| 2001-02-01 00:00:00 | 200 BELMONTTE RD. |
| | CONT: ATLANTIC COAST REST EQUIP |
| | PERMIT # 01010380 |
| | 1)- FL ENERGY CODE REQUIRES ENERGY CALCS |
| | 2)- SBC 104.2.2 COUNTY AMENDMENTS- |
| | ADDITIONAL INFORMATION, ENGINEERING SHOW |
| | ING THAT THE FIRST FLOOR STRUCTURE,WALLS |
| | AND FOUNDATION WILL ACCEPT THE ADDITION- |
| | AL LOADING BEING IMPOSED ON THE STRUC- |
| | TURE. |
| | 3)- SBC 1804.2.7.2 COUNTY AMENDMENTS- |
| | A SOILS TEST REPORT AS TO THE MINIMUM |
| | SOILS BEARING VALUE.A 15 FT STANDARD |
| | PENETRATION TO DETERMINE BASIC SOIL BEAR |
| | ING CAPACITY REQUIRED IN |
| | TABLE 1804.2.7.3 AS AMENDEDED, SHALL BE |
| | DONE IN ACCORDANCE WITH ASTM-D 1586. |
| | 4) SBC 1606 DESIGN INFO. 1997 SBCCI FOR |
| | 110 MPH, STD-10 DESIGNS OR ASCE7-95. |
| | MEAN ROOF HEIGTH GIVEN, POSITVE/ NEGA- |
| | TIVE PRESSURES FOR GLAZED OPENINGS AND |
| | FOR END ZONES. |
| | 5)- NOTE: COUNTY IMPACT FEES AND STAMP |
| | ARE REQUIRED BEFORE ISSUANCE. |
| | 6)- SBC 1606.2.6.2 COMPONENTS & CLADDING |
| | A BUCK DETAIL SHOWING THE ATTACHMENT TO |
| | THE SUBSTRATA. |
| | 7)- SBC 1606.4.1/ 1707.4.1 PRODUCT |
| | APPROVAL FOR ALL WINDOWS, DOORS, GARAGE |
| | DOORS AND STORM SHUTTERS. |
| | 8)- SBC 1503.3.2 COUNTY AMENDMENTS- |
| | ROOF COVERINGS AND SYSTEMS SHALL BE |
| | DESIGNGED TO WITH STAND THE APPROPRIATE |
| | WIND LOADS PRESCRIBED IN 1606, (110 MPH |
| | WIND ZONE- PRODUCT APPROVAL). |
| | 9)- SBC 3401.2.1- ALTERATIONS TO EXIST- |
| | ING BUILDINGS, THE BUILDING OFFICIAL |
| | SHALL DETERMINE THE EXTENT TO WHICH THE |
| | EXISTING SYSTEM SHALL BE MADE TO CONFORM |
| | TO THE REQUIREMENTS OF THE TECHNICAL |
| | CODES FOR NEW CONSTRUCTION. EXISTING |
| | WINDER STAIRS: 1007.8.1 WINDERS SHALL |
| | HAVE A MINIMUM TREAD DEPTH OF 6" AT THE |
| | NARROW EDGE AND SHALL HAVE SHALL HAVE A |
| | MINIMUM TREAD DEPTH OF 11" AT A POINT |
| | 12" FROM THTE NARROW EDGE. |
| | 10)- DISCREPANCY- SHEET A-3 READING ROOM |
| | ATTHE EAST ELEVATION SHOWS (2) WINDOWS |
| | VS. SEC 1/A/4 INDICATES (3) WINDOWS? |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 EX 8412 |