Plan Review Details - Permit 01010575
Plan Review Stops For Permit 01010575
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-02-06 Cont ID  
Sent By dpalmer Date 2001-02-06 Time 07:13 Rev Time 0.00
Received By dpalmer Date 2001-02-05 Time 19:06 Sent To  
Notes
2001-02-06 00:00:00****************** UNSAT ***************
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 2)NOTE: PLEASE NOTE MISSING OUTLET FOR
 KITCHEN COUNTERSPACE. PER 210-52-C-1
  
 3)NOTE: NO ELECTRICAL SUBMITTED FOR
 SERVICE ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION AND
 SUBMIT MORE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-02-05 Cont ID  
Sent By jleech Date 2001-02-05 Time 06:54 Rev Time 0.25
Received By jleech Date 2001-02-05 Time 06:54 Sent To  
Notes
2001-02-05 00:00:00NO A/C PLANS. A/C PLAN REQUIRED WITH A/C
 APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-02-05 Cont ID  
Sent By jleech Date 2001-02-05 Time 06:59 Rev Time 0.25
Received By jleech Date 2001-02-05 Time 06:59 Sent To  
Notes
2001-02-05 00:00:00NO PLUMBING; SHOW RISER DIAGRAM WITH
 PIPE SIZES.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-02-23 Cont ID  
Sent By rmcdouga Date 2001-02-23 Time 10:51 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-02-23 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FRENCH DOORS
 - SINGLE HUNG WINDOWS
 - GLASS BLOCK
 - OVERHEAD GARAGE DOORS
 - SLIDING GLASS DOORS
 - SIDE SWING DOOR WITH SIDELITES
 - ROOF COVERING
 - ARCHED FIXED GLASS
 4)PROVIDE (2) COPIES OF ALL ITEMS
 THAT ARE SUBMITTED ; ADDITIONAL COPIES
 OF THETWO PRODUCT APPROVALS THAT WERE
 SUBMITTED ARE REQUIRED.
  
 5) PROVIDE (2) COPIES OF ENERGY
 CALCULATIONS INCLUDING MANUAL "J" CALCS.
 PER 97 FLORIDA ENERGY CODE.
  
 6) PLAN SHEETS A-5, A-6 AND A-7 APPEAR
 TO BE MISSING,PLEASE CLARIFY.
  
 7) PROVIDE ROOF FRAMING PLAN WITH
 HURRICANE ANCHOR SCHEDULE. INDICATE
 LOCATION, DIRECTION AND MAGNITUDE OF
 LOADS TO BE RESISTED.
  
 8) PROVIDE DETAIL OF ATTIC VENTILATION.
  
 9) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANEL. THIS WILL
 NOT BE REQUIRED IF IMPACT GLAZING IS
 USED IN ALL OPENINGS.
  
 10)PROVIDE DESIGN CERTIFICATION CRITERIA
 ON PLANS OR ON FORM (SEE ATTACHED).
  
 11)INDICATE SPECIAL ROOF NAILING ZONES
 COMPLYING WITH FIGURE 2306.1 OF THE CITY
 AMENDMENTS.
  
 12)INDICATE ACTUAL MEAN ROOF HEIGHT ON
 PLANS.
  
 13)PROVIDE DETAIL OF ARCHED OPENINGS.
  
 14)PROVIDE DETAIL OF FOOTINGS INDICATING
 12" BELOW FINISH GRADE TO BOTTOM OF
 FOOTING, FINISH FLOOR 4" ABOVE F.G.,
 1 1/2" BLOCK RECESS (WATER STOP), ETC.
  
 15)PROVIDE DETAIL OF WINDOW AND DOOR
 BUCK CONNECTIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING