| Plan Review Stops For Permit 01010487 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-01-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-01-24 |
Time |
17:15 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-01-24 00:00:00 | STORM SHUTTERS FIRST FLOOR OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-05-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-18 |
Time |
13:47 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-18 00:00:00 | PROVISO: | | | | | | 1)- WINDOW BUCK ATTACHMENT: PRODUCT | | | APPROVAL REPORTS MAY HAVE DETAIL ON THE | | | BUCK ATTACHMENT IF NOT THE DESIGN | | | PROFESSIONAL WILL BE REQUIRED TO DETAIL | | | THE ATTACHMENT. | | | 2)- PRODUCT APPROVAL REPORTS FOR ALL | | | GLAZED OPENINGS WILL BE REQUIRED FOR ALL | | | GLAZED OPENINGS. SBCCI REPORT OR DADE | | | COUNTY REPORT WILL BE REQUIRED.WPBPOLICY | | | (GUIDELINES)FOR GLAZED OPENINGS MUST BE | | | ADHERRED TO FOR LARGE PROJECTS. | | | 3)- ROOFING: WILL BE UNDER SEPERATE | | | PERMIT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-04-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-04-06 |
Time |
07:20 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-05-18 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2001-04-06 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01010487 | | | 5400 EAST AV | | | (OUT PATIENT OFFICE BLVD) | | | THE WEITZ CO. | | | 686-5511 | | | | | | 1) SBC 1606.2.6.2. COMPONENTS & CLADDING | | | MISSING IS A BUCK ATTACHMENT DETAIL FOR | | | WINDOWS & DOORS. | | | | | | 2)- PRODUCT APPROVALS: FOR ALL ROOFING | | | SYSTEMS, ALL GLAZED OPENINGS, WINDOWS | | | DOORS & SKYLIGHTS WILL REQUIRE PRODUCT | | | APPROVAL REPORTS COMPLYING WITH CHAPTERS | | | 1606/ 1707 OF THE S.B.C. THESE ITEMS CAN | | | BE PROVISOED: THE PRODUCT APPROVALS | | | WOULD REQUIRE A SEPERATE SUB-PERMIT WITH | | | THE ASSOCIATED FEES. | | | | | | 3)- STATE RADON FEES TO BE PAID TO THE | | | CITY : $ 148.00. | | | | | | 4)- COUNTY IMPACT FEES,PLANS ARE TO | | | STAMPED FOR PAYMENT. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-01-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-01-24 |
Time |
12:48 |
Rev Time |
5.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-24 00:00:00 | 5400 EAST AV. / 01010487 | | | BUILDING PLAN REVIEW | | | 1). FL ENERGY CODE 400.ABCD.2 CODE | | | COMPLIANCE CERTIFICATION- THE BUILDINGS | | | OWNER, THE OWNER ARCHETECT, OR OTHER | | | AUTHERIZED AGENT LEGALLY DESIGNATED BY | | | THE OWNER SHALL CERTIFY TO THE BUILDING | | | OFFICIAL THAT THE BUILDING IS IN COMPLI- | | | ANCE WITH THE ENERGY EFFICIENCY CODE. A | | | SIGNATURE IS REQUIRED, HIGHLIGHTED IN | | | YELLOW HIGHLIGHTER ON ENERGY CALC. SHEET | | | 2). DISCREPANCIES: | | | A). SHEET A-4, NOTE #9 IS TO BE DELETED | | | AS PER CONVERSATION WITH ARCH. 01/24/01 | | | OR LETTER DELETING NOTE #9. | | | B). SHEET S-2 IS THE SECOND FLOOR FRAM- | | | ING PLAN, SHEET S-3 ALSO INDICATES IT IS | | | THE SECOND FLOOR FRAMING PLAN? | | | C). STRUCTURAL NOTES ON S-5 SEC.3 | | | PRECAST, PRESTRESSED CONCRETE NOTE 5.A | | | ALL PRESRESSED UNITS TO BE DESIGNED TO C | | | ONFORM TO THE LATEST REQUIREMENTS OF THE | | | STANDARD BUILDING CODE NOT THE SOUTHERN | | | STANDARD CODE. | | | 3). SBC 1606.2.6.2 COMPONENTS & CLADDING | | | A BUCK DETAIL SHOWING ATTACHMENT TO THE | | | STRUCTURE WILL BE REQUIRED. | | | 4). SBC 104.2.2. ADDITIONAL INFORMATION | | | SHEET A-15 DETAIL 3&5 SHOW A HI LEG | | | TRACK ANCHORED TO THE STRUCTURE ABOVE, | | | WHAT SIZE ANCHOR IS TO BE USED, & HOW | | | OFTEN? | | | 5).PRODUCT APPROVALS: FOR ROOFING,ALL | | | GLAZED OPENINGS,WINDOWS, DOORS & SKY- | | | LIGHRS WILL REQUIRE PRODUCT APPOVAL RE- | | | PORTS COMPLYING WITH CHAP.1606/1707 OF | | | THE S.B.C.THESE ITEMS CAN BE PROVISOED: | | | THE PRODUCT APPROVALLS WOULD REQUIRE A | | | SEPERATE SUB-PERMITS WITH THE ASSOCIATED | | | FEES. | | | | | | BUILDING PLAN REVIEW: | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-04-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-05 |
Time |
20:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-05 |
Time |
20:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-01-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-29 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-29 |
Time |
11:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2001-03-29 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-03-29 |
Time |
15:38 |
Rev Time |
1.50 |
| Received By |
mamini |
Date |
2001-03-29 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2001-03-29 00:00:00 | PASSED; | | | 1. RESPONSES TO PREVIOUS REVIEW COMMENTS | | | DATED 1-29-01 SATISFACTORY. | | | IF ANY QUESTIONS PLEASE CONTACT 562-659- | | | 8096 EXT. 8492 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-01-29 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2001-01-29 |
Time |
14:23 |
Rev Time |
0.50 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-29 00:00:00 | FAILED | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION1. REVISED DUMPSTER AREA AS | | | PER OUR STANDARD MINIMUM DETAIL | | | DIMENSIONS. | | | SEE ATTACHED | | | 2. PROVIDE DRAINAGE CALCULATIONS TO | | | JOSE DEL RIOS, STORM WATER ENGINEER | | | 1000 45TH STREET WPB FL 33415 | | | (561) 659 8040 FOR APPROVAL. | | | 3. PROVIDE POLLUTION CONTROL PLAN | | | SHOWING SILT FENCE WITH BALES OF HAY | | | FOR ENTIRE PERIMETER OF CONSTRUCTION | | | AREA. | | | PROVIDE A NOTE STATING COVERAGE FOR | | | EXISTING CATCH BASINS WITH SCREENS AND | | | BALES OF HAY. | | | 4. DRIVEWAY APPROACH MUST MEET OUR | | | STANDARDS. SEE ATTACHED CWPB STANDARD | | | DRIVEWAY APPROACH DETAILS. | | | 5. PROVIDE IMPERVOIUS AND PERVOIUS | | | CALCULATIONS FOR ENTIRE SITE THE TOTAL | | | MUST ADD UP TO 100% OF THE TOTAL SITE | | | AREA. | | | PROVIDE THIS INFORMATION ON A 8 1/2 X11 | | | SHEET WITH EITHER THE PROPERTY CONTROL | | | NUMBER OR THE PROJECT ADDRESS. | | | IF ANY QUESTIONS PLEASE FEEL FREE TO | | | CONTACT OUR OFFICE . | | | 561 659 8040 EXT. 2306 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-05-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-09 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-09 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2001-05-09 00:00:00 | RECEIVED FAXED LETTER INDICATING THAT | | | ANOTHER FIRE HYDRANT WILL BE INSTALLED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-04-04 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-04 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-04 |
Time |
12:44 |
Sent To |
|
|
| Notes |
| 2001-04-04 00:00:00 | 1) NO FIRE SPRINKLER OR HYDRAULIC | | | CALCULATIONS PROVIDED WITH DRAWINGS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-01-17 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-17 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-17 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2001-01-17 00:00:00 | 1) ELEVATION DRAWINGS DID NOT DISPLAY | | | BUILDING ADDRESS. BUILDING ADDRESS TO | | | BE INSTALLED AND COMPLY WITH CITY CODE | | | REQUIREMENTS. | | | 2) AWNINGS PLANNED FOR USE ARE TO BE | | | FIRE RETARDANT. | | | 3) IT APPEARS THAT ANOTHER FIRE HYDRANT | | | IS NEEDED NEAR THE BUILDING. THE FIRE | | | SPRINKLER SYSTEM CONNECTION FOR THE | | | BUILDING SHALL NOT EXCEED 150 FEET FROM | | | A FIRE HYDRANT. | | | 4) PLEASE INDICATE WHAT THE FUTURE RAMP | | | AND PLATFORM WILL BE USED FOR. ARE THESE | | | WHEN INSTALLED, TEMPORARY OR PERMANANT. | | | WHAT CONSTRUCTION TYPE WILL THEY BE. | | | 5) ELEVATOR TO COMPLY WITH ANSI A17.1 | | | 6) PORTABLE FIRE EXTINGUISHERS WHEN | | | INSTALLED, ARE TO BE EQUIPPED WITH A | | | CURRENT SERVICE TAG. | | | 7) PLEASE PROVIDE COMPLETE FIRE | | | SPRINKLER SYSTEM DRAWINGS AND HYDRAULIC | | | CALCULATIONS TO THIS OFFICE. SEPARATE | | | PERMIT REQUIRED. | | | 8) PLEASE PROVIDE COMPLETE FIRE ALARM | | | SYSTEM DRAWINGS TO THIS OFFICE. CUT | | | SHEETS, WIRING DIAGRAM, BATTERY | | | CALCULATIONS, FLOOR PLANS ARE REQUIRED. | | | 9) THE FIRE SPRINKLER SYSTEM AND FIRE | | | ALARM SYSTEM TO BE SUPERVISED BY A | | | LICENSED UL LISTED CENTRAL STATION | | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | | 10) A KNOX-BOX WILL BE REQUIRED FOR | | | RAPID FIRE ACCESS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-05-03 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-05-03 |
Time |
15:14 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2001-05-03 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2001-05-03 00:00:00 | PROVISO: | | | FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | REQUIRED PER 1997 SMC 406 INCLUDING | | | HORN AND STROBE FOR NOTIFICATION PER | | | 1996 NFPA 90A | | | ALL OTHER PREVIOUS INFORMATION REQUESTED | | | EXISTS IN WITH BUILDING PLAN. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2001-04-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-13 |
Time |
14:22 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-04-13 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2001-04-13 00:00:00 | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION WITH MECHANICAL PERMIT | | | APPLICATION: | | | | | | O.A. CALCULATIONS AS PER ASHRAE 62-89. | | | | | | KEY NOTES ON DRAWING A-4 #19 & 20, | | | EXHAUSET SHALL BE 10' FROM OR 24" ABOVE | | | O.A. INTAKE.ONE OF THE EXHAUST OULETS | | | WHEN SCALED ON PLAN IS ONLY 4' 6" FROM | | | O.A. INTAKE. | | | | | | SUBMIT DETAIL ON CONDENSER UNIT STANDS. | | | | | | AHU'S WITH FAN CAPACITY GREATER THAN | | | 2,00 CFM SHALL HAVE FAN SHUTDOWN BY | | | DUCT SMOKE DETECTOR AS PER 1997 SMC | | | 406.1 AND HAVE NOTIFICATION TO | | | ALARM/STROBE IN NORMALLY OCCUPIED AREAS. | | | | | | PLEASE INDICATE ON PLAN WHERE THE | | | CONDENSATE IS BEING DISPOSED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-02-05 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-02-05 |
Time |
15:31 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2001-02-05 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2001-02-05 00:00:00 | *************DENIED********************* | | | 1. VENT STACKES AND EXHAUST OUTLETS | | | SHALL BE MINIMUM 10 FOOT FROM OUTSIDE | | | AIR INTAKE PER 1997 SMC 405SEE A-3 | | | 2. OUTSIDE AIR SCHEDULE AND A/C | | | EQUIPMENT SCHEDULES DO NOT MATCH. | | | PROVIDE CORRECTED INFORMATION ON | | | OUTSIDE AIR TO MATCH EQUIPMENT SUPPLIED. | | | 3. PROVIDE FIRE DAMPER INSTALLATION | | | INFORMATION PER 1997 SMC 610. | | | 4. EXHAUST FANS FROM RR103 AND RR 103A | | | DUCT THROUGH WALL AND UP THROUGH 2ND | | | FLOOR. DUCTS FROM 1ST FLOOR NEED TO BE | | | ENCLOSED IN SHAFT THROUGH 2ND FLOOR PER | | | 1997 SMC 610.4. | | | 5. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2001-10-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-01 |
Time |
13:37 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-10-01 |
Time |
13:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-08-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-08 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2001-08-08 |
Time |
10:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-07-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-07-20 |
Time |
08:22 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-07-20 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2001-07-20 00:00:00 | REVISION TO PLAN; | | | CONDENSATE UNDER GROUND. | | | PROVISO; CONDENSATE DRAIN SHOULD BE | | | TRAPED AT A/H UNIT. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-04-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-04-28 |
Time |
13:07 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2001-04-28 |
Time |
13:07 |
Sent To |
|
|
| Notes |
| 2001-04-28 00:00:00 | PLUMBING PLAN REVIEW. SPC-94 | | | | | | PASSED | | | | | | PROVISO: | | | | | | AIR-CHAMBERS TO BE ACCESSABLE AND | | | RECHARGEABLE. 607.8.2 - 607.8.3 | | | 1-1/4" SUPPLY TO WATER CLOSETS? | | | | | | SUBMIT REVISED H2O RISER DIAGRAMS BEFORE | | | INSPECTIONS. | | | | | | REVIEW BY KEN STEVENS (561) 569-8096 | | | EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-01-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-26 |
Time |
09:32 |
Rev Time |
1.75 |
| Received By |
jleech |
Date |
2001-01-26 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2001-01-26 00:00:00 | DENIED; | | | | | | 1.COFFEE ROOM SINKS SHALL COMPLY WITH | | | FACBC 4.24.1 THRU 4.24.7. | | | | | | 2.DRINKING FOUNTAIN SHALL COMPLY WITH | | | FACBC 4.1.3 (10) AND 4.15. PROVISIONS | | | SHALL BE MADE FOR PEOPLE WHO HAVE | | | TROUBLE BENDING OR STOOPING. CHECK | | | CLEAR FLOOR SPACE, SECOND FLOOR | | | DRINKING FOUNTAIN 30"X 48". | | | | | | 3.P-3 (RISER DIAGRAM) HORIZONTAL DRY | | | VENTS ARE NOT PERMITED. 94 SPC 914.2. | | | | | | 4.WATER RISER DIAGRAM REQUIRED. | | | | | | 5.PROVIDE RAIN FALL CALCULATIONS, TOTAL | | | SQUIRE FOOTAGE OF ROOF AREA FOR EACH | | | ROOF DRAIN AND DEGREE OF PITCH FOR | | | HORIZONTAL RAIN LEADERS AND STORM | | | SEWER. SPC TABLE 1108.1, 1108.2 AND | | | 1108.4. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-05-17 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-05-17 |
Time |
14:54 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|