Plan Review Details - Permit 01010496
| Plan Review Stops For Permit 01010496 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-02-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-02-21 |
Time |
07:46 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-01-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-01-23 |
Time |
06:59 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-23 00:00:00 | BUILDING PLAN REVIEW: | | | 1)- SBC 803.3 MINIMUM INTERIOR FINISH | | | CLASSIFICATION: PROVIDE INFORMATION IN | | | ACCORDANCE WITH ASTM E-84 FOR FLAME | | | SPREAD AND SMOKE DEVELOPMENT. | | | 2)- DOORS 307 & 307A NOT LISTED IN THE | | | DOOR SCHEDULE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX.8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-01-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-22 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-22 |
Time |
17:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-02-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-02-21 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-02-21 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2001-02-21 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | WITH REVISION. | | | | | | APPROVED PROVISO, PENDING FIRE SPRINKLER | | | DRAWINGS. CAPTAIN MIKE CARSILLO AND JIM | | | WHITMER, PLANS REVIEW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-01-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-19 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-19 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2001-01-19 00:00:00 | 1) PLEASE INDICATE THE LOCATION AND | | | PROPOSED ROUTE, WHEN PERSONS EXIT FROM | | | DOORS 367. | | | 2) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION PROVIDED WITH PLANS. | | | 3) DOORS 307 AND 307 A MUST BE ABLE TO | | | SWING TIGHT AGAINST A WALL AS THEY | | | OPEN DIRECTLY OPPOSITE ONE ANOTHER. | | | 4) PLEASE PROVIDE COMPLETE FIRE ALARM | | | SYSTEM SHOP DRAWINGS FOR FIRE ALARM | | | EQUIPMENT SHOWN ON THE DRAWINGS. | | | SEPARATE PERMIT REQUIRED. | | | 5) FIRE SPRINKLER REMODEL TO BE DONE | | | UNDER SEPARATE PERMIT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-02-05 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-02-05 |
Time |
13:01 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2001-02-05 |
Time |
13:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2001-02-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-02-21 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2001-08-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-22 |
Time |
13:28 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2001-08-22 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2001-08-22 00:00:00 | STAIR REVISION 8/10/01REV 8/22/01 JW |
|
|
|
Account Summary | Usage Policy | Privacy Policy