Date 2001-03-11 Time 14:38 Rev Time 0.00
Received By dpalmer Date 2001-03-11 Time 14:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-23 Cont ID  
Sent By dpalmer Date 2001-01-23 Time 08:08 Rev Time 0.00
Received By dpalmer Date 2001-01-23 Time 08:08 Sent To  
Notes
2001-01-23 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
  
  
  
  
  
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 4) PLEASE CORRELATE OCP WITH WIRE SIZES
 ON PANEL SCHEDULE(S). ART 240
  
 5) PLEASE CORRELATE OCP WITH WIRE SIZES
 ON PANEL SCHEDULE(S). ART 240
  
 6) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 7) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 8)PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 9)NOTE: PLEASE NOTE THAT ON SHEET A-8
 YOU SHOW METER WITH NO MAIN DISCONNECT
 AND ON RISER DIAGRAM YOU SHOW MAIN DISC-
 ONNECT NEXT TO METER. PLEASE SHOW ON A-8
 IF THIS IS THE CASE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATAION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-01-20 Cont ID  
Sent By jleech Date 2001-01-20 Time 10:38 Rev Time 0.25
Received By jleech Date 2001-01-20 Time 10:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-01 Cont ID  
Sent By kstevens Date 2001-06-01 Time 08:49 Rev Time 0.33
Received By kstevens Date 2001-06-01 Time 08:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-01-20 Cont ID  
Sent By jleech Date 2001-01-20 Time 10:39 Rev Time 0.25
Received By jleech Date 2001-01-20 Time 10:38 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-04-10 Cont ID  
Sent By rmcdouga Date 2001-04-10 Time 14:06 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-03-30 Cont ID  
Sent By rmcdouga Date 2001-03-30 Time 09:34 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-04-02 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SITE SPECIFIC ENGINEERING FOR BENCH-
 MARK AND LEGEND DOORS ARE NOT ACCEPTABLE
 WITHOUT ORIGINAL WET SIGNATURE, DATE AND
 EMBOSSED SEAL OF THE ENGINEER CERTIFYING
 THE DOORS. PLEASE CORRECT.
  
 4) EGRESS WINDOW IS REQUIRED IN DEN,
 WHICH COULD BE USED AS A SLEEPING ROOM.
 97 SBC SEC. 1005.4
  
 5) PLEASE RECHECK LEFT ELEVATION FOR
 COMPLIANCE WITH TABLE 600 AS IT STILL
 APPEARS TO BE IN VIOLATION AS INDICATED
 ON THE FIRST CHECK LIST.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-02-01 Cont ID  
Sent By rmcdouga Date 2001-02-01 Time 13:26 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-02-01 00:00:00DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALMBEACH CO.,THE PERMIT PLANS STAMPED
 BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)THE DESIGN CERTIFICATION FORMS
 INCORRECTLY LIST THE MEAN ROOF HEIGHT
 AS 15 FT. THE ACTUAL MEAN ROOF IS CLOSE
 TO 18 FT. THIS CHANGE WILL INCREASE THE
 BASIC VELOCITY PRESSURE. PLEASE MAKE
 ALLNECESSARY CORRECTIONS.
  
 4) A COPY OF THE SOIL TEST WITH THE
 WET SIGNATURE, DATE AND EMBOSSED SEAL
 OFTHE ENGINEER IS REQUIRED.
  
 5) PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 - STRUCTURAL WINDOW MULLIONS
 - ROOF COVERING MATERIALS
  
 6)THE SITE SPECIFIC ENGINEERING THAT
 WAS SUBMITTED FOR THE EXTERIOR DOORS IS
 REQUIRED TO HAVE THE WET SIGNATURE,
 DATEAND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND OF THE
 DESIGNPROFESSIONAL OF RECORD.
  
 7) NO FOUNDATION FOR WALL AND FENCE AT
 FRONT OF STRUCTURE IS INDICATED ON
 FOUNDATION PLAN SHEET A-1. PLEASE
 CLARIFY.
  
 8) PROVIDE MANUFACTURER'S
 SPECIFICATIONSAND UL LISTING FOR BBQ.
 97 SBC 2808.
  
 9) PROVIDE ENGINEERING FOR BUTT GLASS
 PER 97 SBC 2406.2.
  
 10)PROVIDE EGRESS WINDOW PER 1005.4 OF
 97 SBC FOR DEN WHICH CAN BE USED AS A
 SLEEPING ROOM.
  
 11)SHEET A-6 REFERENCES DETAIL 18 ON
 A-10 ; THERE IS NO DETAIL 18 ON SHEET
 A-10. PLEASE CLARIFY.
  
 12)NO UPLIFT IS GIVEN FOR DETAIL 17/
 10AON SHEET A-7. NO HEADER OR GIRDER IS
 SHOWN AND NO CONNECTION SPECIFIED AT
 MASTER BED ROOM WALL AT REAR OF
 STRUCTURE WHERE TRUSSES CANTILEVER.
 PLEASE CLARIFY.
  
 13)WINDOWS IN GARAGE WALL FACING NORTH
 PROPERTY LINE EXCEED THE PERCENT OF WALL
 OPENINGS ALLOWED BY TABLE 600 OF 97 SBC.
 PLEASE RECHECK YOUR CALCULATIONS AND
 MAKE NECESSARY REVISIONS.
  
  
 IF YOU HAVE QUESTIONS CALL.
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-02-01 Cont ID  
Sent By rmcdouga Date 2001-02-01 Time 16:49 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-02-01 00:00:00OK PER SHIRLEY GRAHAM 1-19-00 RM 2-1-01


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved