Plan Review Details - Permit 01010497
Plan Review Stops For Permit 01010497
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-03-13 Cont ID  
Sent By jwitmer Date 2001-03-13 Time 14:43 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-22 Cont ID  
Sent By jwitmer Date 2001-01-22 Time 13:38 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-22 00:00:00BUILDING PLAN REVIEW:
 1)- NOTE NOTICE OF COMENCEMENT IS GOOD
 ONLY FOR 90 DAYS FROM DATE RECORDED IF
 WORK HASN'T COMMENCED.
 2)- FL ENERGY CALCULATION WILL BE
 REQUIRED AS PER FL. EN. CODE 400.
 3)- GLAZED OPENINGS WILL REQUIRE PROOF
 OF LARGE MISSLE IMPACT TESTING,SBC
 1606.4.1/1707.4.1- THE CITY WILL PROVISO
 THIS ISSUE, A SEPERATE SUB-PERMIT WILL
 BE REQUIRED, A COPY OF THE CITIES POLICY
 IS ENCLOSED AS WHAT WILL BE REQUIRED.
 4)- FL ACCESSIBILITY CODE 4.13.6-
 MANEUVERING CLEARENCES AT DOORS AT HAND-
 ICAPPED RESTROOM SEE FIGURE 25, A 24"
 MINIMUM ON THE PUSH SIDE, SEE ATTACHMENT
 5)- SBC 803.3 PLEASE INDICATE THE INTER-
 IOR MINIMUM FINISH CLASSIFICATION IN
 ACCORDANCE WITH ASTM E-84. INDICATE THE
 FLAMESPREAD & SMOKE DEVELOPMENT.
 6)- SBC 104.2.2-SHEET A-2 SEC A-A-
 ADDITIONAL INFO. REQUIRED, A DROP CEIL-
 ING OR SOFFITED CEILING NOTES: STUD
 FRAMING SIZED TO MFGR? WHAT SIZE IS THE
 FRAMING? HOW OFTEN IS THE TOP TRACK
 FASTENED ABOVE, AND TO WHAT?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX. 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-05-18 Cont ID  
Sent By dpalmer Date 2001-05-18 Time 09:48 Rev Time 0.00
Received By dpalmer Date 2001-05-18 Time 09:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-06 Cont ID  
Sent By dpalmer Date 2001-03-06 Time 20:37 Rev Time 0.00
Received By dpalmer Date 2001-03-06 Time 20:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-22 Cont ID  
Sent By dpalmer Date 2001-01-22 Time 16:04 Rev Time 0.00
Received By dpalmer Date 2001-01-22 Time 16:04 Sent To  
Notes
2001-01-22 00:00:00************* UNSAT ********************
  
 1)NOTE: PLEASE NOTE PER F.A.C PER
 STATUE 553-79-6-A. PLANS SUBMITTED FOR
 480/277V NEED TO BE SIGNED AND SEALED BY
 A PE.
  
 2)NOTE: PLEASE SEE SHEET E-1 FOR COLOR
 CODING OF FEEDERS. PLEASE SEE LOCAL
 AMENDMENTS ART 215
  
 3)NOTE: PLEASE SEE 210-62 FOR SHOW
 WINDOW OUTLETS.
  
 4)NOTE: PLEASE SHOW CALCULATIONS FOR
 TRACK LIGHTING PER 220-12B
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVEW.
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-03-22 Cont ID  
Sent By rturnque Date 2001-03-22 Time 13:53 Rev Time 0.20
Received By rturnque Date 2001-03-22 Time 13:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-02-27 Cont ID  
Sent By mcarsill Date 2001-02-27 Time 15:06 Rev Time 0.00
Received By mcarsill Date 2001-02-27 Time 15:06 Sent To  
Notes
2001-02-27 00:00:001) PLEASE CLEARLY INDICATE FIRE ALARM
 EQUIPMENT WITHIN TENANT SPACE.
 2) PLEASE PROVIDE PERMIT AND SHOP
 DRAWINGS FOR FIRE ALARM REMODEL.
 3) PLEASE PROVIDE PERMIT AND SHOP
 DRAWINGS FOR FIRE SPRINKLER REMODEL.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-01-17 Cont ID  
Sent By mcarsill Date 2001-01-17 Time 09:28 Rev Time 0.00
Received By mcarsill Date 2001-01-17 Time 09:28 Sent To  
Notes
2001-01-17 00:00:001) NO FIRE ALARM EQUIPMENT SHOWN ON
 PLANS. PLEASE SHOW FIRE ALARM EQUIPMENT
 ON DRAWINGS.
 2) NO INTERIOR FINISH INFORMATION SHOWN
 ON PLANS. PLEASE PROVIDE INTERIOR FINISH
 INFORMATION ON PLANS.
 3) PLEASE INDICATE FIRE EXTINGUISHER
 LOCATION.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-02-05 Cont ID  
Sent By ndenmark Date 2001-02-05 Time 12:49 Rev Time 0.33
Received By ndenmark Date 2001-02-05 Time 12:49 Sent To  
Notes
2001-02-05 00:00:00PROVISO:
 1. LOCATE AIR HANDLER WITH RESPECT TO
 BUILDING CONSTRUCTION TO ALLOW FOR
 SERVICE ACCESSIBLITY PER 1997 SMC 304.2
 AND TO ALLOW FOR THE
 REMOVAL/REPLACEMENT OF EQUIPMENT.
 2. DUCT SMOKE DETECTOR TO BE TIED TO
 BUILDING FIRE ALARM SYSTEM FOR
 NOTIFICATION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-03-20 Cont ID  
Sent By jleech Date 2001-03-20 Time 17:17 Rev Time 0.50
Received By jleech Date 2001-03-20 Time 17:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-22 Cont ID  
Sent By jleech Date 2001-01-22 Time 15:17 Rev Time 0.75
Received By jleech Date 2001-01-22 Time 15:16 Sent To  
Notes
2001-01-22 00:00:00DENIED;
  
 1.HANDICAP DRESSING ROOM SHALL COMPLY
 WITH 97 FACBC 4.35.2, 4.35.4 AND
 4.35.5.
  
 2.FLOOR DRAIN SHOWN ON (PLUMBING FIXTURE
 SCHEDULE) BUT NOT ON SANITARY RISER.
  
 3.AIR CHAMBERS SHALL COMPLY WITH SPC
 607.8.2. APPROVED ENGINEERED SHALL BE
 INSTALLED IN AN ACCESSIBLE PLACE
 607.8.3.
  
 4.DRINKING FOUNTAIN SHALL COMPLY WITH
 FACBC 4.15. PROVISIONS SHALL BE MADE
 FOR PEOPLE WHO HAVE TROUBLE BENDING
 AND STOOPING.
  
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT. 8377