| Plan Review Stops For Permit 01010497 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-03-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-03-13 |
Time |
14:43 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-01-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-01-22 |
Time |
13:38 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-22 00:00:00 | BUILDING PLAN REVIEW: | | | 1)- NOTE NOTICE OF COMENCEMENT IS GOOD | | | ONLY FOR 90 DAYS FROM DATE RECORDED IF | | | WORK HASN'T COMMENCED. | | | 2)- FL ENERGY CALCULATION WILL BE | | | REQUIRED AS PER FL. EN. CODE 400. | | | 3)- GLAZED OPENINGS WILL REQUIRE PROOF | | | OF LARGE MISSLE IMPACT TESTING,SBC | | | 1606.4.1/1707.4.1- THE CITY WILL PROVISO | | | THIS ISSUE, A SEPERATE SUB-PERMIT WILL | | | BE REQUIRED, A COPY OF THE CITIES POLICY | | | IS ENCLOSED AS WHAT WILL BE REQUIRED. | | | 4)- FL ACCESSIBILITY CODE 4.13.6- | | | MANEUVERING CLEARENCES AT DOORS AT HAND- | | | ICAPPED RESTROOM SEE FIGURE 25, A 24" | | | MINIMUM ON THE PUSH SIDE, SEE ATTACHMENT | | | 5)- SBC 803.3 PLEASE INDICATE THE INTER- | | | IOR MINIMUM FINISH CLASSIFICATION IN | | | ACCORDANCE WITH ASTM E-84. INDICATE THE | | | FLAMESPREAD & SMOKE DEVELOPMENT. | | | 6)- SBC 104.2.2-SHEET A-2 SEC A-A- | | | ADDITIONAL INFO. REQUIRED, A DROP CEIL- | | | ING OR SOFFITED CEILING NOTES: STUD | | | FRAMING SIZED TO MFGR? WHAT SIZE IS THE | | | FRAMING? HOW OFTEN IS THE TOP TRACK | | | FASTENED ABOVE, AND TO WHAT? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX. 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-05-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-18 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-18 |
Time |
09:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-03-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-06 |
Time |
20:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-06 |
Time |
20:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-01-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-22 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-22 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2001-01-22 00:00:00 | ************* UNSAT ******************** | | | | | | 1)NOTE: PLEASE NOTE PER F.A.C PER | | | STATUE 553-79-6-A. PLANS SUBMITTED FOR | | | 480/277V NEED TO BE SIGNED AND SEALED BY | | | A PE. | | | | | | 2)NOTE: PLEASE SEE SHEET E-1 FOR COLOR | | | CODING OF FEEDERS. PLEASE SEE LOCAL | | | AMENDMENTS ART 215 | | | | | | 3)NOTE: PLEASE SEE 210-62 FOR SHOW | | | WINDOW OUTLETS. | | | | | | 4)NOTE: PLEASE SHOW CALCULATIONS FOR | | | TRACK LIGHTING PER 220-12B | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVEW. | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-03-22 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2001-03-22 |
Time |
13:53 |
Rev Time |
0.20 |
| Received By |
rturnque |
Date |
2001-03-22 |
Time |
13:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-02-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-02-27 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-02-27 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2001-02-27 00:00:00 | 1) PLEASE CLEARLY INDICATE FIRE ALARM | | | EQUIPMENT WITHIN TENANT SPACE. | | | 2) PLEASE PROVIDE PERMIT AND SHOP | | | DRAWINGS FOR FIRE ALARM REMODEL. | | | 3) PLEASE PROVIDE PERMIT AND SHOP | | | DRAWINGS FOR FIRE SPRINKLER REMODEL. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-01-17 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-17 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-17 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2001-01-17 00:00:00 | 1) NO FIRE ALARM EQUIPMENT SHOWN ON | | | PLANS. PLEASE SHOW FIRE ALARM EQUIPMENT | | | ON DRAWINGS. | | | 2) NO INTERIOR FINISH INFORMATION SHOWN | | | ON PLANS. PLEASE PROVIDE INTERIOR FINISH | | | INFORMATION ON PLANS. | | | 3) PLEASE INDICATE FIRE EXTINGUISHER | | | LOCATION. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-02-05 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-02-05 |
Time |
12:49 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2001-02-05 |
Time |
12:49 |
Sent To |
|
|
| Notes |
| 2001-02-05 00:00:00 | PROVISO: | | | 1. LOCATE AIR HANDLER WITH RESPECT TO | | | BUILDING CONSTRUCTION TO ALLOW FOR | | | SERVICE ACCESSIBLITY PER 1997 SMC 304.2 | | | AND TO ALLOW FOR THE | | | REMOVAL/REPLACEMENT OF EQUIPMENT. | | | 2. DUCT SMOKE DETECTOR TO BE TIED TO | | | BUILDING FIRE ALARM SYSTEM FOR | | | NOTIFICATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-03-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-20 |
Time |
17:17 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2001-03-20 |
Time |
17:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-01-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-22 |
Time |
15:17 |
Rev Time |
0.75 |
| Received By |
jleech |
Date |
2001-01-22 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2001-01-22 00:00:00 | DENIED; | | | | | | 1.HANDICAP DRESSING ROOM SHALL COMPLY | | | WITH 97 FACBC 4.35.2, 4.35.4 AND | | | 4.35.5. | | | | | | 2.FLOOR DRAIN SHOWN ON (PLUMBING FIXTURE | | | SCHEDULE) BUT NOT ON SANITARY RISER. | | | | | | 3.AIR CHAMBERS SHALL COMPLY WITH SPC | | | 607.8.2. APPROVED ENGINEERED SHALL BE | | | INSTALLED IN AN ACCESSIBLE PLACE | | | 607.8.3. | | | | | | 4.DRINKING FOUNTAIN SHALL COMPLY WITH | | | FACBC 4.15. PROVISIONS SHALL BE MADE | | | FOR PEOPLE WHO HAVE TROUBLE BENDING | | | AND STOOPING. | | | | | | PLUMBING PLAN REVIEW BY | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|
|