Plan Review Details - Permit 01010653
Plan Review Stops For Permit 01010653
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-26 Cont ID  
Sent By dpalmer Date 2001-03-26 Time 22:00 Rev Time 0.00
Received By dpalmer Date 2001-03-26 Time 22:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-25 Cont ID  
Sent By dpalmer Date 2001-01-25 Time 16:42 Rev Time 0.00
Received By dpalmer Date 2001-01-25 Time 16:40 Sent To  
Notes
2001-01-25 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 4) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 5)NOTE: PLEASE NOTE THE PLANS SHOW TWO
 PANELS IN GARAGE. RISER DIAGRAM SHOWS
 ONLY ONE PANEL? PLEASE CLARIFY.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS P
 LEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-01-20 Cont ID  
Sent By jleech Date 2001-01-20 Time 10:59 Rev Time 0.25
Received By jleech Date 2001-01-20 Time 10:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-09-13 Cont ID  
Sent By kstevens Date 2001-09-13 Time 19:18 Rev Time 0.33
Received By kstevens Date 2001-09-13 Time 19:18 Sent To  
Notes
2001-09-13 00:00:00DENIED
  
 WATER CLOSET - BIDET - AND SHOWER IN
 MASTER BATH ARE NOT VENTED. PLEASE
 SUBMIT A REVISION THAT REFLECTS THE
 INSTALLATION OF THE SANITARY PIPING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-01-20 Cont ID  
Sent By jleech Date 2001-01-20 Time 10:59 Rev Time 0.25
Received By jleech Date 2001-01-20 Time 10:59 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-04-04 Cont ID  
Sent By rmcdouga Date 2001-04-04 Time 12:24 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-04-04 00:00:00************BUILDING PROVISO************
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ARCHED TOP FIXED GLASS WINDOW
  
 2) SITE SPECIFIC ENGINEERING FOR THE
 BENCHMARK AND LEGEND DOORS THAT WERE
 SUBMITTED ARE NOT ACCEPTABLE. THE
 ENGINEER CERTIFYING THE DOORS TEST DATA
 AND THE ARCHITECT ARE BOTH REQUIRED TO
 WET SIGN, DATE AND SEAL THE FORM. PLEASE
 RESUBMIT FORMS WITH REQUIRED INFORMATION
 PRIOR TO INSTALLATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-02-09 Cont ID  
Sent By rmcdouga Date 2001-02-09 Time 15:50 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-02-09 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND OF THE
 DESIGNPROFESSIONAL OF RECORD. ( FRONT
 DOOR )
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ARCH TOP FIXED GLASS WINDOW
 - 6'X 8' GARAGE DOOR ( NOT INCLUDED ON
 PRODUCT APPROVAL THAT WAS SUBMITTED )
  
 5) PROVIDE POSITIVE AND NEGATIVE WIND
 PRESSURES FOR ALL EXTERIOR WINDOW AND
 DOOR OPENINGS.
  
 6) ONE HOUR FIRE RATED GLASS BLOCK IS
 REQUIRED AT ZERO LOT LINE.97SBC 2112.1.2
  
 7) PROVIDE MANUFACTURER'S
 SPECIFICATIONSAND UL LISTING FOR BBQ.
  
 8) THE MEAN ROOF HEIGHT LISTED ON THE
 DESIGN COMPLIANCE FORM AS 15' IS
 INCORRECT, THE ACTUAL MRH IS + 18'. THIS
 WILL CHANGE THE BASIC VELOCITY PRESSURE.
 PLEASE CORRECT.
  
 9) SAFETY GLAZING IS REQUIRED IN BATH
 ROOM #2. 97SBC 2405.2
  
 10)DETAIL A/A6 ON SHEET A-8 FOR PRIVACY
 WALL CAN NOT BE USED ON A ZERO LOT LINE,
 BECAUSE THE FOUNDATION WILL ENCROACH
 ONTO THE ADJOINING PROPERTY. PLEASE
 CORRECT.
  
 11)NOTE ON SHEET A-2 REFERS TO SITE PLAN
 FOR EXACT DIMENSIONS OF PRIVACY WALL;
 HOWEVER THE PRIVACY WALL IS NOT SHOWN ON
 THE SITE PLAN. PLEASE CLARIFY.
  
 12)THERE ARE (2) SHEETS OF THE PLANS
 IDENTIFIED AS A-8 AND (2) SHEETS AS
 A-9. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-01-19 Cont ID  
Sent By sgraham Date 2001-01-19 Time 08:16 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***