Plan Review Details - Permit 01010260
Plan Review Stops For Permit 01010260
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-01-22 Cont ID  
Sent By dlauderm Date 2001-01-22 Time 11:14 Rev Time 0.30
Received By dlauderm Date 2001-01-22 Time 11:09 Sent To  
Notes
2001-01-22 00:00:00PASSED WITH PROVIOS:
 NEW WATER SERVICES MUST BE RELEASED
 BY THE HEALTH DEPRTMENT PRIOR TO
 BEING PLACED IN USE (IF REQUIRED)
 THE BACKFLOW PREVENTER LOCATIONS AND
 HEIGHTS MUST BE PREAPPROVED BY THE
 CITY BACKFLOW PREVENTER TECH, ORVILLE
 POLK.YOU NEED TO SCHEDULE A VISIT
 WITH HIM PRIOR TO INSTALLING THE
 DEVICES.HIS PHONE NUMBER IS 659-8005.
 THE GREASE TRAP WAS REPLACED, BUT THE
 OLD ONE WAS CRUSHED AND LEFT IN THE CITY
 ROAD RIGHT OF WAY.PRIOR TO ALLOWING
 THE ROAD TO BE BUILT THIS CRUSHED
 GREASE TRAP NEEDS TO BE REMOVED BY THE
 PROPERTY OWNER OR ROAD CONTRACTOR.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-01-23 Cont ID  
Sent By mcarsill Date 2001-01-23 Time 08:55 Rev Time 0.00
Received By mcarsill Date 2001-01-23 Time 08:55 Sent To  
Notes
2001-01-23 00:00:001) ON PAGE R6, THE FIRE HYDRANT IS NOTED
 TO BE REMOVED. WHERE IS THE FIRE HYDRANT
 GOING TO BE RELOCATED. ALSO FIRE
 HYDRANTS LOCATED ON THE EXECUTIVE
 CENTER DRIVE EXTENSION TO BE NO FARTHER
 THAN 500 FEET APART.
 2) FIRE RESCUE ACCESS IS REQUIRED ON THE
 EXECUTIVE CENTER DRIVE EXTENSION.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8397
 835-2910

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-01-21 Cont ID  
Sent By pschmitz Date 2001-01-21 Time 13:18 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-21 00:00:00PLUMBING PLAN REVIEW PROVISO
 (1) PRIOR TO CONSTRUCTION, ALL REQUIRED
 PERMITS OR APPROVALS MUST BE OBTAINED
 FOR ALL ASPECTS OF THE PROJECT FROM THE
 APPROPRIATE AGENCIES, INCLUDING ANY
 EASMENTS FROM PUBLIC OR PRIVATE ENTITIES
 (2) CONSTRUCTION SERVICES DEPARTMENT
 SHALL PERMIT,INSPECT AND TEST ALL WATER,
 WASTE WATER,ON PRIVATE PROPERTY AND IN
 EASMENTS, NOT OWNED BY THE CITY OF WEST
 PALM BEACH.
 THIS INSTALLATION SHALL COMPLY WITH THE
 CITY OF WEST PALM BEACH UTILITY DEPT.STD
 FOR MATERIALS,INSTALLATION AND TESTING.
 END OF COMMENTS,QUESTIONS CONTACT
 PAUL SCHMITZ 561-659-8096 X 8233