Plan Review Details - Permit 01010147
Plan Review Stops For Permit 01010147
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-02-15 Cont ID  
Sent By jwitmer Date 2001-02-15 Time 07:39 Rev Time 0.75
Received By jwitmer Date 2001-02-15 Time 07:39 Sent To  
Notes
2001-02-15 00:00:00PERMIT # 01010147
 201 CLEMATIS ST
 DAVID BROOKS ENTERPRISES
 PHONE: 863-1200
  
 STRUCTURAL PLAN REVIEW:
 THE ISSUES THAT WERE IN CONFLICT WITH
 THE CODE HAVE ALL BEEN ADDRESSED ACCEPT
 FOR THE FIRST ISSUE, THE OCCUPANT LOAD.
 AS A RULE OF THUMB WHEN THERE IS A
 DIFFERENCE IN CODE INTERPRETATION,
 WE TAKE THE ISSUE TO THE BUILDING
 OFFICIAL FOR A FINAL INTERPRETATION.THE
 BUILDING OFFICIAL AGREES THAT THE
 OCCUPANT LOAD FOR THE 991 SQ. FT. @ 15FT
 PER PERSON YIELDS AN OCCUPANT LOAD OF
 66 PEOPLE.
 1)- SBC 1004.1.2: EVERY ROOM OR TENANT
 SPACE WHICH HAS AN OCCUPANT LOAD OF 50
 OR MORE PERSONS SHALL NOT HAVE LESS THAN
 (2) TWO EGRESS DOORS.
 2)-SBC 1004.1.4: WHERE TWO OR MORE EXITS
 OR EXIT ACCESS DOORS ARE REQUIRED, AT
 LEAST TWO OF THE EXIT DOORS OR EXIT
 ACCESS DOORS SHALL BE PLACED A DISTANCE
 APART EQUAL TO NOT LESS THAN ONE HALF
 OF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED MEASURED IN A STRAIGHT
 LINE BETWEEN SUCH EXITS OR EXIT ACCESS
 DOORS.
  
 THE SECOND ISSUE THAT THE BUILDING
 OFFICIAL BROUGHT UP IS FLOOR LOADING.
 WHEN THIS BUILDING WAS C.O.,EDTHIS
 AREA WAS TO BE USED FOR LIGHT STORAGE OF
 PROPS. THERE IS A NEED TO DO A FLOOR
 ANALYSIS TO SEE IF THE EXISTING FLOOR
 JOIST WILL MEET THE FLOOR LOADING OF
 100 PSF LIVE LOAD AS PER SBC TABLE
 1604.1 FOR THEATERS: AISLES, CORRIDORS
 AND LOBBIES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX.8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-18 Cont ID  
Sent By jwitmer Date 2001-01-18 Time 07:45 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-18 00:00:001). OCCUPANT LOAD & MEANS OF EGRESS-
 SBC TABLE 1003.1 WITH 991 SQ. FT. TABLE
 1003.1 SETS THE OCCUPANT LOAD AS 66
 PEOPLE.SECTION 1020.1.3 STATES FOR A
 BUSINESS OCCUPANCY ABOVE THE GROUND
 FLOOR NO MORE THAN 40 PEOPLE ABOVE THE
 STREET WITH A SINGLE EXIT.
 2).SBC 104.2.2- ADDITIONAL INFORMATION
 WILL BE REQUIRED:
 A). A FIRE SPRINKLER PLAN WILL BE RE-
 QUIRED.
 B). THE PLANS AREN'T CLEAR WITH WHAT
 LOOKS LIKE IT COULD BE A CHAIR LIFT
 IF IT IS WE NEED CUT SHEETS, SHAFT
 RATING, OPENING PROTTECTIVES FOR
 THE SECOND FLOOR.IF NOT, FL. ACC-
 ESSIBILITY CODE REQUIRES VERTICAL
 ACCESSIBILITY FOR CHANGES IN
 ELEVATION (FL ACC 4.3.8.C), THIS
 ALSO INCLUDES THE CHANGE IN HEIGTH
 AT THE ENTRY DOOR AS WELL AS AT THE
 ELEVATED BAANQUET SEATS 7".
 3). PLANS INDICATE THIS IS A FIRE
 SPRINKLERED BUILDING, PLEASE INDICATE
 (TABLE 803.3) THE MINIMUM INTERIOR FIN-
 ISH CLASSIFICATIONS.
 4).PLANS INDICATE GLAZING NEXT TO THE
 ENTRY DOOR(SBC 2405.2.3) REQUIRES THAT
 SAFETY GLAZING BE INSTALLED,HAZARDOUS
 LOCATION.
 5).FL. ACC. CODE 4.13.9 DOOR HARDWARE-
 HANDLES,PULLS,LATCHES,LOCKS, AND OTHER
 OPERATING DEVISES ON ACCESSIBLE DOORS
 SHALL HAVE A SHAPE THAT IS EASY TO GRASP
 LEVER-OPERATED MECANISMS, PUSH-TYPE
 MECHANISMS AND U-SHAPED HANDLES ARE
 ACCEPTABLE DESIGNS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-22 Cont ID  
Sent By dpalmer Date 2001-01-22 Time 12:17 Rev Time 0.00
Received By dpalmer Date 2001-01-22 Time 12:17 Sent To  
Notes
2001-01-22 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE PROVIDE CLARIFICATION ON
 ELEC REQ`D FOR BAR/KITCHEN EQUIPMENT
 SHOWN ON E-201. ALL BRANCH CIRCUIT #`S
 ARE TO BE SHOWN. #`S ARE SHOWN BUT NOT
 PANELS? PLEASE SHOW THE PANEL SCHEDULE
 FOR THESE ITEMS. E-201 IS NOT SHOWN AS
 PHASE II.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 3)NOTE: PLEASE SEE REVISED LOAD SUMMARY
 SHOWN ON UPPER LEFT SIDE OF SHEETE-301
 NOTED AS PHASE II. PLEASE NOTE THE ADDED
 AMPERAGES. 17,466 AMPS?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-01-10 Cont ID  
Sent By mcarsill Date 2001-01-10 Time 14:08 Rev Time 0.00
Received By mcarsill Date 2001-01-10 Time 14:08 Sent To  
Notes
2001-01-10 00:00:001) PROVISIONS ARE TO MADE FOR AT LEAST
 TWO HANDICAPPED PERSONS.
 2) PLEASE PROVIDE SEPARATE PLANS AND
 PERMITS FOR FIRE SPRINKLER SYSTEM
 REMODEL. PLEASE PROVIDE REVISED
 HYDRAULIC CALCULATIONS.
 3) PLEASE PROVIDE SEPARATE PLANS AND
 PERMIT FOR FIRE ALARM SYSTEM REMODEL.
 CUT SHEETS, WIRING DIAGRAM, FLOOR PLANS
 AND BATTERY CALCULATIONS ARE TO BE
 PROVIDED.
 4) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION FOR SPACE.
 5) ANY CHANGES IN ELEVATIONS LESS THAN
 21 INCHES SHALL BE BY RAMPS. STAIRS WHEN
 INSTALLED SHALL BE A MINIMUM OF THREE AT
 SEVEN INCHES EACH.
 6) PLEASE IDENTIFY MAIN EXIT WHICH IS
 CAPABLE OF EXITING OF AT LEAST 50
 PERCENT OF THE OCCUPANT LOAD.
 7) CLEARLY IDENTIFY ALL ILLUMINATED
 EXIT SIGNS AND EMERGENCY LIGHTING
 EQUIPMENT IN SPACE.
 8) PLEASE EXPLAIN SINGLE MEANS EGRESS.
 WHY IS THERE NOT A ANOTHER MEANS OF
 EGRESS FROM THE SPACE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-02-02 Cont ID  
Sent By ndenmark Date 2001-02-02 Time 07:56 Rev Time 0.33
Received By ndenmark Date 2001-02-02 Time 07:56 Sent To  
Notes
2001-02-02 00:00:00PHASE ONE ONLY

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-28 Cont ID  
Sent By pschmitz Date 2001-01-28 Time 16:09 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-02-01 00:00:00PLUMBING PLAN REVIEW DENIED
 COMMENTS STD PLBG CODE 94,FACBC 97
 (1) CONTACT PALM BEACH COUNTY HEALTH
 UNIT, DIV OF ENVIROMENTAL HEALTH FOR
 0HEIR PLAN REVIEW AND COMMENTS.
 561-355-4077 X 4534 MIKE LAUDERMILK.
 (2) COMPLY WITH MINM FACILITIES TAB 407,
 ADA REQUIRMENTS FOR ALL ELEMENTS OF THE
 CABARET RESTAURANT.
 END OF COMMENTS 561-659-8096 X 8233
2001-01-28 00:00:00PLUMBING PLAN REVIEWUNSATFACTORY
 (1)

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***