Plan Review Details - Permit 01010543
Plan Review Stops For Permit 01010543
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-01-03 Cont ID  
Sent By dpalmer Date 2002-01-03 Time 06:43 Rev Time 0.00
Received By dpalmer Date 2002-01-03 Time 06:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-22 Cont ID  
Sent By dpalmer Date 2001-03-22 Time 20:13 Rev Time 0.00
Received By dpalmer Date 2001-03-22 Time 20:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-30 Cont ID  
Sent By dpalmer Date 2001-01-30 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2001-01-30 Time 14:47 Sent To  
Notes
2001-01-30 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 4) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-01-27 Cont ID  
Sent By jleech Date 2001-01-27 Time 07:52 Rev Time 0.33
Received By jleech Date 2001-01-27 Time 07:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-01-27 Cont ID  
Sent By jleech Date 2001-01-27 Time 07:52 Rev Time 0.25
Received By jleech Date 2001-01-27 Time 07:52 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-03-27 Cont ID  
Sent By rmcdouga Date 2001-03-27 Time 08:20 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-03-27 00:00:00***************PROVISO******************
  
 1) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS PRIOR TO
 INSTALLATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-02-26 Cont ID  
Sent By rmcdouga Date 2001-02-26 Time 11:47 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-02-26 00:00:00DENIED
  
 1) PROVIDE ENERGY CALCULATIONS THAT
 HAVE SIGNATURE OF OWNER/AGENT.
  
 2) PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 - EXTERIOR DOOR TO MASTER BATH
 - FRENCH DOORS
 PRODUCT APPROVAL FOR SLIDING GLASS DOOR
 WAS SUBMITTED, HOWEVER NONE ARE
 INDICATED ON PLANS. PLEASE CLARIFY.
  
 3) WET SIGNATURE OF ENGINEER IS
 REQUIRED ON DESIGN CERTIFICATION FORM.
 PLEASE USE THE CITY OF WEST PALM BEACH
 CERTIFICATION FORMS WHICH ARE ATTACHED
 TO THE ONES THAT WERE SUBMITTED.
  
 4) ATTIC ACCESS MUST BE PROVIDED TO NEW
 ADDITION.
  
 5) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE INDICATING THE SPECIFIC TYPES
 OF ANCHORS TO BE USED FOR STORM PANEL.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-01-24 Cont ID  
Sent By sgraham Date 2001-01-24 Time 16:29 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***