Plan Review Details - Permit 01010549
Plan Review Stops For Permit 01010549
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-02-22 Cont ID  
Sent By jwitmer Date 2001-02-22 Time 08:31 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-22 Cont ID  
Sent By jwitmer Date 2001-01-22 Time 17:15 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-22 00:00:00BUILDING PLAN REVIEW:
 1)- SBC 1203.4.1: TOILET ROOMS SHALL NOT
 OPEN DIRECTLY INTO A ROOM USED FOR THE
 PREPARATION OF FOOD FOR SERVICE TO THE
 PUBLIC.
 2)- SBC 1204.2 SURROUNDING MATERIALS:
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBENT
 MATERIAL TO A HEIGHT OF 4'-0" ABOVE THE
 FLOOR.
 3)- SBC 803.3 MINIMUM INTERIOR FINISH CL
 ASSIFICATION, AS PER ASTM E84. PROVIDE
 THE FLAMESPREAD AND THE SMOKE DEVELOP-
 MENT FOR THE INTERIOR FINISHES OR THE
 MINIMUM CLASSIFICATION OF MATERIALS TO
 BE USED.
 4)- FL ACCESSIBILITY CODE 4.13.6
 MANEUVERING CLEARENCES AT DOORS SEE FIG.
 #25 FOR DOORS TO RESTROOM.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-22 Cont ID  
Sent By dpalmer Date 2001-02-22 Time 08:43 Rev Time 0.00
Received By dpalmer Date 2001-02-22 Time 08:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-01-22 Cont ID  
Sent By dpalmer Date 2001-01-22 Time 20:24 Rev Time 0.00
Received By dpalmer Date 2001-01-22 Time 20:24 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-02-27 Cont ID  
Sent By lsmith Date 2001-02-27 Time 08:49 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-01-18 Cont ID  
Sent By mcarsill Date 2001-01-18 Time 13:06 Rev Time 0.00
Received By mcarsill Date 2001-01-18 Time 13:06 Sent To  
Notes
2001-01-18 00:00:001) INTERIOR FINISH MUST MEET A MINIMUM
 OF A CLASS C FLAME SPREAD.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-02-06 Cont ID  
Sent By ndenmark Date 2001-02-06 Time 07:37 Rev Time 0.33
Received By ndenmark Date 2001-02-06 Time 07:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-11-06 Cont ID  
Sent By kstevens Date 2001-11-06 Time 17:42 Rev Time 1.00
Received By kstevens Date 2001-11-06 Time 17:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-02-27 Cont ID  
Sent By jleech Date 2001-02-27 Time 07:54 Rev Time 0.75
Received By jleech Date 2001-02-27 Time 07:53 Sent To  
Notes
2001-02-27 00:00:00PLANS MUST BE REVIEWED BY HEALTH DEPART-
 MENT. APPROVAL STAMP MUST BE AFFIX TO
 PLAN.
 PLANS HAVE BEEN APPROVED BY HEATH DEPT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-23 Cont ID  
Sent By jleech Date 2001-01-23 Time 16:44 Rev Time 2.00
Received By jleech Date 2001-01-23 Time 16:44 Sent To  
Notes
2001-01-23 00:00:00DENIED;
  
 1.MOP SINK IS IN THE ACCESSIBLE ROUTE
 OF THE BATHROOM 97 FACBC 4.3.
  
 2.WATER HEATER MUST BE READILY
 ACCESSIBLE 94 SPC 501.7. INSTALL W/H
 ON FLOOR OR INSTALL A FIXED SHIPS
 LADDER.
  
 3.3" FLOOR DRAIN WITH TRAP PRIMER
 REQUIRED IN RESTROOM. SPC 409.4.1.1.
  
 4.BATHROOM CANNOT OPEN DIRECTLY INTO
 A ROOM USED FOR THE PREPARATION OF
 FOOD FOR THE PREPARATION OF FOOD FOR
 SERVICE TO THE PUBLIC SPC 404.2.
  
 5.(AIR CHAMBER DETAIL) AIR CHAMBERS
 SHALL COMPLY WITH SPC 607.8.1. MUST
 BE ENGINEERED OR CALCULATED AND COMPLY
 WITH 607.8.3. THEY MUST BE ACCESSIBLE.
  
 6.SEPORATE GREASY WASTE LINE REQUIRED
 FOR MOP SINK AND THE TWO FLOOR SINKS
 AND RUN TO EXISTING GREASE TRAP.
  
 7.A-3 WATER HEATER DETAIL SHOWS 50 GAL.
 LOW BOY. WATER RISER SHOWS 20 GAL.W/H.
 WHAT SIZE IS WATER HEATER.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-02-27 Cont ID  
Sent By pkrauss Date 2001-02-27 Time 08:52 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***