Plan Review Details - Permit 01010477
| Plan Review Stops For Permit 01010477 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-02-01 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-02-01 |
Time |
16:38 |
Rev Time |
1.50 |
| Received By |
jgomez |
Date |
2001-02-01 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2001-02-01 00:00:00 | APPROVED WITH PROVISO: | | | 1-SEE COMMENTS ON PLANS. | | 2001-01-27 00:00:00 | APPROVED WITH PROVISO: | | | | | | 1-PROVIDE SAFETY GLASS AT BATHROOM | | | WINDOW. SECTION 2405.2 SBC 1997. | | | | | | 2-PROVIDE PRODUCT APPROVAL FOR NEW | | | EXTERIOR DOOR. | | | | | | 3-RESPOND TO ALL ITEMS REQUESTED BY THE | | | PLUMBING PLAN REVIEWER IN ORDER TO | | | OBTAIN ALL PERMITS. | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT JULIO GOMEZ AT 659-8096 EXT 8232 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-01-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-17 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-17 |
Time |
11:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-01-31 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-31 |
Time |
19:33 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2001-01-31 |
Time |
19:33 |
Sent To |
|
|
| Notes |
| 2001-01-31 00:00:00 | PROVISO; | | | GAS PERMIT APPLICATION WITH PLANS | | | REQUIRED FOR GAS HEATER. PLANS NEED TO | | | INCLUDE COMBUSTION AIR CAULKS FOR WATER | | | HEATER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-01-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-13 |
Time |
14:09 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-01-13 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2001-01-13 00:00:00 | DENIED; | | | 1.SHOWER STALL MUST BE 30" INSIDE DIA. | | | | | | 2.SHOW HOW GAS WATER HEATER WILL BE VENT | | | ED AND HOW CONFINED SPACE WILL BE | | | SUPPLYED WITH AIR FOR C0OMBUSTION, | | | VENTILATION AND DILUTION OF FLUE GASES | | | | | | 3. RISER DIAGRAM; | | | A.MINIMUM SIZE PIPE UNDER SLAB IS | | | 2" KITCHEN SINK. | | | B.MINIMUM SIZE PIPE FOR W/C WASTE | | | IS 3" | | | C.WASHING MACHINE IS UNVENTED. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|
|
|