Plan Review Details - Permit 01010342
Plan Review Stops For Permit 01010342
Review Stop FS  
Rev No 1 Status P Date 2001-01-10 Cont ID  
Sent By mcarsill Date 2001-01-10 Time 10:58 Rev Time 0.00
Received By mcarsill Date 2001-01-10 Time 10:57 Sent To  
Notes
2001-01-10 00:00:001) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL ELECTRICAL, MECHANICAL AND SERVICE
 ROOMS. ANY VERTICAL SHAFTS ARE ALSO TO
 BE FIRE SPRINKLER PROTECTED.
 2) FIRE SPRINKLER SYSTEM TO BE INSTALLED
 IN ACCORDANCE WITH NFPA 13.
 3) SPARE HEAD BOX AND WRENCH REQUIRED.
 4) FIRE HYDRANTS TO COMPLY WITH CITY
 UTILITY AND FIRE RESCUE REQUIREMENTS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910