Plan Review Details - Permit 01010477
Plan Review Stops For Permit 01010477
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-02-01 Cont ID  
Sent By jgomez Date 2001-02-01 Time 16:38 Rev Time 1.50
Received By jgomez Date 2001-02-01 Time 16:38 Sent To  
Notes
2001-02-01 00:00:00APPROVED WITH PROVISO:
 1-SEE COMMENTS ON PLANS.
2001-01-27 00:00:00APPROVED WITH PROVISO:
  
 1-PROVIDE SAFETY GLASS AT BATHROOM
 WINDOW. SECTION 2405.2 SBC 1997.
  
 2-PROVIDE PRODUCT APPROVAL FOR NEW
 EXTERIOR DOOR.
  
 3-RESPOND TO ALL ITEMS REQUESTED BY THE
 PLUMBING PLAN REVIEWER IN ORDER TO
 OBTAIN ALL PERMITS.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT JULIO GOMEZ AT 659-8096 EXT 8232

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-01-17 Cont ID  
Sent By dpalmer Date 2001-01-17 Time 11:04 Rev Time 0.00
Received By dpalmer Date 2001-01-17 Time 11:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-01-31 Cont ID  
Sent By jleech Date 2001-01-31 Time 19:33 Rev Time 0.33
Received By jleech Date 2001-01-31 Time 19:33 Sent To  
Notes
2001-01-31 00:00:00PROVISO;
 GAS PERMIT APPLICATION WITH PLANS
 REQUIRED FOR GAS HEATER. PLANS NEED TO
 INCLUDE COMBUSTION AIR CAULKS FOR WATER
 HEATER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-13 Cont ID  
Sent By jleech Date 2001-01-13 Time 14:09 Rev Time 1.00
Received By jleech Date 2001-01-13 Time 14:09 Sent To  
Notes
2001-01-13 00:00:00DENIED;
 1.SHOWER STALL MUST BE 30" INSIDE DIA.
  
 2.SHOW HOW GAS WATER HEATER WILL BE VENT
 ED AND HOW CONFINED SPACE WILL BE
 SUPPLYED WITH AIR FOR C0OMBUSTION,
 VENTILATION AND DILUTION OF FLUE GASES
  
 3. RISER DIAGRAM;
 A.MINIMUM SIZE PIPE UNDER SLAB IS
 2" KITCHEN SINK.
 B.MINIMUM SIZE PIPE FOR W/C WASTE
 IS 3"
 C.WASHING MACHINE IS UNVENTED.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377